MIB Viewer

CPS6000-MIB

808 objects
MIB for CPS6000 Power System.
Imported Objects
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.10520Nodeteps
1.3.6.1.4.1.10520.2Nodecontrollermibs
1.3.6.1.4.1.10520.2.1Noderelease
1.3.6.1.4.1.10520.2.1.1Identitycps6000MIB for CPS6000 Power System.
1.3.6.1.4.1.10520.2.1.1.1Nodecps6000Dc1
1.3.6.1.4.1.10520.2.1.1.1.1Scalarcps6000Dc1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.1.2Scalarcps6000Dc1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.1.3Scalarcps6000Dc1Typread-onlycurrentType
1.3.6.1.4.1.10520.2.1.1.1.4Scalarcps6000Dc1Sttread-writecurrentState Values: FLOAT, BOOST
1.3.6.1.4.1.10520.2.1.1.1.5Scalarcps6000Dc1Vdcread-onlycurrentVoltage (mV)
1.3.6.1.4.1.10520.2.1.1.1.6Scalarcps6000Dc1Adcread-onlycurrentCurrent (Amps)
1.3.6.1.4.1.10520.2.1.1.1.7Scalarcps6000Dc1Capread-onlycurrentTotal Installed Rectifier Capacity (Amps)
1.3.6.1.4.1.10520.2.1.1.1.8Scalarcps6000Dc1Olcapread-onlycurrentTotal On-line Rectifier Capacity (Amps)
1.3.6.1.4.1.10520.2.1.1.1.9Scalarcps6000Dc1Scapread-writecurrentString Capacity (Amps)
1.3.6.1.4.1.10520.2.1.1.1.10Scalarcps6000Dc1Nstread-onlycurrentNumber of Strings
1.3.6.1.4.1.10520.2.1.1.1.11Scalarcps6000Dc1Cpsread-onlycurrentCells per String
1.3.6.1.4.1.10520.2.1.1.1.12Scalarcps6000Dc1Btyread-onlycurrentBattery Type
1.3.6.1.4.1.10520.2.1.1.1.13Scalarcps6000Dc1Trdread-onlycurrentTotal Rectifier Drain (Amps)
1.3.6.1.4.1.10520.2.1.1.1.14Scalarcps6000Dc1Isdread-writecurrentImminent Shutdown Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.1.15Scalarcps6000Dc1Bodread-onlycurrentBattery On Discharge
1.3.6.1.4.1.10520.2.1.1.1.16Scalarcps6000Dc1Rssread-writecurrentRectifier Restart Values: off(0), on(1)
1.3.6.1.4.1.10520.2.1.1.1.17Scalarcps6000Dc1Rotread-writecurrentAll Rectifier On Threshold
1.3.6.1.4.1.10520.2.1.1.1.18Scalarcps6000Dc1Bstread-onlycurrentBoost
1.3.6.1.4.1.10520.2.1.1.1.19Scalarcps6000Dc1Amjread-onlycurrentAuxiliary Fuse Major Value: Alarm report from AMJ1
1.3.6.1.4.1.10520.2.1.1.1.20Scalarcps6000Dc1Eporead-onlycurrentEmergency Power Off Value: Alarm report from EPO1
1.3.6.1.4.1.10520.2.1.1.1.21Scalarcps6000Dc1Fajread-onlycurrentExternal Fuse Major Value: Alarm report from FAJ1
1.3.6.1.4.1.10520.2.1.1.1.22Scalarcps6000Dc1Fanread-onlycurrentExternal Fuse Minor Value: Alarm report from FAN1
1.3.6.1.4.1.10520.2.1.1.1.23Scalarcps6000Dc1Vsfread-onlycurrentSense/Control Fuse Value: Alarm report from VSF1
1.3.6.1.4.1.10520.2.1.1.1.24Scalarcps6000Dc1Osaread-onlycurrentOpen String Value: Alarm report from OSA1
1.3.6.1.4.1.10520.2.1.1.1.25Scalarcps6000Dc1Zidread-onlycurrentID Not Configured Value: Alarm report from ZID1
1.3.6.1.4.1.10520.2.1.1.1.26Scalarcps6000Dc1Tparead-onlycurrentThermal Probe Alarm Value: Alarm report from TPA1
1.3.6.1.4.1.10520.2.1.1.1.27Scalarcps6000Dc1Vmfread-onlycurrentVoltage Module Fail Value: Alarm report from VMF1
1.3.6.1.4.1.10520.2.1.1.1.28Scalarcps6000Dc1Cmaread-onlycurrentMinor Communication Failure Value: Alarm report from CMA1
1.3.6.1.4.1.10520.2.1.1.1.29Scalarcps6000Dc1Macfread-onlycurrentMultiple AC Failure Value: Alarm report from MACF1
1.3.6.1.4.1.10520.2.1.1.1.30Scalarcps6000Dc1Mcmread-onlycurrentMajor Communication Failure Value: Alarm report from MCM1
1.3.6.1.4.1.10520.2.1.1.1.31Scalarcps6000Dc1Rfaread-onlycurrentRectifier Fail Value: Alarm report from RFA1
1.3.6.1.4.1.10520.2.1.1.1.32Scalarcps6000Dc1Didread-onlycurrentID Conflict Value: Alarm report from DID1
1.3.6.1.4.1.10520.2.1.1.1.33Scalarcps6000Dc1Clmread-onlycurrentRectifier Current Limit Value: Alarm report from CLM1
1.3.6.1.4.1.10520.2.1.1.1.34Scalarcps6000Dc1Vlaread-onlycurrentVery Low Voltage Value: Alarm report from VLA1
1.3.6.1.4.1.10520.2.1.1.1.35Scalarcps6000Dc1Acfread-onlycurrentAC Fail Value: Alarm report from ACF1
1.3.6.1.4.1.10520.2.1.1.1.36Scalarcps6000Dc1Manread-onlycurrentManual Off Value: Alarm report from MAN1
1.3.6.1.4.1.10520.2.1.1.1.37Scalarcps6000Dc1Mmanread-onlycurrentMultiple Manual Off Value: Alarm report from MMAN1
1.3.6.1.4.1.10520.2.1.1.1.38Scalarcps6000Dc1Mfaread-onlycurrentMultiple Rectifier Fail Value: Alarm report from MFA1
1.3.6.1.4.1.10520.2.1.1.1.39Scalarcps6000Dc1Rtlread-onlycurrentReserve Time Low Value: Alarm report from RTL1
1.3.6.1.4.1.10520.2.1.1.1.40Scalarcps6000Dc1Rrtlread-onlycurrentReal-time Reserve Time Low Value: Alarm report from RRTL1
1.3.6.1.4.1.10520.2.1.1.1.41Scalarcps6000Dc1Rlsread-onlycurrentRedundancy Loss Value: Alarm report from RLS1
1.3.6.1.4.1.10520.2.1.1.1.42Scalarcps6000Dc1Bdaread-onlycurrentBattery On Discharge Value: Alarm report from BDA1
1.3.6.1.4.1.10520.2.1.1.1.43Scalarcps6000Dc1Hvaread-onlycurrentHigh Voltage Value: Alarm report from HVA1
1.3.6.1.4.1.10520.2.1.1.1.44Scalarcps6000Dc1Hfvread-onlycurrentHigh Float Voltage Value: Alarm report from HFV1
1.3.6.1.4.1.10520.2.1.1.1.45Scalarcps6000Dc1Ronread-writecurrentExternal Standby
1.3.6.1.4.1.10520.2.1.1.1.46Scalarcps6000Dc1Rsqread-writecurrentRectifier Sequencing Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.1.47Scalarcps6000Dc1Rtmread-onlycurrentReserve Time
1.3.6.1.4.1.10520.2.1.1.1.48Scalarcps6000Dc1Icrread-onlycurrentIncompatible Rectifier Value: Alarm report from ICR1
1.3.6.1.4.1.10520.2.1.1.1.49Scalarcps6000Dc1Rfnread-onlycurrentRectifier Fan Fail Value: Alarm report from RFN1
1.3.6.1.4.1.10520.2.1.1.1.50Scalarcps6000Dc1Emdread-onlycurrentEnergy Management Disabled Value: Alarm report from EMD1
1.3.6.1.4.1.10520.2.1.1.1.51Scalarcps6000Dc1Mlsread-writecurrentAll Shunts Monitored Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.1.52Scalarcps6000Dc1Bdtread-onlycurrentBD Duration
1.3.6.1.4.1.10520.2.1.1.1.53Scalarcps6000Dc1Emsread-onlycurrentEnergy Management State
1.3.6.1.4.1.10520.2.1.1.1.54Scalarcps6000Dc1Emeread-writecurrentEnergy Management Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.1.55Scalarcps6000Dc1Emtread-writecurrentEfficiency Target (%)
