AISLCANALOG-MIB
52 objects
MIB module for SLCs with analog input points.
Imported Objects
| SNMPv2-SMI | enterprises MODULE-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | DisplayString TruthValue |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.539 | Nodeaii | |||
| 1.3.6.1.4.1.539.28 | IdentityaiSLCAnalog | MIB module for SLCs with analog input points. | ||
| 1.3.6.1.4.1.539.28.1 | TableaiSLCAnalogInputTable | not-accessible | current | Table of analog inputs points indexed by point number. Includes description, configuration and status information. |
| 1.3.6.1.4.1.539.28.1.1 | RowaiSLCAnalogInputEntry | not-accessible | current | Entry of aiSLCAnalogInputTable. |
| 1.3.6.1.4.1.539.28.1.1.1 | ColumnaislcainPointNumber | read-only | current | Input point number to which this table row applies. |
| 1.3.6.1.4.1.539.28.1.1.2 | ColumnaislcainScanningEnabled | read-write | current | Enable or disable scanning of the input. |
| 1.3.6.1.4.1.539.28.1.1.3 | ColumnaislcainDescription | read-write | current | Textual description of the point. Maximum length is 80 characters. |
| 1.3.6.1.4.1.539.28.1.1.4 | ColumnaislcainTrapEnable | read-write | current | Enable or disable alarm traps. |
| 1.3.6.1.4.1.539.28.1.1.5 | ColumnaislcainNormalStateTrap | read-write | current | If enabled, transitions from an alarm state to the normal state will generate an SNMP trap or TL1 message. |
| 1.3.6.1.4.1.539.28.1.1.6 | ColumnaislcainHighAlarmSeverity | read-write | current | Severity of the point's alarm state, or notReported(5) if the point does not generate an alarm. |
| 1.3.6.1.4.1.539.28.1.1.7 | ColumnaislcainHighAlarmStateText | read-write | current | Textual description of the point's alarm state. Maximum length is 80 characters. |
| 1.3.6.1.4.1.539.28.1.1.8 | ColumnaislcainLowAlarmSeverity | read-write | current | Severity of the point's alarm state, or notReported(5) if the point does not generate an alarm. |
| 1.3.6.1.4.1.539.28.1.1.9 | ColumnaislcainLowAlarmStateText | read-write | current | Textual description of the point's alarm state. Maximum length is 80 characters. |
| 1.3.6.1.4.1.539.28.1.1.10 | ColumnaislcainNormalStateText | read-write | current | Textual description of the point's normal state. Maximum length is 80 characters. |
| 1.3.6.1.4.1.539.28.1.1.11 | ColumnaislcainUserUnits | read-write | current | The user-defined units for this input (e.g. degC, degF, etc.). |
| 1.3.6.1.4.1.539.28.1.1.12 | ColumnaislcainMinInputmA | read-write | current | The current in mA corresponding to the minimum input in user-defined units. |
| 1.3.6.1.4.1.539.28.1.1.13 | ColumnaislcainMinInputuu | read-write | current | The minimum value in user-defined units corresponding to the minimum input in mA. |
| 1.3.6.1.4.1.539.28.1.1.14 | ColumnaislcainMaxInputmA | read-write | current | The current in mA corresponding to the maximum input in user-defined units. |
| 1.3.6.1.4.1.539.28.1.1.15 | ColumnaislcainMaxInputuu | read-write | current | The maximum value in user-defined units corresponding to the maximum input in mA. |
| 1.3.6.1.4.1.539.28.1.1.16 | ColumnaislcainHighLimitScan | read-write | current | If enabled, the high limit threshold will be checked when the input is scanned. |
| 1.3.6.1.4.1.539.28.1.1.17 | ColumnaislcainHighAlarmThresholduu | read-write | current | The high alarm level in user-defined units. |
| 1.3.6.1.4.1.539.28.1.1.18 | ColumnaislcainHighAlarmThresholdIntervaluu | read-write | current | The high alarm level threshold interval in user-defined units. When the high alarm is active, each time the input rises another interval higher, a new alarm is… |
| 1.3.6.1.4.1.539.28.1.1.19 | ColumnaislcainHighAlarmMinPeriod | read-write | current | The minimum number of seconds the input(s) should be energized when the input exceeds the high alarm threshold. |
| 1.3.6.1.4.1.539.28.1.1.20 | ColumnaislcainHighAlarmHysteresisuu | read-write | current | The amount by which the input must drop below the High Alarm Threshold before the High Alarm will be cleared. |
| 1.3.6.1.4.1.539.28.1.1.21 | ColumnaislcainLowLimitScan | read-write | current | If enabled, the low limit threshold will be checked when the input is scanned. |
