ASETEK-RACKCDU-SMI-V1-MIB-V16
151 objects
No module-level DESCRIPTION found.
Imported Objects
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.39829 | Nodeasetek | |||
| 1.3.6.1.4.1.39829.1 | NoderackCDU | |||
| 1.3.6.1.4.1.39829.1.0 | Nodetraps | |||
| 1.3.6.1.4.1.39829.1.1 | Nodeproduct | |||
| 1.3.6.1.4.1.39829.1.1.1 | Scalarname | read-write | mandatory | Product name. |
| 1.3.6.1.4.1.39829.1.1.2 | Scalarversion | read-only | mandatory | Software version. |
| 1.3.6.1.4.1.39829.1.1.3 | Scalardate | read-only | mandatory | Software revision date. |
| 1.3.6.1.4.1.39829.1.1.4 | ScalarrackNumber | read-write | mandatory | RackCDU number. |
| 1.3.6.1.4.1.39829.1.1.5 | Scalardescription | read-write | mandatory | RackCDU description. |
| 1.3.6.1.4.1.39829.1.1.6 | Scalarstatus | read-only | mandatory | The overall status of the RackCDU. Status is evaluated based on the notification settings. If a noticiation has been disabled it will not be included in the ov… |
| 1.3.6.1.4.1.39829.1.2 | Nodesetup | |||
| 1.3.6.1.4.1.39829.1.2.1 | TablenotifyTable | not-accessible | mandatory | Table of settings used to setup notifications. |
| 1.3.6.1.4.1.39829.1.2.1.1 | RownotifyEntry | not-accessible | mandatory | Single notify entry containing notification receiver info. |
| 1.3.6.1.4.1.39829.1.2.1.1.1 | ColumnnotifyReceiverNumber | read-only | mandatory | Index of notification receiver. |
| 1.3.6.1.4.1.39829.1.2.1.1.2 | ColumnnotifyEnabled | read-write | mandatory | Indicates if this notify entry is enabled or not. |
| 1.3.6.1.4.1.39829.1.2.1.1.3 | ColumnnotifyReceiverIPAddress | read-write | mandatory | Notification receiver IP address. |
| 1.3.6.1.4.1.39829.1.2.1.1.4 | ColumnnotifyCommunity | read-write | mandatory | Notification community to be used by agent to send trap. |
| 1.3.6.1.4.1.39829.1.3 | Nodemeasurements | |||
| 1.3.6.1.4.1.39829.1.3.100 | ScalartemperatureFacilityIn | read-only | mandatory | The temperature of the water going into the RackCDU on the Facility side (cold). |
| 1.3.6.1.4.1.39829.1.3.101 | ScalartemperatureFacilityOut | read-only | mandatory | The temperature of the water going out of the RackCDU on the Facility side (hot). |
| 1.3.6.1.4.1.39829.1.3.102 | ScalartemperatureServerIn | read-only | mandatory | The temperature of the water going into the servers node (cold). |
| 1.3.6.1.4.1.39829.1.3.103 | ScalartemperatureServerOut | read-only | mandatory | The temperature of the water going out of the servers node (hot). |
| 1.3.6.1.4.1.39829.1.3.104 | ScalartemperatureAmbient | read-only | obsolete | The temperature of the ambient air close to the RackCDU. |
| 1.3.6.1.4.1.39829.1.3.105 | ScalarpressureServer | read-only | mandatory | The pressure inside the RackCDU on the server side. |
| 1.3.6.1.4.1.39829.1.3.106 | ScalarpressureFacility | read-only | mandatory | The pressure inside the RackCDU on the facility side. |
| 1.3.6.1.4.1.39829.1.3.107 | ScalarserverLeak | read-only | mandatory | Boolean indication of whether the RackCDU has detected a leak in the system. |
| 1.3.6.1.4.1.39829.1.3.108 | ScalarserverLevel | read-only | mandatory | Boolean indication of whether the RackCDU has detected a low level of cooleant. |
| 1.3.6.1.4.1.39829.1.3.109 | ScalarflowFacility | read-only | mandatory | The flow of the cooleant on the facility side. |
| 1.3.6.1.4.1.39829.1.3.110 | Scalarheatload | read-only | mandatory | The heatload of the cooleant on the facility side. Can be averaged from e.g. 1 to 28800 (24 hours) sec. |
| 1.3.6.1.4.1.39829.1.3.111 | ScalarcontrollerOut | read-only | mandatory | The controller output. |
| 1.3.6.1.4.1.39829.1.4 | Nodenetwork | |||
| 1.3.6.1.4.1.39829.1.4.91 | ScalaripStoreFlash | read-write | mandatory | store settings to Flash. |
| 1.3.6.1.4.1.39829.1.4.92 | ScalarmodeOfOperation | read-write | mandatory | Mode of operation of ControlBox, can be agent or master. |
| 1.3.6.1.4.1.39829.1.4.93 | ScalaripAddr | read-write | mandatory | IP address of ControlBox. |
| 1.3.6.1.4.1.39829.1.4.94 | ScalarpriDNS | read-write | mandatory | Primary DNS address of ControlBox. |
| 1.3.6.1.4.1.39829.1.4.95 | ScalarsecDNS | read-write | mandatory | Secondary DNS address of ControlBox. |
| 1.3.6.1.4.1.39829.1.4.96 | ScalarnetMask | read-write | mandatory | Netmask of ControlBox. |