1.3.6.1.4.1.10520.2.1.1.1.56Scalarcps6000Dc1Emoread-writecurrentEfficiency Rectifier Turn On Threshold (%)
1.3.6.1.4.1.10520.2.1.1.1.57Scalarcps6000Dc1Pocread-onlycurrentPercent of Charge (%)
1.3.6.1.4.1.10520.2.1.1.1.58Scalarcps6000Dc1Lsfread-onlycurrentLoadshare Fail Value: Alarm report from LSF1
1.3.6.1.4.1.10520.2.1.1.2Nodecps6000Ps1
1.3.6.1.4.1.10520.2.1.1.2.1Scalarcps6000Ps1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.2.2Scalarcps6000Ps1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.2.3Scalarcps6000Ps1Sidread-writecurrentSite ID
1.3.6.1.4.1.10520.2.1.1.2.4Scalarcps6000Ps1Sderead-writecurrentSite Description
1.3.6.1.4.1.10520.2.1.1.2.5Scalarcps6000Ps1Swvread-onlycurrentSoftware Version
1.3.6.1.4.1.10520.2.1.1.2.6Scalarcps6000Ps1Verbread-onlycurrentBoot Block Version
1.3.6.1.4.1.10520.2.1.1.2.7Scalarcps6000Ps1Verwread-onlycurrentWeb Page Version
1.3.6.1.4.1.10520.2.1.1.2.8Scalarcps6000Ps1Verdread-onlycurrentDisplay Version
1.3.6.1.4.1.10520.2.1.1.2.9Scalarcps6000Ps1Dfltread-onlycurrentDefaults Version
1.3.6.1.4.1.10520.2.1.1.2.10Scalarcps6000Ps1Brcread-onlycurrentBoard Code
1.3.6.1.4.1.10520.2.1.1.2.11Scalarcps6000Ps1Snread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.2.12Scalarcps6000Ps1Uslread-writecurrentUninstall Missing Equipment Values: uninstall(1)
1.3.6.1.4.1.10520.2.1.1.2.13Scalarcps6000Ps1Datread-writecurrentSystem Date
1.3.6.1.4.1.10520.2.1.1.2.14Scalarcps6000Ps1Dtfread-writecurrentDate Format Values: mm/dd/yyyy, dd/mm/yyyy, yyyy/mm/dd
1.3.6.1.4.1.10520.2.1.1.2.15Scalarcps6000Ps1Timread-writecurrentSystem Time
1.3.6.1.4.1.10520.2.1.1.2.16Scalarcps6000Ps1Tmfread-writecurrentSystem Time Format Values: h12(12), h24(24)
1.3.6.1.4.1.10520.2.1.1.2.17Scalarcps6000Ps1Dlsread-writecurrentDaylight Savings Values: off(0), on(1)
1.3.6.1.4.1.10520.2.1.1.2.18Scalarcps6000Ps1Lngread-writecurrentFront Panel Language
1.3.6.1.4.1.10520.2.1.1.2.19Scalarcps6000Ps1Pttread-writecurrentCommunication Port Type Values: LOCAL, MODEM
1.3.6.1.4.1.10520.2.1.1.2.20Scalarcps6000Ps1Amtread-onlycurrentAmbient Temperature (C)
1.3.6.1.4.1.10520.2.1.1.2.21Scalarcps6000Ps1Tunread-writecurrentTemperature Units Values: C, F
1.3.6.1.4.1.10520.2.1.1.2.22Scalarcps6000Ps1Usrread-writecurrentEnable User Accounts Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.2.23Scalarcps6000Ps1Poeread-writecurrentPower Off Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.2.24Scalarcps6000Ps1Fpcread-writecurrentFront Panel Configuration Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.2.25Scalarcps6000Ps1Rrfread-writecurrentRemote Rectifier Off Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.2.26Scalarcps6000Ps1Amthread-onlycurrentHigh Ambient Temperature Value: Alarm report from AMTH1
1.3.6.1.4.1.10520.2.1.1.2.27Scalarcps6000Ps1Amtlread-onlycurrentLow Ambient Temperature Value: Alarm report from AMTL1
1.3.6.1.4.1.10520.2.1.1.2.28Scalarcps6000Ps1Bblread-onlycurrentMemory Backup Battery Low Value: Alarm report from BBL1
1.3.6.1.4.1.10520.2.1.1.2.29Scalarcps6000Ps1Cchread-onlycurrentConfiguration Changed Value: Alarm report from CCH1
1.3.6.1.4.1.10520.2.1.1.2.30Scalarcps6000Ps1Clcread-onlycurrentClock Changed Value: Alarm report from CLC1
1.3.6.1.4.1.10520.2.1.1.2.31Scalarcps6000Ps1Eprread-onlycurrentExternal Password Reset Value: Alarm report from EPR1
1.3.6.1.4.1.10520.2.1.1.2.32Scalarcps6000Ps1Exlread-onlycurrentExcessive Login Attempts Value: Alarm report from EXL1
1.3.6.1.4.1.10520.2.1.1.2.33Scalarcps6000Ps1Hclread-onlycurrentHistory Cleared Value: Alarm report from HCL1
1.3.6.1.4.1.10520.2.1.1.2.34Scalarcps6000Ps1Pfdread-onlycurrentPasswords At Default Value: Alarm report from PFD1
1.3.6.1.4.1.10520.2.1.1.2.35Scalarcps6000Ps1Phtread-onlycurrentProcessor Halt Value: Alarm report from PHT1
1.3.6.1.4.1.10520.2.1.1.2.36Scalarcps6000Ps1Stfread-onlycurrentSelf Test Failed Value: Alarm report from STF1
1.3.6.1.4.1.10520.2.1.1.2.37Scalarcps6000Ps1Pgiread-onlycurrentProgram Line Invalid Value: Alarm report from PGI1
1.3.6.1.4.1.10520.2.1.1.2.38Scalarcps6000Ps1Ax1read-onlycurrentAuxilliary Event 1 Value: Alarm report from AUX1
1.3.6.1.4.1.10520.2.1.1.2.39Scalarcps6000Ps1Ax2read-onlycurrentAuxilliary Event 1 Value: Alarm report from AUX2
1.3.6.1.4.1.10520.2.1.1.2.40Scalarcps6000Ps1Ax3read-onlycurrentAuxilliary Event 1 Value: Alarm report from AUX3
1.3.6.1.4.1.10520.2.1.1.2.41Scalarcps6000Ps1Ax4read-onlycurrentAuxilliary Event 1 Value: Alarm report from AUX4
1.3.6.1.4.1.10520.2.1.1.2.42Scalarcps6000Ps1Ax5read-onlycurrentAuxilliary Event 1 Value: Alarm report from AUX5
1.3.6.1.4.1.10520.2.1.1.2.43Scalarcps6000Ps1Ax6read-onlycurrentAuxilliary Event 1 Value: Alarm report from AUX6
1.3.6.1.4.1.10520.2.1.1.2.44Scalarcps6000Ps1Rssread-writecurrentRestart Devices Values: restart(1)
1.3.6.1.4.1.10520.2.1.1.2.45Scalarcps6000Ps1Sysread-writecurrentSystem Description
1.3.6.1.4.1.10520.2.1.1.2.46Scalarcps6000Ps1Lnglread-onlycurrentAvailable Languages
1.3.6.1.4.1.10520.2.1.1.2.47Scalarcps6000Ps1Fstread-writecurrentFactory Defaults
1.3.6.1.4.1.10520.2.1.1.2.48Scalarcps6000Ps1Fstlread-onlycurrentFactory Defaults List
1.3.6.1.4.1.10520.2.1.1.2.49Scalarcps6000Ps1Fperead-writecurrentFront Panel Pin Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.2.50Scalarcps6000Ps1Fptread-writecurrentFront Panel Pin Timeout
1.3.6.1.4.1.10520.2.1.1.2.51Scalarcps6000Ps1Astread-onlycurrentSystem Alarm State
1.3.6.1.4.1.10520.2.1.1.2.52Scalarcps6000Ps1Dssread-writecurrentDaylight Saving Start mon:wk:dow:min or, mon:-1:dom:min
1.3.6.1.4.1.10520.2.1.1.2.53Scalarcps6000Ps1Dseread-writecurrentDaylight Saving End mon:wk:dow:min or, mon:-1:dom:min
1.3.6.1.4.1.10520.2.1.1.3Nodecps6000At1
1.3.6.1.4.1.10520.2.1.1.3.1Scalarcps6000At1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.3.2Scalarcps6000At1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.3.3Scalarcps6000At1Sttread-writecurrentAlarm Test Active Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.3.4Scalarcps6000At1Stgread-onlycurrentStage
