MIB Viewer

AISLCDISCRETE-MIB

54 objects
MIB module for SLCs with discrete input and output points.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.539Nodeaii
1.3.6.1.4.1.539.24IdentityaiSLCDiscreteMIB module for SLCs with discrete input and output points.
1.3.6.1.4.1.539.24.1TableaiSLCDiscreteInputTablenot-accessiblecurrentTable of discrete input points indexed by point number. Includes description, configuration, and status information.
1.3.6.1.4.1.539.24.1.1RowaiSLCDiscreteInputEntrynot-accessiblecurrentEntry of aiSLCDiscreteInputTable.
1.3.6.1.4.1.539.24.1.1.1ColumnaislcdinPointNumberread-onlycurrentInput point number to which this table row applies.
1.3.6.1.4.1.539.24.1.1.2ColumnaislcdinDescriptionread-writecurrentTextual description of the point. Maximum length is 80 characters.
1.3.6.1.4.1.539.24.1.1.3ColumnaislcdinTrapEnableread-writecurrentEnable or disable alarm traps.
1.3.6.1.4.1.539.24.1.1.4ColumnaislcdinNormalInputread-writecurrentInput that corresponds to the point's normal state.
1.3.6.1.4.1.539.24.1.1.5ColumnaislcdinAlarmSeverityread-writecurrentSeverity of the point's alarm state, or notReported(5) if the point does not generate an alarm.
1.3.6.1.4.1.539.24.1.1.6ColumnaislcdinNormalStateTextread-writecurrentTextual description of the point's normal state. Maximum length is 80 characters.
1.3.6.1.4.1.539.24.1.1.7ColumnaislcdinAlarmStateTextread-writecurrentTextual description of the point's alarm state. Maximum length is 80 characters.
1.3.6.1.4.1.539.24.1.1.8ColumnaislcdinCurrentInputread-onlycurrentThe current input to the point.
1.3.6.1.4.1.539.24.1.1.9ColumnaislcdinLastChangeTimeread-onlycurrentTextual representation of the time of the most recent input change. 24-hour format: YYYY-MM-DD HH:MM:SS.
1.3.6.1.4.1.539.24.1.1.10ColumnaislcdinCurrentStateread-onlycurrentThe point's current alarm state, or normal(5).
1.3.6.1.4.1.539.24.1.1.11ColumnaislcdinCurrentStateTextread-onlycurrentTextual description of the point's current state. This is either aislcdinNormalStateText or aislcdinAlarmStateText.
1.3.6.1.4.1.539.24.1.1.12Columnaislcdintl1AccessIDread-writecurrentUnique TL1 access identifier for this point. Maximum length is 22 characters.
1.3.6.1.4.1.539.24.1.1.13Columnaislcdintl1Provisionedread-writecurrentEnable TL1 management of this point.
1.3.6.1.4.1.539.24.1.1.14Columnaislcdintl1AccessIDTyperead-writecurrentIdentifies the point as either an equipment(1) alarm condition or an environmental(2) alarm.
1.3.6.1.4.1.539.24.1.1.15Columnaislcdintl1NotificationCoderead-writecurrentSeverity of the point's alarm state.
1.3.6.1.4.1.539.24.1.1.16Columnaislcdintl1ServiceAffectingread-writecurrentIndicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcdintl1AccessIDType is equipment(1).
1.3.6.1.4.1.539.24.1.1.17Columnaislcdintl1ConditionTyperead-writecurrentString indicating the type of alarm condition, used only when aislcdintl1AccessIDType is equipment(1). Maximum length is 20 characters.
1.3.6.1.4.1.539.24.1.1.18Columnaislcdintl1ConditionDescriptionread-writecurrentTextual description of the alarm condition, used only when aislcdintl1AccessIDType is equipment(1). Maximum length is 64 characters.
1.3.6.1.4.1.539.24.1.1.19Columnaislcdintl1AlarmTyperead-writecurrentString indicating the type of alarm, used only when aislcdintl1AccessIDType is environmental(2). Maximum length is 10 characters.
1.3.6.1.4.1.539.24.1.1.20Columnaislcdintl1AlarmMessageread-writecurrentTextual description of the alarm, used only when aislcdintl1AccessIDType is environmental(2). Maximum length is 40 characters.
1.3.6.1.4.1.539.24.1.1.21ColumnaislcdinDebounceValueread-writecurrentNumber of 100 msec intervals to wait for the input to stop bouncing.
1.3.6.1.4.1.539.24.2TableaiSLCDiscreteOutputTablenot-accessiblecurrentTable of discrete input points indexed by point number. Includes description, configuration, and status information.
1.3.6.1.4.1.539.24.2.1RowaiSLCDiscreteOutputEntrynot-accessiblecurrentEntry of aiSLCDiscreteOutputTable.