| 1.3.6.1.4.1.539.28.1.1.22 | ColumnaislcainLowAlarmThresholduu | read-write | current | The low alarm level in user-defined units. |
| 1.3.6.1.4.1.539.28.1.1.23 | ColumnaislcainLowAlarmThresholdIntervaluu | read-write | current | The low alarm level threshold interval in user-defined units. When the low alarm is active, each time the input drops another interval lower, a new alarm is se… |
| 1.3.6.1.4.1.539.28.1.1.24 | ColumnaislcainLowAlarmMinPeriod | read-write | current | The minimum number of seconds the input(s) should be energized when the input falls below the low alarm threshold. |
| 1.3.6.1.4.1.539.28.1.1.25 | ColumnaislcainLowAlarmHysteresisuu | read-write | current | The amount by which the input must rise above the Low Alarm Threshold before the Low Alarm will be cleared. |
| 1.3.6.1.4.1.539.28.1.1.26 | ColumnaislcainCurrentValueuu | read-only | current | The current input value in user-defined units. |
| 1.3.6.1.4.1.539.28.1.1.27 | ColumnaislcainCurrentValuemA | read-only | current | The current input value in mA. |
| 1.3.6.1.4.1.539.28.1.1.28 | ColumnaislcainLastChangeTime | read-only | current | Textural representation of the time of the most recent output change. 24-hour format YYYY-MM-DD HH:MM:SS. |
| 1.3.6.1.4.1.539.28.1.1.29 | Columnaislcaintl1AccessID | read-write | current | Unique TL1 access identifier for this point. Maximum length is 22 characters. |
| 1.3.6.1.4.1.539.28.1.1.30 | Columnaislcaintl1Provisioned | read-write | current | Enable TL1 management of this point. |
| 1.3.6.1.4.1.539.28.1.1.31 | Columnaislcaintl1AccessIDType | read-write | current | Identifies the point as either an equipment(1) alarm condition or an environmental(2) alarm. |
| 1.3.6.1.4.1.539.28.1.1.32 | Columnaislcaintl1HighAlarmType | read-write | current | String indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters. |
| 1.3.6.1.4.1.539.28.1.1.33 | Columnaislcaintl1HighAlarmMessage | read-write | current | Textual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters. |
| 1.3.6.1.4.1.539.28.1.1.34 | Columnaislcaintl1LowAlarmType | read-write | current | String indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters. |
| 1.3.6.1.4.1.539.28.1.1.35 | Columnaislcaintl1LowAlarmMessage | read-write | current | Textual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters. |
| 1.3.6.1.4.1.539.28.1.1.36 | Columnaislcaintl1HighAlarmNotificationCode | read-write | current | Severity of the point's alarm state. |
| 1.3.6.1.4.1.539.28.1.1.37 | Columnaislcaintl1HighAlarmServiceAffecting | read-write | current | Indicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1). |
| 1.3.6.1.4.1.539.28.1.1.38 | Columnaislcaintl1HighAlarmConditionType | read-write | current | String indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters. |
| 1.3.6.1.4.1.539.28.1.1.39 | Columnaislcaintl1HighAlarmConditionDesc | read-write | current | Textual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters. |
| 1.3.6.1.4.1.539.28.1.1.40 | Columnaislcaintl1LowAlarmNotificationCode | read-write | current | Severity of the point's alarm state. |
| 1.3.6.1.4.1.539.28.1.1.41 | Columnaislcaintl1LowAlarmServiceAffecting | read-write | current | Indicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1). |
| 1.3.6.1.4.1.539.28.1.1.42 | Columnaislcaintl1LowAlarmConditionType | read-write | current | String indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters. |
| 1.3.6.1.4.1.539.28.1.1.43 | Columnaislcaintl1LowAlarmConditionDesc | read-write | current | Textual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters. |
| 1.3.6.1.4.1.539.28.1.1.44 | ColumnaislcainAnalogStatus | read-only | current | The current alarm status of the analog input. |
| 1.3.6.1.4.1.539.28.1.1.45 | ColumnaislcainCurrentStateText | read-only | current | Textual description of the point's current state. This is either aislcainNormalStateText or aislcainAlarmStateText. |
| 1.3.6.1.4.1.539.28.1.1.46 | ColumnaislcainAnalogAlarmState | read-only | current | The point's current alarm state, or normal(5). |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| NonNegativeInteger | INTEGER (0..2147483647) | ||
| PositiveInteger | INTEGER (1..2147483647) |