1.3.6.1.4.1.10520.2.1.1.3.5Scalarcps6000At1Lteread-writecurrentAlarm Test Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.3.6Scalarcps6000At1Durread-writecurrentAlarm Contact Duration (Seconds)
1.3.6.1.4.1.10520.2.1.1.3.7Scalarcps6000At1Pmjread-writecurrentPower Major Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.3.8Scalarcps6000At1Pmnread-writecurrentPower Minor Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.3.9Scalarcps6000At1R1read-writecurrentTest Relay 1 Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.3.10Scalarcps6000At1R2read-writecurrentTest Relay 2 Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.3.11Scalarcps6000At1R3read-writecurrentTest Relay 3 Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.3.12Scalarcps6000At1R4read-writecurrentTest Relay 4 Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.3.13Scalarcps6000At1Ataread-onlycurrentAlarm Test Active Value: Alarm report from ATA1
1.3.6.1.4.1.10520.2.1.1.3.14Scalarcps6000At1Atbread-onlycurrentAlarm Test Aborted Value: Alarm report from ATB1
1.3.6.1.4.1.10520.2.1.1.3.15Scalarcps6000At1Etsread-writecurrentDo Email Test Values: start(1)
1.3.6.1.4.1.10520.2.1.1.3.16Scalarcps6000At1Emsread-onlycurrentEmail Test Results
1.3.6.1.4.1.10520.2.1.1.3.17Scalarcps6000At1Irtread-writecurrentIndividual Relay Test State Values: , PMJ, PMN, R1, R2, R3, R4
1.3.6.1.4.1.10520.2.1.1.4Nodecps6000Dct1
1.3.6.1.4.1.10520.2.1.1.4.1Scalarcps6000Dct1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.4.2Scalarcps6000Dct1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.4.3Scalarcps6000Dct1Srcread-writecurrentSource
1.3.6.1.4.1.10520.2.1.1.5Nodecps6000Gm1
1.3.6.1.4.1.10520.2.1.1.5.1Scalarcps6000Gm1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.5.2Scalarcps6000Gm1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.5.3Scalarcps6000Gm1Lseread-writecurrentLoad Share Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.5.4Scalarcps6000Gm1Fsdread-writecurrentFloat High Voltage Shutdown (mV)
1.3.6.1.4.1.10520.2.1.1.5.5Scalarcps6000Gm1Bsdread-writecurrentBoost High Voltage Shutdown (mV)
1.3.6.1.4.1.10520.2.1.1.5.6Scalarcps6000Gm1Fspread-writecurrentFloat Set Point (mV)
1.3.6.1.4.1.10520.2.1.1.5.7Scalarcps6000Gm1Bspread-writecurrentBoost Set Point (mV)
1.3.6.1.4.1.10520.2.1.1.5.8Scalarcps6000Gm1Fclread-writecurrentFloat Current Limit (%)
1.3.6.1.4.1.10520.2.1.1.5.9Scalarcps6000Gm1Bclread-writecurrentBoost Current Limit (%)
1.3.6.1.4.1.10520.2.1.1.5.10Scalarcps6000Gm1Rmeread-writecurrentRedundancy Monitor Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.6Tablecps6000RecTablenot-accessiblecurrentTable of all Rectifier data
1.3.6.1.4.1.10520.2.1.1.6.1Rowcps6000RecEntrynot-accessiblecurrentEntry of information for one Rectifier
1.3.6.1.4.1.10520.2.1.1.6.1.1Columncps6000RecEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.6.1.2Columncps6000RecEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.6.1.3Columncps6000RecEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.6.1.4Columncps6000RecEntryTypread-writecurrentType
1.3.6.1.4.1.10520.2.1.1.6.1.5Columncps6000RecEntryAdcread-onlycurrentDC Current (Amps)
1.3.6.1.4.1.10520.2.1.1.6.1.6Columncps6000RecEntryVdcread-onlycurrentDC Voltage (Volts)
1.3.6.1.4.1.10520.2.1.1.6.1.7Columncps6000RecEntrySttread-writecurrentState Values: ON, OFF, STANDBY, VACANT
1.3.6.1.4.1.10520.2.1.1.6.1.8Columncps6000RecEntryCapread-onlycurrentCapacity (Amps)
1.3.6.1.4.1.10520.2.1.1.6.1.9Columncps6000RecEntryTmpread-onlycurrentTemperature (C)
1.3.6.1.4.1.10520.2.1.1.6.1.10Columncps6000RecEntrySeqread-writecurrentUse in Sequence Enable Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.6.1.11Columncps6000RecEntryRfaread-onlycurrentRectifier Fail
1.3.6.1.4.1.10520.2.1.1.6.1.12Columncps6000RecEntryAcfread-onlycurrentAC Fail
1.3.6.1.4.1.10520.2.1.1.6.1.13Columncps6000RecEntryManread-onlycurrentStandby or Manual Off
1.3.6.1.4.1.10520.2.1.1.6.1.14Columncps6000RecEntryDidread-onlycurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.6.1.15Columncps6000RecEntryClmread-onlycurrentCurrent Limit
1.3.6.1.4.1.10520.2.1.1.6.1.16Columncps6000RecEntryRcfread-onlycurrentCommunication Failure
1.3.6.1.4.1.10520.2.1.1.6.1.17Columncps6000RecEntryRfnread-onlycurrentFan Failure
1.3.6.1.4.1.10520.2.1.1.6.1.18Columncps6000RecEntrySnread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.6.1.19Columncps6000RecEntryVacread-onlycurrentAC Voltage (Volts)
1.3.6.1.4.1.10520.2.1.1.6.1.20Columncps6000RecEntryAacread-onlycurrentAC Current (mA)
1.3.6.1.4.1.10520.2.1.1.7Nodecps6000Cp1
1.3.6.1.4.1.10520.2.1.1.7.1Scalarcps6000Cp1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.7.2Scalarcps6000Cp1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.7.3Scalarcps6000Cp1Vdcread-onlycurrentDC Voltage (Volts)
1.3.6.1.4.1.10520.2.1.1.7.4Scalarcps6000Cp1Adcread-onlycurrentDC Current (Amps)
1.3.6.1.4.1.10520.2.1.1.7.5Scalarcps6000Cp1Capread-onlycurrentCapacity (Amps)
1.3.6.1.4.1.10520.2.1.1.7.6Scalarcps6000Cp1Vspread-writecurrentVoltage Set Point (mV)
1.3.6.1.4.1.10520.2.1.1.7.7Scalarcps6000Cp1Dthread-writecurrentLow Voltage Disconnect (mV)
1.3.6.1.4.1.10520.2.1.1.7.8Scalarcps6000Cp1Rthread-writecurrentLow Voltage Reconnect (mV)
1.3.6.1.4.1.10520.2.1.1.7.9Scalarcps6000Cp1Lvdread-writecurrentLow Voltage Disconnect Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.7.10Scalarcps6000Cp1Cfaread-onlycurrentConverter Fail Value: Alarm report from CFA1
1.3.6.1.4.1.10520.2.1.1.7.11Scalarcps6000Cp1Dfaread-onlycurrentDistribution Fail Value: Alarm report from CDFA1
1.3.6.1.4.1.10520.2.1.1.7.12Scalarcps6000Cp1Didread-onlycurrentID Conflict Value: Alarm report from CDID1
1.3.6.1.4.1.10520.2.1.1.7.13Scalarcps6000Cp1Mfaread-onlycurrentMultiple Converter Fail Value: Alarm report from CMFA1
1.3.6.1.4.1.10520.2.1.1.7.14Scalarcps6000Cp1Cfnread-onlycurrentConverter Fan Minor Value: Alarm report from CFN1
1.3.6.1.4.1.10520.2.1.1.7.15Scalarcps6000Cp1Cfjread-onlycurrentConverter Fan Major Value: Alarm report from CFJ1
