ALPHA-INVERTER-SYS-MIB
60 objects
This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System.
Imported Objects
| ALPHA-RESOURCE-MIB | ScaledNumber simple |
| SNMPv2-CONF | MODULE-COMPLIANCE OBJECT-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY OBJECT-TYPE |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.7309.5.3.3 | IdentityinverterSystem | This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System. | ||
| 1.3.6.1.4.1.7309.5.3.3.1 | ScalarinvTotalAcOutputPowerVa | read-only | current | The total output power summed from all the phases (VA). |
| 1.3.6.1.4.1.7309.5.3.3.2 | ScalarinvSysAverageLoadingOfInstalledPowerVa | read-only | current | The average output loading of all phases (% VA). |
| 1.3.6.1.4.1.7309.5.3.3.3 | ScalarinvSysAverageDcInputToOutputPowerRatio | read-only | current | The percentage of the output that is taken from the DC input (%). |
| 1.3.6.1.4.1.7309.5.3.3.4 | ScalarinvSysSystemMode | read-only | current | The mode of the system. See manual for decoding the number. |
| 1.3.6.1.4.1.7309.5.3.3.5 | ScalarinvSysPhase1OutputPowerVa | read-only | current | The total output power from the phase 1 (VA). |
| 1.3.6.1.4.1.7309.5.3.3.6 | ScalarinvSysPhase2OutputPowerVa | read-only | current | The total output power from phase 2 (VA). |
| 1.3.6.1.4.1.7309.5.3.3.7 | ScalarinvSysPhase3OutputPowerVa | read-only | current | The total output power from the phase 3 (VA). |
| 1.3.6.1.4.1.7309.5.3.3.8 | ScalarinvSysAverageOutputVoltageMeasured | read-only | current | The average output voltage of all the phases (V). |
| 1.3.6.1.4.1.7309.5.3.3.9 | ScalarinvSysEnabledDisconnects | read-only | current | The number of disconnects that are enabled. |
| 1.3.6.1.4.1.7309.5.3.3.10 | ScalarinvSysActivatedDisconnects | read-only | current | The number of disconnects that are active. |
| 1.3.6.1.4.1.7309.5.3.3.11 | ScalarinvSysTotalDCInputCurrent | read-only | current | Total DC input current for the inverter system (A). |
| 1.3.6.1.4.1.7309.5.3.3.12 | ScalarinvSysAverageDcInputVoltage | read-only | current | Average DC input voltage reading for the inverter system (V). |
| 1.3.6.1.4.1.7309.5.3.3.13 | ScalarinvSysTotalDcInputPower | read-only | current | Total DC input power reading for the inverter system (W). |
| 1.3.6.1.4.1.7309.5.3.3.14 | ScalarinvSysSystemOnBypass | read-only | current | True when the bypass switch is on. The AC input from the grid is fed to the AC load directly. |
| 1.3.6.1.4.1.7309.5.3.3.18 | ScalarinvSysTotalAcInputPowerVa | read-only | current | Total AC input power reading of the Inverter System (VA). |
| 1.3.6.1.4.1.7309.5.3.3.80 | NodephaseGroup | |||
| 1.3.6.1.4.1.7309.5.3.3.80.1 | ScalarinvSysAcPhaseCount | read-only | current | |
| 1.3.6.1.4.1.7309.5.3.3.80.2 | TableinvSysAcPhaseTable | not-accessible | current | |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1 | RowinvSysAcPhaseEntry | not-accessible | current | |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.1 | ColumninvSysAcPhaseAcOutputPowerVa | read-only | current | The power of the AC output (VA). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.2 | ColumninvSysAcPhaseOutputVoltageMeasured | read-only | current | The output voltage of the phase or inverter (V). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.3 | ColumninvSysAcPhaseOutputCurrent | read-only | current | The output current of the phase or inverter (A). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.4 | ColumninvSysAcPhaseFrequency | read-only | current | Frequency to which the inverters will lock (Hz). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.5 | ColumninvSysAcPhaseLoadingOfInstalledPowerVa | read-only | current | The ratio of output load to installed power (%VA). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.6 | ColumninvSysAcPhaseNumberOfModulesOn | read-only | current | The number of inverters that are On and can deliver power. |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.7 | ColumninvSysAcPhaseLoadingOfInstalledPowerWatts | read-only | current | The ratio of output load to installed power (% W). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.8 | ColumninvSysAcPhaseDcInputToOutputPowerRatioMeasured | read-only | current | The measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately. |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.9 | ColumninvSysAcPhaseAcInputPowerWatts | read-only | current | The power drawn by the AC input (W). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.10 | ColumninvSysAcPhaseAcInputPowerVa | read-only | current | The power drawn by the AC input (VA). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.11 | ColumninvSysAcPhaseAcOutputPowerWatts | read-only | current | The power of the AC output (W). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.12 | ColumninvSysAcPhaseDCInputPowerWatts | read-only | current | The power drawn by the DC input (W). |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.13 | ColumninvSysAcPhaseNumberOfRedundantModulesMeasured | read-only | current | Number of inverters currently unneeded by the load. |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.14 | ColumninvSysAcPhaseNumberOfModulesDetected | read-only | current | The number of inverters assigned to this phase that the T2S has detected. |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.15 | ColumninvSysAcPhaseNumberOfModulesOff | read-only | current | The number of inverters that are manually turned off. |
| 1.3.6.1.4.1.7309.5.3.3.80.2.1.16 | ColumninvSysAcPhaseNumberOfModulesFailed | read-only | current | The number of inverters that have failed and cannot deliver power. |
| 1.3.6.1.4.1.7309.5.3.3.81 | NodeacInputGroup | |||
| 1.3.6.1.4.1.7309.5.3.3.81.1 | ScalarinvSysAcInputCount | read-only | current | |
| 1.3.6.1.4.1.7309.5.3.3.81.2 | TableinvSysAcInputTable | not-accessible | current | |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1 | RowinvSysAcInputEntry | not-accessible | current | |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.1 | ColumninvSysAcInputInputVoltage | read-only | current | The input voltage of the inverter or group (V). |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.2 | ColumninvSysAcInputInputCurrent | read-only | current | The input current of the inverter or group (A). |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.3 | ColumninvSysAcInputFrequency | read-only | current | The frequency of the input voltage and current of the inverter or group (Hz). |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.4 | ColumninvSysAcInputAcInputPowerVa | read-only | current | The power drawn by the AC input (VA). |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.5 | ColumninvSysAcInputNumberOfModulesOn | read-only | current | The number of inverters that are On and can deliver power. |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.6 | ColumninvSysAcInputAcInputPowerWatts | read-only | current | The power drawn by the AC input (W). |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.7 | ColumninvSysAcInputNumberOfModulesDetected | read-only | current | The number of inverters assigned to this phase that the T2S has detected. |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.8 | ColumninvSysAcInputNumberOfModulesOff | read-only | current | The number of inverters that are manually turned off. |
| 1.3.6.1.4.1.7309.5.3.3.81.2.1.9 | ColumninvSysAcInputNumberOfModulesFailed | read-only | current | The number of inverters that have failed and cannot deliver power. |
| 1.3.6.1.4.1.7309.5.3.3.82 | NodedcInputGroup | |||
| 1.3.6.1.4.1.7309.5.3.3.82.1 | ScalarinvSysDcInputCount | read-only | current | |
| 1.3.6.1.4.1.7309.5.3.3.82.2 | TableinvSysDcInputTable | not-accessible | current | |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1 | RowinvSysDcInputEntry | not-accessible | current | |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.1 | ColumninvSysDcInputInputVoltage | read-only | current | The input voltage of the inverter or group (V). |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.2 | ColumninvSysDcInputInputCurrent | read-only | current | The input current of the inverter or group (A). |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.3 | ColumninvSysDcInputDcInputPowerWatts | read-only | current | The power drawn by the DC input (W). |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.4 | ColumninvSysDcInputNumberOfModulesOn | read-only | current | The number of inverters that are On and can deliver power. |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.5 | ColumninvSysDcInputNumberOfModulesOff | read-only | current | The number of inverters that are manually turned off. |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.6 | ColumninvSysDcInputNumberOfModulesFailed | read-only | current | The number of inverters that have failed and cannot deliver power. |
| 1.3.6.1.4.1.7309.5.3.3.82.2.1.7 | ColumninvSysDcInputNumberOfModulesDetected | read-only | current | The number of inverters assigned to this phase that the T2S has detected. |