1.3.6.1.4.1.539.24.2.1.1ColumnaislcdoutPointNumberread-onlycurrentOutput point number to which this table row applies.
1.3.6.1.4.1.539.24.2.1.2ColumnaislcdoutDescriptionread-writecurrentTextual description of the point. Maximum length is 80 characters.
1.3.6.1.4.1.539.24.2.1.3ColumnaislcdoutOutputEnableread-writecurrentEnable or disable this point. When the point is disabled, the output is immediately de-energized and remains so regardless of the values of other objects in th…
1.3.6.1.4.1.539.24.2.1.4ColumnaislcdoutNormalOutputnot-accessibledeprecatedDEPRECATED: use aislcdoutAlarmStateOutput.
1.3.6.1.4.1.539.24.2.1.5ColumnaislcdoutMomentaryTimeoutread-writecurrentIf zero, the output will stay in the alarm state until it is returned to the normal state by some other event. If nonzero, this defines the time interval for m…
1.3.6.1.4.1.539.24.2.1.6ColumnaislcdoutCurrentOutputnot-accessibledeprecatedDEPRECATED: use aislcdoutOutput.
1.3.6.1.4.1.539.24.2.1.7Columnaislcdouttl1AccessIDread-writecurrentUnique TL1 access identifier for this point. Maximum length is 22 characters.
1.3.6.1.4.1.539.24.2.1.8ColumnaislcdoutTrapEnableread-writecurrentEnable or disable traps. If enabled, a trap is sent whenever the point changes state.
1.3.6.1.4.1.539.24.2.1.9ColumnaislcdoutAlarmStateOutputread-writecurrentOutput that corresponds to the point's alarm state.
1.3.6.1.4.1.539.24.2.1.10ColumnaislcdoutAlarmSeverityread-writecurrentSeverity of the point's alarm state, or notReported(5) if the point does not generate an alarm.
1.3.6.1.4.1.539.24.2.1.11ColumnaislcdoutNonAlarmStateTextread-writecurrentTextual description of the point's non-alarm state. Maximum length is 80 characters.
1.3.6.1.4.1.539.24.2.1.12ColumnaislcdoutAlarmStateTextread-writecurrentTextual description of the point's alarm state. Maximum length is 80 characters.
1.3.6.1.4.1.539.24.2.1.13ColumnaislcdoutOutputread-writecurrentOn a read operation, this is the current output of the point. On a write operation when the output is controlled by aislcdoutEnergizeExpression, the write is r…
1.3.6.1.4.1.539.24.2.1.14ColumnaislcdoutLastChangeTimeread-onlycurrentTextual representation of the time of the most recent output change. 24-hour format: YYYY-MM-DD HH:MM:SS.
1.3.6.1.4.1.539.24.2.1.15ColumnaislcdoutCurrentStateread-onlycurrentThe point's current alarm state, or normal(5).
1.3.6.1.4.1.539.24.2.1.16ColumnaislcdoutCurrentStateTextread-onlycurrentTextual description of the point's current state. This is either aislcdoutNonAlarmStateText or aislcdoutAlarmStateText.
1.3.6.1.4.1.539.24.2.1.17ColumnaislcdoutEnergizeExpressionread-writecurrentString that describes when this output goes into the energized state, as a function of a discrete input (or analog input for AIscout2). For AIscout, an integer…
1.3.6.1.4.1.539.24.3ScalaraislcdiscPowerSupplyStatusread-onlycurrentStatus of the power supply. okay(1) or trouble(2). When the SLC is booted, this indicates okay(1) until the software determines the correct status.
1.3.6.1.4.1.539.24.4ScalaraislcdiscPowerSupplyAStatusread-onlycurrentStatus of the 'A' power supply.
1.3.6.1.4.1.539.24.5ScalaraislcdiscPowerSupplyBStatusread-onlycurrentStatus of the 'B' power supply.
1.3.6.1.4.1.539.24.6ScalaraislcdiscFanStatusread-onlycurrentStatus of the fan unit.
1.3.6.1.4.1.539.24.7Scalaraislcdisc5VPowerSupplyAStatusread-onlycurrentStatus of the 'A' 5V power supply.
1.3.6.1.4.1.539.24.8Scalaraislcdisc5VPowerSupplyBStatusread-onlycurrentStatus of the 'B' 5V power supply.
1.3.6.1.4.1.539.24.9ScalaraislcdiscFiber1TransmitterStatusread-onlycurrentStatus of the first fiber port's transmitter.
1.3.6.1.4.1.539.24.10ScalaraislcdiscFiber2TransmitterStatusread-onlycurrentStatus of the second fiber port's transmitter.
1.3.6.1.4.1.539.24.11ScalaraislcdiscAnalogInputPowerSupplyStatusread-onlycurrentStatus of the analog input power supply fuse.
Type Definitions
NameSyntaxStatusDescription
PositiveIntegerINTEGER (1..2147483647)