1.3.6.1.4.1.10520.2.1.1.7.16Scalarcps6000Cp1Iccread-onlycurrentIncompatible Converter Alarm Value: Alarm report from ICC1
1.3.6.1.4.1.10520.2.1.1.7.17Scalarcps6000Cp1Hvaread-onlycurrentConverter High Voltage Major Value: Alarm report from CHVA1
1.3.6.1.4.1.10520.2.1.1.7.18Scalarcps6000Cp1Hfvread-onlycurrentConverter High Voltage Minor Value: Alarm report from CHFV1
1.3.6.1.4.1.10520.2.1.1.7.19Scalarcps6000Cp1Vlaread-onlycurrentConverter Very Low Voltage Value: Alarm report from CVLA
1.3.6.1.4.1.10520.2.1.1.7.20Scalarcps6000Cp1Rlread-onlycurrentConverter Redundancy Loss Value: Alarm report from CRL1
1.3.6.1.4.1.10520.2.1.1.7.21Scalarcps6000Cp1Typread-onlycurrentType
1.3.6.1.4.1.10520.2.1.1.7.22Scalarcps6000Cp1Olcapread-onlycurrentTotal On-line Converter Capacity (Amps)
1.3.6.1.4.1.10520.2.1.1.7.23Scalarcps6000Cp1Vsdread-writecurrentVoltage Shutdown (mV)
1.3.6.1.4.1.10520.2.1.1.7.24Scalarcps6000Cp1Clmread-writecurrentCurrent Limit (%)
1.3.6.1.4.1.10520.2.1.1.7.25Scalarcps6000Cp1Rofread-writecurrentRemote Turn Off Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.7.26Scalarcps6000Cp1Rmeread-writecurrentRedundancy Monitor Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.7.27Scalarcps6000Cp1Rssread-writecurrentRestart Values: restart(1)
1.3.6.1.4.1.10520.2.1.1.8Tablecps6000DccTablenot-accessiblecurrentTable of all Converter data
1.3.6.1.4.1.10520.2.1.1.8.1Rowcps6000DccEntrynot-accessiblecurrentEntry of information for one Converter
1.3.6.1.4.1.10520.2.1.1.8.1.1Columncps6000DccEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.8.1.2Columncps6000DccEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.8.1.3Columncps6000DccEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.8.1.4Columncps6000DccEntryTypread-onlycurrentType
1.3.6.1.4.1.10520.2.1.1.8.1.5Columncps6000DccEntryAdcread-onlycurrentDC Current (Amps)
1.3.6.1.4.1.10520.2.1.1.8.1.6Columncps6000DccEntryCapread-onlycurrentCapacity (Amps)
1.3.6.1.4.1.10520.2.1.1.8.1.7Columncps6000DccEntrySttread-writecurrentState Values: ON, OFF, STANDBY, VACANT
1.3.6.1.4.1.10520.2.1.1.8.1.8Columncps6000DccEntryCfaread-onlycurrentConverter Fail
1.3.6.1.4.1.10520.2.1.1.8.1.9Columncps6000DccEntryDfaread-onlycurrentDistribution Fuse Fail
1.3.6.1.4.1.10520.2.1.1.8.1.10Columncps6000DccEntryDidread-onlycurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.8.1.11Columncps6000DccEntryCcfread-onlycurrentCommunication Failure
1.3.6.1.4.1.10520.2.1.1.8.1.12Columncps6000DccEntryCfnread-onlycurrentFan Failure
1.3.6.1.4.1.10520.2.1.1.8.1.13Columncps6000DccEntrySnread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.9Nodecps6000Bs1
1.3.6.1.4.1.10520.2.1.1.9.1Scalarcps6000Bs1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.9.2Scalarcps6000Bs1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.9.3Scalarcps6000Bs1Sttread-onlycurrentState Values: QRCT, MANUAL, BTP, TIMED AUTO, OFF
1.3.6.1.4.1.10520.2.1.1.9.4Scalarcps6000Bs1Atmread-writecurrentAuto Mode Values: OFF, QRCT, TIMED
1.3.6.1.4.1.10520.2.1.1.9.5Scalarcps6000Bs1Tmdread-writecurrentTimed Manual Duration (Hours)
1.3.6.1.4.1.10520.2.1.1.9.6Scalarcps6000Bs1Amfread-writecurrentAuto Multiplication Factor
1.3.6.1.4.1.10520.2.1.1.9.7Scalarcps6000Bs1Ctaread-writecurrentCurrent Terminated Current Threshold (Amps)
1.3.6.1.4.1.10520.2.1.1.9.8Scalarcps6000Bs1Bsaread-onlycurrentBoost State Alarm Value: Alarm report from linked object
1.3.6.1.4.1.10520.2.1.1.10Nodecps6000Sc1
1.3.6.1.4.1.10520.2.1.1.10.1Scalarcps6000Sc1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.10.2Scalarcps6000Sc1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.10.3Scalarcps6000Sc1Sttread-writecurrentState Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.10.4Scalarcps6000Sc1Rveread-writecurrentRaise Voltage Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.10.5Scalarcps6000Sc1Lttread-writecurrentLower Temperature Threshold (C)
1.3.6.1.4.1.10520.2.1.1.10.6Scalarcps6000Sc1Nttread-writecurrentNominal Temperature Threshold (C)
1.3.6.1.4.1.10520.2.1.1.10.7Scalarcps6000Sc1Uttread-writecurrentUpper Temperature Threshold (C)
1.3.6.1.4.1.10520.2.1.1.10.8Scalarcps6000Sc1Sptread-writecurrentStep Temperature (C)
1.3.6.1.4.1.10520.2.1.1.10.9Scalarcps6000Sc1Lspread-writecurrentLower Temperature Slope/Cell (mV/C/Cell)
1.3.6.1.4.1.10520.2.1.1.10.10Scalarcps6000Sc1Uspread-writecurrentUpper Temperature Slope/Cell (mV/C/Cell)
1.3.6.1.4.1.10520.2.1.1.11Tablecps6000BtdTablenot-accessiblecurrentTable of all Battery Type Definition data
1.3.6.1.4.1.10520.2.1.1.11.1Rowcps6000BtdEntrynot-accessiblecurrentEntry of information for one Battery Type Definition
1.3.6.1.4.1.10520.2.1.1.11.1.1Columncps6000BtdEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.11.1.2Columncps6000BtdEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.11.1.3Columncps6000BtdEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.11.1.4Columncps6000BtdEntryBtyread-writecurrentBattery Type
1.3.6.1.4.1.10520.2.1.1.11.1.5Columncps6000BtdEntryBtcread-writecurrentBattery Class Values: FLOODED, SEALED
1.3.6.1.4.1.10520.2.1.1.11.1.6Columncps6000BtdEntryCapread-writecurrentCapacity (Amps)
1.3.6.1.4.1.10520.2.1.1.12Nodecps6000Br1
1.3.6.1.4.1.10520.2.1.1.12.1Scalarcps6000Br1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.12.2Scalarcps6000Br1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.12.3Scalarcps6000Br1Hbtread-onlycurrentHighest Battery Temperature (C)
1.3.6.1.4.1.10520.2.1.1.12.4Scalarcps6000Br1Adcread-onlycurrentTotal Battery Current (Amps)
1.3.6.1.4.1.10520.2.1.1.12.5Scalarcps6000Br1Capread-onlycurrentInstalled Battery Capacity (Amps)
1.3.6.1.4.1.10520.2.1.1.12.6Scalarcps6000Br1Olcapread-onlycurrentOn-line Battery Capacity (Amps)
1.3.6.1.4.1.10520.2.1.1.12.7Scalarcps6000Br1Btsread-writecurrentBattery Test State Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.12.8Scalarcps6000Br1Scdread-writecurrentBattery Voltage Imbalance Detection Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.12.9Scalarcps6000Br1Scvread-writecurrentBattery Imbalance Threshold (mV)