| 1.3.6.1.4.1.39829.1.4.97 | Scalargateway | read-write | mandatory | Gateway of ControlBox. |
| 1.3.6.1.4.1.39829.1.4.98 | ScalaripSrc | read-write | mandatory | IP address source of ControlBox, eg. static or dhcp. |
| 1.3.6.1.4.1.39829.1.4.99 | ScalaripReboot | read-write | mandatory | IP address reboot. |
| 1.3.6.1.4.1.39829.1.5 | Nodecontroller | |||
| 1.3.6.1.4.1.39829.1.5.80 | ScalargainProportional | read-write | mandatory | Proportional gain in PID controller. |
| 1.3.6.1.4.1.39829.1.5.81 | ScalargainIntegral | read-write | mandatory | Integral gain in PID controller. |
| 1.3.6.1.4.1.39829.1.5.82 | ScalargainDifferential | read-write | mandatory | Differential gain in PID controller. |
| 1.3.6.1.4.1.39829.1.5.83 | ScalardeltaOutMax | read-write | mandatory | Maximum delta output from controller. |
| 1.3.6.1.4.1.39829.1.5.84 | ScalarlimitPwmMax | read-write | mandatory | Maximum PWM output. |
| 1.3.6.1.4.1.39829.1.5.85 | ScalarlimitPwmMin | read-write | mandatory | Minimum PWM output. |
| 1.3.6.1.4.1.39829.1.5.86 | ScalarsetpointFacilityOut | read-write | mandatory | Setpoint for Facility Out Temperature. |
| 1.3.6.1.4.1.39829.1.5.87 | ScalarcontrollerOutAlpha | read-write | mandatory | Controller Out Alpha - damping factor of output. |
| 1.3.6.1.4.1.39829.1.6 | Nodeunits | |||
| 1.3.6.1.4.1.39829.1.6.70 | ScalarfluidHeatCapacity | read-write | mandatory | Heat Capacity of the liquid coolant utilized in the facility loop. |
| 1.3.6.1.4.1.39829.1.6.71 | ScalarheatAverageFactor | read-write | mandatory | The time frame of which the heat load is averaged. A short time frame make the heat load sensative to small changes is temperature and flow which results in a … |
| 1.3.6.1.4.1.39829.1.6.72 | ScalarharnessVersion | read-write | mandatory | Must be set to the harness version utilized by the RackCDU. The harness version may affect the functionality of the RackCDU and it it therefor important that t… |
| 1.3.6.1.4.1.39829.1.7 | Nodenotifications | |||
| 1.3.6.1.4.1.39829.1.7.150 | ScalarsnmpTrapsAlarmEnable | read-write | mandatory | Enable SNMP Alarm traps. |
| 1.3.6.1.4.1.39829.1.7.151 | ScalarsnmpTrapsWarningEnable | read-write | mandatory | Enable SNMP Warning traps. |
| 1.3.6.1.4.1.39829.1.7.152 | ScalarsmtpTrapsAlarmEnable | read-write | mandatory | Enable SMTP Alarm traps. |
| 1.3.6.1.4.1.39829.1.7.153 | ScalarsmtpTrapsWarningEnable | read-write | mandatory | Enable SMTP Warning traps. |
| 1.3.6.1.4.1.39829.1.7.154 | ScalarwarningMinFi | read-write | mandatory | Set Facility In Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.155 | ScalarwarningMinEnableFi | read-write | mandatory | Enable Facility In Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.156 | ScalarwarningMaxFi | read-write | mandatory | Set Facility In Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.157 | ScalarwarningMaxEnableFi | read-write | mandatory | Enable Facility In Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.158 | ScalaralarmMinFi | read-write | mandatory | Set Facility In Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.159 | ScalaralarmMinEnableFi | read-write | mandatory | Enable Facility In Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.160 | ScalaralarmMaxFi | read-write | mandatory | Set Facility In Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.161 | ScalaralarmMaxEnableFi | read-write | mandatory | Enable Facility In Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.162 | ScalarwarningMinFo | read-write | mandatory | Set Facility Out Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.163 | ScalarwarningMinEnableFo | read-write | mandatory | Enable Facility Out Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.164 | ScalarwarningMaxFo | read-write | mandatory | Set Facility Out Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.165 | ScalarwarningMaxEnableFo | read-write | mandatory | Enable Facility Out Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.166 | ScalaralarmMinFo | read-write | mandatory | Set Facility Out Min alarm level. |
| 1.3.6.1.4.1.39829.1.7.167 | ScalaralarmMinEnableFo | read-write | mandatory | Enable Facility Out Min alarm level. |
