MIB Viewer

ALPHA-INVERTER-SYS-MIB

60 objects
This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System.
Imported Objects
ALPHA-RESOURCE-MIBScaledNumber simple
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMIMODULE-IDENTITY OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.7309.5.3.3IdentityinverterSystemThis MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System.
1.3.6.1.4.1.7309.5.3.3.1ScalarinvTotalAcOutputPowerVaread-onlycurrentThe total output power summed from all the phases (VA).
1.3.6.1.4.1.7309.5.3.3.2ScalarinvSysAverageLoadingOfInstalledPowerVaread-onlycurrentThe average output loading of all phases (% VA).
1.3.6.1.4.1.7309.5.3.3.3ScalarinvSysAverageDcInputToOutputPowerRatioread-onlycurrentThe percentage of the output that is taken from the DC input (%).
1.3.6.1.4.1.7309.5.3.3.4ScalarinvSysSystemModeread-onlycurrentThe mode of the system. See manual for decoding the number.
1.3.6.1.4.1.7309.5.3.3.5ScalarinvSysPhase1OutputPowerVaread-onlycurrentThe total output power from the phase 1 (VA).
1.3.6.1.4.1.7309.5.3.3.6ScalarinvSysPhase2OutputPowerVaread-onlycurrentThe total output power from phase 2 (VA).
1.3.6.1.4.1.7309.5.3.3.7ScalarinvSysPhase3OutputPowerVaread-onlycurrentThe total output power from the phase 3 (VA).
1.3.6.1.4.1.7309.5.3.3.8ScalarinvSysAverageOutputVoltageMeasuredread-onlycurrentThe average output voltage of all the phases (V).
1.3.6.1.4.1.7309.5.3.3.9ScalarinvSysEnabledDisconnectsread-onlycurrentThe number of disconnects that are enabled.
1.3.6.1.4.1.7309.5.3.3.10ScalarinvSysActivatedDisconnectsread-onlycurrentThe number of disconnects that are active.
1.3.6.1.4.1.7309.5.3.3.11ScalarinvSysTotalDCInputCurrentread-onlycurrentTotal DC input current for the inverter system (A).
1.3.6.1.4.1.7309.5.3.3.12ScalarinvSysAverageDcInputVoltageread-onlycurrentAverage DC input voltage reading for the inverter system (V).
1.3.6.1.4.1.7309.5.3.3.13ScalarinvSysTotalDcInputPowerread-onlycurrentTotal DC input power reading for the inverter system (W).
1.3.6.1.4.1.7309.5.3.3.14ScalarinvSysSystemOnBypassread-onlycurrentTrue when the bypass switch is on. The AC input from the grid is fed to the AC load directly.
1.3.6.1.4.1.7309.5.3.3.18ScalarinvSysTotalAcInputPowerVaread-onlycurrentTotal AC input power reading of the Inverter System (VA).
1.3.6.1.4.1.7309.5.3.3.80NodephaseGroup
1.3.6.1.4.1.7309.5.3.3.80.1ScalarinvSysAcPhaseCountread-onlycurrent
1.3.6.1.4.1.7309.5.3.3.80.2TableinvSysAcPhaseTablenot-accessiblecurrent
1.3.6.1.4.1.7309.5.3.3.80.2.1RowinvSysAcPhaseEntrynot-accessiblecurrent
1.3.6.1.4.1.7309.5.3.3.80.2.1.1ColumninvSysAcPhaseAcOutputPowerVaread-onlycurrentThe power of the AC output (VA).
1.3.6.1.4.1.7309.5.3.3.80.2.1.2ColumninvSysAcPhaseOutputVoltageMeasuredread-onlycurrentThe output voltage of the phase or inverter (V).
1.3.6.1.4.1.7309.5.3.3.80.2.1.3ColumninvSysAcPhaseOutputCurrentread-onlycurrentThe output current of the phase or inverter (A).
1.3.6.1.4.1.7309.5.3.3.80.2.1.4ColumninvSysAcPhaseFrequencyread-onlycurrentFrequency to which the inverters will lock (Hz).
1.3.6.1.4.1.7309.5.3.3.80.2.1.5ColumninvSysAcPhaseLoadingOfInstalledPowerVaread-onlycurrentThe ratio of output load to installed power (%VA).
1.3.6.1.4.1.7309.5.3.3.80.2.1.6ColumninvSysAcPhaseNumberOfModulesOnread-onlycurrentThe number of inverters that are On and can deliver power.
1.3.6.1.4.1.7309.5.3.3.80.2.1.7ColumninvSysAcPhaseLoadingOfInstalledPowerWattsread-onlycurrentThe ratio of output load to installed power (% W).
1.3.6.1.4.1.7309.5.3.3.80.2.1.8ColumninvSysAcPhaseDcInputToOutputPowerRatioMeasuredread-onlycurrentThe measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately.
1.3.6.1.4.1.7309.5.3.3.80.2.1.9ColumninvSysAcPhaseAcInputPowerWattsread-onlycurrentThe power drawn by the AC input (W).
1.3.6.1.4.1.7309.5.3.3.80.2.1.10ColumninvSysAcPhaseAcInputPowerVaread-onlycurrentThe power drawn by the AC input (VA).