1.3.6.1.4.1.10520.2.1.1.12.10Scalarcps6000Br1Ntmread-onlycurrentNumber of Temperature Probes Present
1.3.6.1.4.1.10520.2.1.1.12.11Scalarcps6000Br1Nvmread-onlycurrentNumber of Mid-cell V PresentTemperature
1.3.6.1.4.1.10520.2.1.1.12.12Scalarcps6000Br1Cleread-writecurrentCurrent Limit Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.12.13Scalarcps6000Br1Cltread-writecurrentCurrent Limit Threshold (Amps)
1.3.6.1.4.1.10520.2.1.1.12.14Scalarcps6000Br1Mttread-writecurrentManual Test Type Values: DISABLE, 20%, TIMED
1.3.6.1.4.1.10520.2.1.1.12.15Scalarcps6000Br1Bteread-writecurrentAutomatic Test Type Values: DISABLE, 20%, TIMED
1.3.6.1.4.1.10520.2.1.1.12.16Scalarcps6000Br1Atdread-writecurrentAuto Test Date
1.3.6.1.4.1.10520.2.1.1.12.17Scalarcps6000Br1Athread-writecurrentAuto Test Hour
1.3.6.1.4.1.10520.2.1.1.12.18Scalarcps6000Br1Atwread-writecurrentAuto Test Minimum Hours after BD
1.3.6.1.4.1.10520.2.1.1.12.19Scalarcps6000Br1Tinread-writecurrentAuto Test Interval (Months)
1.3.6.1.4.1.10520.2.1.1.12.20Scalarcps6000Br1Tmdread-writecurrentManual Test Duration
1.3.6.1.4.1.10520.2.1.1.12.21Scalarcps6000Br1Tevread-writecurrentManual Test Alarm Voltage (mV)
1.3.6.1.4.1.10520.2.1.1.12.22Scalarcps6000Br1Btvread-writecurrentBattery Test Rectifier Voltage (mV)
1.3.6.1.4.1.10520.2.1.1.12.23Scalarcps6000Br1Tthread-writecurrentHigh Temperature Threshold (C)
1.3.6.1.4.1.10520.2.1.1.12.24Scalarcps6000Br1Cevread-writecurrentEnd Volts per Cell (mV)
1.3.6.1.4.1.10520.2.1.1.12.25Scalarcps6000Br1Btrread-onlycurrentBattery Test Results
1.3.6.1.4.1.10520.2.1.1.12.26Scalarcps6000Br1Btaread-onlycurrentBattery Test Active Value: Alarm report from BTA1
1.3.6.1.4.1.10520.2.1.1.12.27Scalarcps6000Br1Bfaread-onlycurrentBattery Test Failed Value: Alarm report from BFA1
1.3.6.1.4.1.10520.2.1.1.12.28Scalarcps6000Br1Btharead-onlycurrentHigh Battery Temperature Value: Alarm report from BTHA1
1.3.6.1.4.1.10520.2.1.1.12.29Scalarcps6000Br1Isdaread-onlycurrentImminent Shutdown Value: Alarm report from ISD1
1.3.6.1.4.1.10520.2.1.1.12.30Scalarcps6000Br1Mdpread-onlycurrentVoltage Duplicate ID Value: Alarm report from MDP1
1.3.6.1.4.1.10520.2.1.1.12.31Scalarcps6000Br1Mzdread-onlycurrentVoltage ID Not Configured Value: Alarm report from MZD1
1.3.6.1.4.1.10520.2.1.1.12.32Scalarcps6000Br1Scdaread-onlycurrentShorted Cell Detected Value: Alarm report from SCD1
1.3.6.1.4.1.10520.2.1.1.13Tablecps6000CntTablenot-accessiblecurrentTable of all Contactor data
1.3.6.1.4.1.10520.2.1.1.13.1Rowcps6000CntEntrynot-accessiblecurrentEntry of information for one Contactor
1.3.6.1.4.1.10520.2.1.1.13.1.1Columncps6000CntEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.13.1.2Columncps6000CntEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.13.1.3Columncps6000CntEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.13.1.4Columncps6000CntEntrySttread-writecurrentStatus Values: NONE, DISCON, CONNECT, FAILED
1.3.6.1.4.1.10520.2.1.1.13.1.5Columncps6000CntEntryEnaread-writecurrentControl Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.13.1.6Columncps6000CntEntryDthread-writecurrentDisconnect Threshold (mV)
1.3.6.1.4.1.10520.2.1.1.13.1.7Columncps6000CntEntryDdyread-writecurrentDisconnect Delay (Minutes)
1.3.6.1.4.1.10520.2.1.1.13.1.8Columncps6000CntEntryDamread-writecurrentDisconnect Automode Values: none(0), voltage(1), voltageAndTime(2)
1.3.6.1.4.1.10520.2.1.1.13.1.9Columncps6000CntEntryDtmread-onlycurrentDisconnect Time Remaining (Minutes)
1.3.6.1.4.1.10520.2.1.1.13.1.10Columncps6000CntEntryRthread-writecurrentReconnect Threshold (mV)
1.3.6.1.4.1.10520.2.1.1.13.1.11Columncps6000CntEntryRdyread-writecurrentReconnect Delay (Seconds)
1.3.6.1.4.1.10520.2.1.1.13.1.12Columncps6000CntEntryRamread-writecurrentReconnect Automode Values: none(0), voltage(1), voltageAndTime(2)
1.3.6.1.4.1.10520.2.1.1.13.1.13Columncps6000CntEntryRtmread-onlycurrentReconnect Time Remaining (Seconds)
1.3.6.1.4.1.10520.2.1.1.13.1.14Columncps6000CntEntryCnoread-onlycurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.13.1.15Columncps6000CntEntryCnfread-onlycurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.14Tablecps6000DcnTablenot-accessiblecurrentTable of all Distribution Contactor Interface data
1.3.6.1.4.1.10520.2.1.1.14.1Rowcps6000DcnEntrynot-accessiblecurrentEntry of information for one Distribution Contactor Interface
1.3.6.1.4.1.10520.2.1.1.14.1.1Columncps6000DcnEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.14.1.2Columncps6000DcnEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.14.1.3Columncps6000DcnEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.14.1.4Columncps6000DcnEntrySttread-onlycurrentState Values: NONE, MISSING, PRESENT
1.3.6.1.4.1.10520.2.1.1.14.1.5Columncps6000DcnEntryTypread-writecurrentContactor Interface Type Values: NONE, CN1, CN2, CN3, CN4
1.3.6.1.4.1.10520.2.1.1.14.1.6Columncps6000DcnEntrySnread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.14.1.7Columncps6000DcnEntryBrcread-onlycurrentBoard Code
1.3.6.1.4.1.10520.2.1.1.15Tablecps6000DcmTablenot-accessiblecurrentTable of all Distribution Current Monitor data
1.3.6.1.4.1.10520.2.1.1.15.1Rowcps6000DcmEntrynot-accessiblecurrentEntry of information for one Distribution Current Monitor
1.3.6.1.4.1.10520.2.1.1.15.1.1Columncps6000DcmEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.15.1.2Columncps6000DcmEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.15.1.3Columncps6000DcmEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.15.1.4Columncps6000DcmEntrySttread-onlycurrentState Values: NONE, MISSING, PRESENT
1.3.6.1.4.1.10520.2.1.1.15.1.5Columncps6000DcmEntryTypread-writecurrentShunt Type Values: NONE, LOAD, BATTERY
1.3.6.1.4.1.10520.2.1.1.15.1.6Columncps6000DcmEntryValread-onlycurrentReading (Amps x 1000)
1.3.6.1.4.1.10520.2.1.1.15.1.7Columncps6000DcmEntrySharead-writecurrentShunt Rating (Amps)