| 1.3.6.1.4.1.39829.1.7.168 | ScalaralarmMaxFo | read-write | mandatory | Set Facility Out Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.169 | ScalaralarmMaxEnableFo | read-write | mandatory | Enable Facility Out Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.170 | ScalarwarningMinSi | read-write | mandatory | Set Server In Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.171 | ScalarwarningMinEnableSi | read-write | mandatory | Enable Server In Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.172 | ScalarwarningMaxSi | read-write | mandatory | Set Server In Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.173 | ScalarwarningMaxEnableSi | read-write | mandatory | Enable Server In Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.174 | ScalaralarmMinSi | read-write | mandatory | Set Server In Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.175 | ScalaralarmMinEnableSi | read-write | mandatory | Enable Server In Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.176 | ScalaralarmMaxSi | read-write | mandatory | Set Server In Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.177 | ScalaralarmMaxEnableSi | read-write | mandatory | Enable Server In Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.178 | ScalarwarningMinSo | read-write | mandatory | Set Server Out Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.179 | ScalarwarningMinEnableSo | read-write | mandatory | Enable Server Out Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.180 | ScalarwarningMaxSo | read-write | mandatory | Set Server Out Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.181 | ScalarwarningMaxEnableSo | read-write | mandatory | Enable Server Out Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.182 | ScalaralarmMinSo | read-write | mandatory | Set Server Out Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.183 | ScalaralarmMinEnableSo | read-write | mandatory | Enable Server Out Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.184 | ScalaralarmMaxSo | read-write | mandatory | Set Server Out Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.185 | ScalaralarmMaxEnableSo | read-write | mandatory | Enable Server Out Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.186 | ScalarwarningMinFlow | read-write | mandatory | Set Flow Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.187 | ScalarwarningMinEnableFlow | read-write | mandatory | Enable Flow Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.188 | ScalarwarningMaxFlow | read-write | mandatory | Set Flow Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.189 | ScalarwarningMaxEnableFlow | read-write | mandatory | Enable Flow Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.190 | ScalaralarmMinFlow | read-write | mandatory | Set Flow Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.191 | ScalaralarmMinEnableFlow | read-write | mandatory | Enable Flow Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.192 | ScalaralarmMaxFlow | read-write | mandatory | Set Flow Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.193 | ScalaralarmMaxEnableFlow | read-write | mandatory | Enable Flow Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.194 | ScalarwarningMinPressureServer | read-write | mandatory | Set Server Pressure Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.195 | ScalarwarningMinEnablePressureServer | read-write | mandatory | Enable Server Pressure Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.196 | ScalarwarningMaxPressureServer | read-write | mandatory | Set Server Pressure Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.197 | ScalarwarningMaxEnablePressureServer | read-write | mandatory | Enable Server Pressure Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.198 | ScalaralarmMinPressureServer | read-write | mandatory | Set Server Pressure Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.199 | ScalaralarmMinEnablePressureServer | read-write | mandatory | Enable Server Pressure Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.200 | ScalaralarmMaxPressureServer | read-write | mandatory | Set Server Pressure Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.201 | ScalaralarmMaxEnablePressureServer | read-write | mandatory | Enable Server Pressure Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.202 | ScalarwarningMinPressureFacility | read-write | mandatory | Set Facility Pressure Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.203 | ScalarwarningMinEnablePressureFacility | read-write | mandatory | Enable Facility Pressure Min Warning level. |