1.3.6.1.4.1.7309.5.3.3.80.2.1.11ColumninvSysAcPhaseAcOutputPowerWattsread-onlycurrentThe power of the AC output (W).
1.3.6.1.4.1.7309.5.3.3.80.2.1.12ColumninvSysAcPhaseDCInputPowerWattsread-onlycurrentThe power drawn by the DC input (W).
1.3.6.1.4.1.7309.5.3.3.80.2.1.13ColumninvSysAcPhaseNumberOfRedundantModulesMeasuredread-onlycurrentNumber of inverters currently unneeded by the load.
1.3.6.1.4.1.7309.5.3.3.80.2.1.14ColumninvSysAcPhaseNumberOfModulesDetectedread-onlycurrentThe number of inverters assigned to this phase that the T2S has detected.
1.3.6.1.4.1.7309.5.3.3.80.2.1.15ColumninvSysAcPhaseNumberOfModulesOffread-onlycurrentThe number of inverters that are manually turned off.
1.3.6.1.4.1.7309.5.3.3.80.2.1.16ColumninvSysAcPhaseNumberOfModulesFailedread-onlycurrentThe number of inverters that have failed and cannot deliver power.
1.3.6.1.4.1.7309.5.3.3.81NodeacInputGroup
1.3.6.1.4.1.7309.5.3.3.81.1ScalarinvSysAcInputCountread-onlycurrent
1.3.6.1.4.1.7309.5.3.3.81.2TableinvSysAcInputTablenot-accessiblecurrent
1.3.6.1.4.1.7309.5.3.3.81.2.1RowinvSysAcInputEntrynot-accessiblecurrent
1.3.6.1.4.1.7309.5.3.3.81.2.1.1ColumninvSysAcInputInputVoltageread-onlycurrentThe input voltage of the inverter or group (V).
1.3.6.1.4.1.7309.5.3.3.81.2.1.2ColumninvSysAcInputInputCurrentread-onlycurrentThe input current of the inverter or group (A).
1.3.6.1.4.1.7309.5.3.3.81.2.1.3ColumninvSysAcInputFrequencyread-onlycurrentThe frequency of the input voltage and current of the inverter or group (Hz).
1.3.6.1.4.1.7309.5.3.3.81.2.1.4ColumninvSysAcInputAcInputPowerVaread-onlycurrentThe power drawn by the AC input (VA).
1.3.6.1.4.1.7309.5.3.3.81.2.1.5ColumninvSysAcInputNumberOfModulesOnread-onlycurrentThe number of inverters that are On and can deliver power.
1.3.6.1.4.1.7309.5.3.3.81.2.1.6ColumninvSysAcInputAcInputPowerWattsread-onlycurrentThe power drawn by the AC input (W).
1.3.6.1.4.1.7309.5.3.3.81.2.1.7ColumninvSysAcInputNumberOfModulesDetectedread-onlycurrentThe number of inverters assigned to this phase that the T2S has detected.
1.3.6.1.4.1.7309.5.3.3.81.2.1.8ColumninvSysAcInputNumberOfModulesOffread-onlycurrentThe number of inverters that are manually turned off.
1.3.6.1.4.1.7309.5.3.3.81.2.1.9ColumninvSysAcInputNumberOfModulesFailedread-onlycurrentThe number of inverters that have failed and cannot deliver power.
1.3.6.1.4.1.7309.5.3.3.82NodedcInputGroup
1.3.6.1.4.1.7309.5.3.3.82.1ScalarinvSysDcInputCountread-onlycurrent
1.3.6.1.4.1.7309.5.3.3.82.2TableinvSysDcInputTablenot-accessiblecurrent
1.3.6.1.4.1.7309.5.3.3.82.2.1RowinvSysDcInputEntrynot-accessiblecurrent
1.3.6.1.4.1.7309.5.3.3.82.2.1.1ColumninvSysDcInputInputVoltageread-onlycurrentThe input voltage of the inverter or group (V).
1.3.6.1.4.1.7309.5.3.3.82.2.1.2ColumninvSysDcInputInputCurrentread-onlycurrentThe input current of the inverter or group (A).
1.3.6.1.4.1.7309.5.3.3.82.2.1.3ColumninvSysDcInputDcInputPowerWattsread-onlycurrentThe power drawn by the DC input (W).
1.3.6.1.4.1.7309.5.3.3.82.2.1.4ColumninvSysDcInputNumberOfModulesOnread-onlycurrentThe number of inverters that are On and can deliver power.
1.3.6.1.4.1.7309.5.3.3.82.2.1.5ColumninvSysDcInputNumberOfModulesOffread-onlycurrentThe number of inverters that are manually turned off.
1.3.6.1.4.1.7309.5.3.3.82.2.1.6ColumninvSysDcInputNumberOfModulesFailedread-onlycurrentThe number of inverters that have failed and cannot deliver power.
1.3.6.1.4.1.7309.5.3.3.82.2.1.7ColumninvSysDcInputNumberOfModulesDetectedread-onlycurrentThe number of inverters assigned to this phase that the T2S has detected.