1.3.6.1.4.1.10520.2.1.1.15.1.8Columncps6000DcmEntrySnread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.15.1.9Columncps6000DcmEntryBrcread-onlycurrentBoard Code
1.3.6.1.4.1.10520.2.1.1.16Tablecps6000UdeTablenot-accessiblecurrentTable of all User Defined Event data
1.3.6.1.4.1.10520.2.1.1.16.1Rowcps6000UdeEntrynot-accessiblecurrentEntry of information for one User Defined Event
1.3.6.1.4.1.10520.2.1.1.16.1.1Columncps6000UdeEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.16.1.2Columncps6000UdeEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.16.1.3Columncps6000UdeEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.16.1.4Columncps6000UdeEntryAstread-onlycurrentAlarm State
1.3.6.1.4.1.10520.2.1.1.16.1.5Columncps6000UdeEntrySevread-writecurrentSeverity Values: CRIT, MAJ, MIN, WRN, RO
1.3.6.1.4.1.10520.2.1.1.16.1.6Columncps6000UdeEntryPrgread-writecurrentProgram Line
1.3.6.1.4.1.10520.2.1.1.16.1.7Columncps6000UdeEntryDurread-writecurrentMinimum Duration (Seconds)
1.3.6.1.4.1.10520.2.1.1.16.1.8Columncps6000UdeEntryLatread-writecurrentLatched Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.16.1.9Columncps6000UdeEntryAccread-writecurrentContact Closure Values: R1, R2, R3, R4
1.3.6.1.4.1.10520.2.1.1.16.1.10Columncps6000UdeEntryDlyread-writecurrentNotify Delay (Seconds)
1.3.6.1.4.1.10520.2.1.1.16.1.11Columncps6000UdeEntryNooread-writecurrentNotify on Occur Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.16.1.12Columncps6000UdeEntryNorread-writecurrentNotify on Retire Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.16.1.13Columncps6000UdeEntryNagread-writecurrentNAG on Occur Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.16.1.14Columncps6000UdeEntryDstread-writecurrentNotify Destination Values: P1, P2, P3, P4
1.3.6.1.4.1.10520.2.1.1.16.1.15Columncps6000UdeEntryFdsread-writecurrentFront Panel Description
1.3.6.1.4.1.10520.2.1.1.17Nodecps6000Cm1
1.3.6.1.4.1.10520.2.1.1.17.1Scalarcps6000Cm1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.17.2Scalarcps6000Cm1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.17.3Scalarcps6000Cm1Ngiread-writecurrentNag Interval (Minutes)
1.3.6.1.4.1.10520.2.1.1.17.4Scalarcps6000Cm1Cofread-onlycurrentQueue Overflow Value: Alarm report from COF1
1.3.6.1.4.1.10520.2.1.1.17.5Scalarcps6000Cm1Corread-onlycurrentNumber Did Not Respond Value: Alarm report from COR1
1.3.6.1.4.1.10520.2.1.1.17.6Scalarcps6000Cm1Nncread-onlycurrentNumber Not Configured Value: Alarm report from NNC1
1.3.6.1.4.1.10520.2.1.1.18Tablecps6000CopTablenot-accessiblecurrentTable of all Call Out Phone Number data
1.3.6.1.4.1.10520.2.1.1.18.1Rowcps6000CopEntrynot-accessiblecurrentEntry of information for one Call Out Phone Number
1.3.6.1.4.1.10520.2.1.1.18.1.1Columncps6000CopEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.18.1.2Columncps6000CopEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.18.1.3Columncps6000CopEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.18.1.4Columncps6000CopEntryTypread-writecurrentType Values: DATA, PAGER
1.3.6.1.4.1.10520.2.1.1.18.1.5Columncps6000CopEntryPhnread-writecurrentPhone Number
1.3.6.1.4.1.10520.2.1.1.18.1.6Columncps6000CopEntryBdrread-writecurrentConnect Baudrate Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.18.1.7Columncps6000CopEntryDbtread-writecurrentData Bits Values: d7(7), d8(8)
1.3.6.1.4.1.10520.2.1.1.18.1.8Columncps6000CopEntryPryread-writecurrentParity Values: O, E, N
1.3.6.1.4.1.10520.2.1.1.18.1.9Columncps6000CopEntrySbtread-writecurrentStop Bits Values: s1(1), s2(2)
1.3.6.1.4.1.10520.2.1.1.18.1.10Columncps6000CopEntryDlyread-writecurrentPager ID Delay
1.3.6.1.4.1.10520.2.1.1.18.1.11Columncps6000CopEntryPgrread-writecurrentPager ID
1.3.6.1.4.1.10520.2.1.1.18.1.12Columncps6000CopEntryMsgread-writecurrentPager Message
1.3.6.1.4.1.10520.2.1.1.19Tablecps6000CoeTablenot-accessiblecurrentTable of all Email Address data
1.3.6.1.4.1.10520.2.1.1.19.1Rowcps6000CoeEntrynot-accessiblecurrentEntry of information for one Email Address
1.3.6.1.4.1.10520.2.1.1.19.1.1Columncps6000CoeEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.19.1.2Columncps6000CoeEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.19.1.3Columncps6000CoeEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.19.1.4Columncps6000CoeEntryAdrread-writecurrentEmail Address
1.3.6.1.4.1.10520.2.1.1.19.1.5Columncps6000CoeEntryTypread-writecurrentAddress Type
1.3.6.1.4.1.10520.2.1.1.20Tablecps6000SndTablenot-accessiblecurrentTable of all SNMP Trap Destination data
1.3.6.1.4.1.10520.2.1.1.20.1Rowcps6000SndEntrynot-accessiblecurrentEntry of information for one SNMP Trap Destination
1.3.6.1.4.1.10520.2.1.1.20.1.1Columncps6000SndEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.20.1.2Columncps6000SndEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.20.1.3Columncps6000SndEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.20.1.4Columncps6000SndEntryIpread-writecurrentIP Address
1.3.6.1.4.1.10520.2.1.1.20.1.5Columncps6000SndEntryCsread-writecurrentCommunity String
1.3.6.1.4.1.10520.2.1.1.21Nodecps6000Po1
1.3.6.1.4.1.10520.2.1.1.21.1Scalarcps6000Po1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.21.2Scalarcps6000Po1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.21.3Scalarcps6000Po1Phnread-writecurrentPhone Number
1.3.6.1.4.1.10520.2.1.1.21.4Scalarcps6000Po1Bdrread-writecurrentConnect Baudrate Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.21.5Scalarcps6000Po1Dbtread-writecurrentData Bits Values: d7(7), d8(8)
1.3.6.1.4.1.10520.2.1.1.21.6Scalarcps6000Po1Pryread-writecurrentParity Values: O, E, N
1.3.6.1.4.1.10520.2.1.1.21.7Scalarcps6000Po1Sbtread-writecurrentStop Bits Values: s1(1), s2(2)
1.3.6.1.4.1.10520.2.1.1.21.8Scalarcps6000Po1Intread-writecurrentInterval Values: Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Daily, Monthly, Quarterly, Never
1.3.6.1.4.1.10520.2.1.1.21.9Scalarcps6000Po1Timread-writecurrentTime