| 1.3.6.1.4.1.39829.1.7.204 | ScalarwarningMaxPressureFacility | read-write | mandatory | Set Facility Pressure Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.205 | ScalarwarningMaxEnablePressureFacility | read-write | mandatory | Enable Facility Pressure Max Warning level. |
| 1.3.6.1.4.1.39829.1.7.206 | ScalaralarmMinPressureFacility | read-write | mandatory | Set Facility Pressure Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.207 | ScalaralarmMinEnablePressureFacility | read-write | mandatory | Enable Facility Pressure Min Alarm level. |
| 1.3.6.1.4.1.39829.1.7.208 | ScalaralarmMaxPressureFacility | read-write | mandatory | Set Facility Pressure Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.209 | ScalaralarmMaxEnablePressureFacility | read-write | mandatory | Enable Facility Pressure Max Alarm level. |
| 1.3.6.1.4.1.39829.1.7.210 | ScalaralarmEnableLeak | read-write | mandatory | Enable leak detection. |
| 1.3.6.1.4.1.39829.1.7.211 | ScalaralarmEnableLevel | read-write | mandatory | Enable low liquid level. |
| 1.3.6.1.4.1.39829.1.8 | Nodeconformance | |||
| 1.3.6.1.4.1.39829.1.8.1 | NodecduProdGroup | |||
| 1.3.6.1.4.1.39829.1.8.2 | NodecduSetupGroup | |||
| 1.3.6.1.4.1.39829.1.8.3 | NodecduMeasGroup | |||
| 1.3.6.1.4.1.39829.1.8.4 | NodecduMeasGroupRev2 | |||
| 1.3.6.1.4.1.39829.1.8.5 | NodecduNetGroup | |||
| 1.3.6.1.4.1.39829.1.8.6 | NodecduCntlGroup | |||
| 1.3.6.1.4.1.39829.1.8.7 | NodecduUnitGroup | |||
| 1.3.6.1.4.1.39829.1.8.8 | NodecduNotifyGroup | |||
| 1.3.6.1.4.1.39829.1.8.9 | NodecduTrapGroup | |||
| 1.3.6.1.4.1.39829.1.8.10 | NodecduCompliances | |||
| 1.3.6.1.4.1.39829.1.8.11 | NodecduEventGroup | |||
| 1.3.6.1.4.1.39829.1.8.12 | NodecduTrapGroupRev2 | |||
| 1.3.6.1.4.1.39829.1.8.13 | NodecduCompliancesRev2 | |||
| 1.3.6.1.4.1.39829.1.9 | NodeeventDescriptors | |||
| 1.3.6.1.4.1.39829.1.9.1 | ScalareventDescription | read-only | mandatory | Text which provide the user with a corrective action in case of a warning or alarm trap. IMPORTANT: Must only be used in traps! Any other use of this object is… |
| 1.3.6.1.4.1.39829.1.9.2 | ScalareventValue | read-only | mandatory | Event value placeholder sent with generic traps where the unit of the value can be different. IMPORTANT: Must only be used in traps! Any other use of this obje… |
| 1.3.6.1.4.1.39829.1.500 | NodealarmNotify | Trap alarm notification information for the SNMP Manager (obsolete). | ||
| 1.3.6.1.4.1.39829.1.501 | NodewarningNotify | Trap warning notification information for the SNMP Manager (obsolete). | ||
| 1.3.6.1.4.1.39829.1.504 | NodefacilitySupplyWarning | Facility supply temperature warning. | ||
| 1.3.6.1.4.1.39829.1.505 | NodefacilityReturnWarning | Facility return temperature warning. | ||
| 1.3.6.1.4.1.39829.1.506 | NodeserverSupplyWarning | Server supply temperature warning. | ||
| 1.3.6.1.4.1.39829.1.507 | NodeserverReturnWarning | Server return temperature warning. | ||
| 1.3.6.1.4.1.39829.1.508 | NodefacilityPressureWarning | Facility pressure warning. | ||
| 1.3.6.1.4.1.39829.1.509 | NodeserverPressureWarning | Server pressure warning. | ||
| 1.3.6.1.4.1.39829.1.512 | NodefacilityFlowWarning | Facility flow warning. | ||
| 1.3.6.1.4.1.39829.1.517 | NodefacilitySupplyAlarm | Facility supply temperature alarm. | ||
| 1.3.6.1.4.1.39829.1.518 | NodefacilityReturnAlarm | Facility return temperature alarm. | ||
| 1.3.6.1.4.1.39829.1.519 | NodeserverSupplyAlarm | Server supply temperature alarm. | ||
| 1.3.6.1.4.1.39829.1.520 | NodeserverReturnAlarm | Server return temperature alarm. | ||
| 1.3.6.1.4.1.39829.1.521 | NodefacilityPressureAlarm | Facility pressure alarm. | ||
| 1.3.6.1.4.1.39829.1.522 | NodeserverPressureAlarm | Server pressure alarm. | ||
| 1.3.6.1.4.1.39829.1.523 | NodeleakDetectionAlarm | Leak detection alarm. | ||
| 1.3.6.1.4.1.39829.1.524 | NodeliquidLevelAlarm | Low liquid level alarm. | ||
| 1.3.6.1.4.1.39829.1.525 | NodefacilityFlowAlarm | Facility flow alarm. |