1.3.6.1.4.1.10520.2.1.1.21.10Scalarcps6000Po1Cl01read-writecurrentCommand Line 1
1.3.6.1.4.1.10520.2.1.1.21.11Scalarcps6000Po1Cl02read-writecurrentCommand Line 2
1.3.6.1.4.1.10520.2.1.1.21.12Scalarcps6000Po1Cl03read-writecurrentCommand Line 3
1.3.6.1.4.1.10520.2.1.1.21.13Scalarcps6000Po1Cl04read-writecurrentCommand Line 4
1.3.6.1.4.1.10520.2.1.1.21.14Scalarcps6000Po1Cl05read-writecurrentCommand Line 5
1.3.6.1.4.1.10520.2.1.1.21.15Scalarcps6000Po1Cl06read-writecurrentCommand Line 6
1.3.6.1.4.1.10520.2.1.1.21.16Scalarcps6000Po1Cl07read-writecurrentCommand Line 7
1.3.6.1.4.1.10520.2.1.1.21.17Scalarcps6000Po1Cl08read-writecurrentCommand Line 8
1.3.6.1.4.1.10520.2.1.1.21.18Scalarcps6000Po1Cl09read-writecurrentCommand Line 9
1.3.6.1.4.1.10520.2.1.1.21.19Scalarcps6000Po1Cl10read-writecurrentCommand Line 10
1.3.6.1.4.1.10520.2.1.1.21.20Scalarcps6000Po1Porread-onlycurrentNumber Did Not Respond Value: Alarm report from POR1
1.3.6.1.4.1.10520.2.1.1.22Nodecps6000Cb1
1.3.6.1.4.1.10520.2.1.1.22.1Scalarcps6000Cb1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.22.2Scalarcps6000Cb1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.22.3Scalarcps6000Cb1Sttread-writecurrentState Values: off(0), on(1)
1.3.6.1.4.1.10520.2.1.1.22.4Scalarcps6000Cb1Ph1read-writecurrentCall-Back Phone Number 1
1.3.6.1.4.1.10520.2.1.1.22.5Scalarcps6000Cb1Br1read-writecurrentConnect Baudrate 1 Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.22.6Scalarcps6000Cb1Ph2read-writecurrentCall-Back Phone Number 2
1.3.6.1.4.1.10520.2.1.1.22.7Scalarcps6000Cb1Br2read-writecurrentConnect Baudrate 2 Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.22.8Scalarcps6000Cb1Ph3read-writecurrentCall-Back Phone Number 3
1.3.6.1.4.1.10520.2.1.1.22.9Scalarcps6000Cb1Br3read-writecurrentConnect Baudrate 3 Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.22.10Scalarcps6000Cb1Ph4read-writecurrentCall-Back Phone Number 4
1.3.6.1.4.1.10520.2.1.1.22.11Scalarcps6000Cb1Br4read-writecurrentConnect Baudrate 4 Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.22.12Scalarcps6000Cb1Ph5read-writecurrentCall-Back Phone Number 5
1.3.6.1.4.1.10520.2.1.1.22.13Scalarcps6000Cb1Br5read-writecurrentConnect Baudrate 5 Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.23Nodecps6000Mp1
1.3.6.1.4.1.10520.2.1.1.23.1Scalarcps6000Mp1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.23.2Scalarcps6000Mp1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.23.3Scalarcps6000Mp1Sttread-onlycurrentState
1.3.6.1.4.1.10520.2.1.1.23.4Scalarcps6000Mp1Dbtread-writecurrentData Bits Values: d7(7), d8(8)
1.3.6.1.4.1.10520.2.1.1.23.5Scalarcps6000Mp1Bdrread-writecurrentBaudrate Values: b300(300), b1200(1200), b2400(2400), b4800(4800), b9600(9600), b19200(19200)
1.3.6.1.4.1.10520.2.1.1.23.6Scalarcps6000Mp1Pryread-writecurrentParity Values: O, E, N
1.3.6.1.4.1.10520.2.1.1.23.7Scalarcps6000Mp1Sbtread-writecurrentStop Bits Values: s1(1), s2(2)
1.3.6.1.4.1.10520.2.1.1.23.8Scalarcps6000Mp1Tmoread-writecurrentTime-Out (Minutes)
1.3.6.1.4.1.10520.2.1.1.23.9Scalarcps6000Mp1Hshread-writecurrentHandshaking Values: NO, SW
1.3.6.1.4.1.10520.2.1.1.23.10Scalarcps6000Mp1Nrgread-writecurrentNumber of Rings Before Answer
1.3.6.1.4.1.10520.2.1.1.23.11Scalarcps6000Mp1Wreread-writecurrentWrite Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.23.12Scalarcps6000Mp1Insread-writecurrentModem Init String
1.3.6.1.4.1.10520.2.1.1.24Nodecps6000Lp1
1.3.6.1.4.1.10520.2.1.1.24.1Scalarcps6000Lp1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.24.2Scalarcps6000Lp1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.24.3Scalarcps6000Lp1Sttread-onlycurrentState
1.3.6.1.4.1.10520.2.1.1.24.4Scalarcps6000Lp1Bdrread-writecurrentBaudrate Values: 300, 1200, 2400, 4800, 9600, 19200, AUTO
1.3.6.1.4.1.10520.2.1.1.24.5Scalarcps6000Lp1Dbtread-writecurrentData Bits Values: d7(7), d8(8)
1.3.6.1.4.1.10520.2.1.1.24.6Scalarcps6000Lp1Pryread-writecurrentParity Values: O, E, N
1.3.6.1.4.1.10520.2.1.1.24.7Scalarcps6000Lp1Sbtread-writecurrentStop Bits Values: s1(1), s2(2)
1.3.6.1.4.1.10520.2.1.1.24.8Scalarcps6000Lp1Tmoread-writecurrentTime-Out (Minutes)
1.3.6.1.4.1.10520.2.1.1.24.9Scalarcps6000Lp1Hshread-writecurrentHandshaking Values: NO, HW, SW
1.3.6.1.4.1.10520.2.1.1.24.10Scalarcps6000Lp1Appread-writecurrentApplication Values: TERMINAL, TL1, EVENT LOG
1.3.6.1.4.1.10520.2.1.1.24.11Scalarcps6000Lp1Wreread-writecurrentWrite Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.25Nodecps6000Tlm1
1.3.6.1.4.1.10520.2.1.1.25.1Scalarcps6000Tlm1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.25.2Scalarcps6000Tlm1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.25.3Scalarcps6000Tlm1Aueread-writecurrentActivate-User Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.25.4Scalarcps6000Tlm1Ctsread-writecurrentCTS Connect Detection Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.25.5Scalarcps6000Tlm1Dsrread-writecurrentDSR Connect Detection Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.25.6Scalarcps6000Tlm1Prtread-writecurrentTCP/IP Port
1.3.6.1.4.1.10520.2.1.1.26Tablecps6000Tl1Tablenot-accessiblecurrentTable of all TL1 Object data
1.3.6.1.4.1.10520.2.1.1.26.1Rowcps6000Tl1Entrynot-accessiblecurrentEntry of information for one TL1 Object
1.3.6.1.4.1.10520.2.1.1.26.1.1Columncps6000Tl1EntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.26.1.2Columncps6000Tl1EntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.26.1.3Columncps6000Tl1EntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.26.1.4Columncps6000Tl1EntryCdsread-writecurrentCondition Description
1.3.6.1.4.1.10520.2.1.1.26.1.5Columncps6000Tl1EntryAidread-writecurrentAid
1.3.6.1.4.1.10520.2.1.1.26.1.6Columncps6000Tl1EntryCndread-writecurrentCondition Type
1.3.6.1.4.1.10520.2.1.1.26.1.7Columncps6000Tl1EntrySafread-writecurrentService Affecting Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.26.1.8Columncps6000Tl1EntryRptread-writecurrentReporting Values: EQUIPMENT, ENVIRONMENT, PRESENCE
1.3.6.1.4.1.10520.2.1.1.27Nodecps6000Net1
1.3.6.1.4.1.10520.2.1.1.27.1Scalarcps6000Net1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.27.2Scalarcps6000Net1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.27.3Scalarcps6000Net1Eadread-onlycurrentEthernet Address
1.3.6.1.4.1.10520.2.1.1.27.4Scalarcps6000Net1Dhcpread-writecurrentDHCP Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.27.5Scalarcps6000Net1Ipread-writecurrentStatic IP Address
1.3.6.1.4.1.10520.2.1.1.27.6Scalarcps6000Net1Wipread-onlycurrentWorking IP Address
1.3.6.1.4.1.10520.2.1.1.27.7Scalarcps6000Net1Subread-writecurrentSubnet Mask
1.3.6.1.4.1.10520.2.1.1.27.8Scalarcps6000Net1Gtwyread-writecurrentDefault Gateway
1.3.6.1.4.1.10520.2.1.1.27.9Scalarcps6000Net1Hostread-writecurrentHost Name
1.3.6.1.4.1.10520.2.1.1.27.10Scalarcps6000Net1Domread-writecurrentDomain Name
1.3.6.1.4.1.10520.2.1.1.27.11Scalarcps6000Net1Dnsread-writecurrentDNS Server Address
1.3.6.1.4.1.10520.2.1.1.27.12Scalarcps6000Net1Wreread-writecurrentWrite Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.27.13Scalarcps6000Net1Tmoread-writecurrentTimeout (Minutes)
1.3.6.1.4.1.10520.2.1.1.27.14Scalarcps6000Net1Msrvread-writecurrentMail Server Address
1.3.6.1.4.1.10520.2.1.1.28Tablecps6000DrcTablenot-accessiblecurrentTable of all Derived Channel data
1.3.6.1.4.1.10520.2.1.1.28.1Rowcps6000DrcEntrynot-accessiblecurrentEntry of information for one Derived Channel
1.3.6.1.4.1.10520.2.1.1.28.1.1Columncps6000DrcEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.28.1.2Columncps6000DrcEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.28.1.3Columncps6000DrcEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.28.1.4Columncps6000DrcEntryValread-onlycurrentValue
1.3.6.1.4.1.10520.2.1.1.28.1.5Columncps6000DrcEntryPrgread-writecurrentProgram Line
1.3.6.1.4.1.10520.2.1.1.28.1.6Columncps6000DrcEntryUniread-writecurrentUnit
1.3.6.1.4.1.10520.2.1.1.29Tablecps6000InpTablenot-accessiblecurrentTable of all Input Management data
1.3.6.1.4.1.10520.2.1.1.29.1Rowcps6000InpEntrynot-accessiblecurrentEntry of information for one Input Management
1.3.6.1.4.1.10520.2.1.1.29.1.1Columncps6000InpEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.29.1.2Columncps6000InpEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.29.1.3Columncps6000InpEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.29.1.4Columncps6000InpEntrySttread-onlycurrentInput State Values: alarming(1), nonAlarming(0)
1.3.6.1.4.1.10520.2.1.1.29.1.5Columncps6000InpEntryTypread-writecurrentType Alarm Object ID or, REMLVD for Remote LVD
1.3.6.1.4.1.10520.2.1.1.29.1.6Columncps6000InpEntryPolread-writecurrentInput Alarming Polarity Values: OPEN, CLOSED
1.3.6.1.4.1.10520.2.1.1.29.1.7Columncps6000InpEntrySnread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.29.1.8Columncps6000InpEntryBrcread-onlycurrentBoard Code
1.3.6.1.4.1.10520.2.1.1.30Nodecps6000Rp1
1.3.6.1.4.1.10520.2.1.1.30.1Scalarcps6000Rp1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.30.2Scalarcps6000Rp1Desread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.30.3Scalarcps6000Rp1Frqread-writecurrentFrequency (Hz)
1.3.6.1.4.1.10520.2.1.1.30.4Scalarcps6000Rp1Vspread-writecurrentVoltage Set-point (Volts)
1.3.6.1.4.1.10520.2.1.1.30.5Scalarcps6000Rp1Oferead-writecurrentOffset Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.30.6Scalarcps6000Rp1Rmeread-writecurrentRedundancy Monitor Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.30.7Scalarcps6000Rp1Rssread-writecurrentRestart Values: restart(1)
1.3.6.1.4.1.10520.2.1.1.30.8Scalarcps6000Rp1Rfread-onlycurrentRinger Minor Fail
1.3.6.1.4.1.10520.2.1.1.30.9Scalarcps6000Rp1Rpffread-onlycurrentRinger Fan Fail
1.3.6.1.4.1.10520.2.1.1.30.10Scalarcps6000Rp1Rpxjread-onlycurrentRinger Major External Fault
1.3.6.1.4.1.10520.2.1.1.30.11Scalarcps6000Rp1Rpxnread-onlycurrentRinger Minor External Fault
1.3.6.1.4.1.10520.2.1.1.30.12Scalarcps6000Rp1Rprlread-onlycurrentRinger Redundency Loss
1.3.6.1.4.1.10520.2.1.1.30.13Scalarcps6000Rp1Rpfjread-onlycurrentRinger Major Fail
1.3.6.1.4.1.10520.2.1.1.30.14Scalarcps6000Rp1Rcdpread-onlycurrentRinger ID Conflict Value: Alarm report from RCDP1
1.3.6.1.4.1.10520.2.1.1.31Tablecps6000RchTablenot-accessiblecurrentTable of all Ringer Chassis data
1.3.6.1.4.1.10520.2.1.1.31.1Rowcps6000RchEntrynot-accessiblecurrentEntry of information for one Ringer Chassis
1.3.6.1.4.1.10520.2.1.1.31.1.1Columncps6000RchEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.31.1.2Columncps6000RchEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.31.1.3Columncps6000RchEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.31.1.4Columncps6000RchEntrySttread-writecurrentRinger Group State
1.3.6.1.4.1.10520.2.1.1.31.1.5Columncps6000RchEntryVaread-onlycurrentRinger Output VA
1.3.6.1.4.1.10520.2.1.1.31.1.6Columncps6000RchEntryPriread-onlycurrentPrimary Ringer
1.3.6.1.4.1.10520.2.1.1.31.1.7Columncps6000RchEntrySecread-onlycurrentSecondary Ringer
1.3.6.1.4.1.10520.2.1.1.31.1.8Columncps6000RchEntryRfread-onlycurrentRinger Minor Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.31.1.9Columncps6000RchEntryRpffread-onlycurrentRinger Fan Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.31.1.10Columncps6000RchEntryRpxjread-onlycurrentRinger Major External Fault Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.31.1.11Columncps6000RchEntryRpxnread-onlycurrentRinger Minor External Fault Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.31.1.12Columncps6000RchEntryRprlread-onlycurrentRinger Redundency Loss Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.31.1.13Columncps6000RchEntryRpfjread-onlycurrentRinger Major Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.31.1.14Columncps6000RchEntryRcdpread-onlycurrentRinger ID Conflict Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.32Tablecps6000AlarmTablenot-accessiblecurrentTable of all Alarm data
1.3.6.1.4.1.10520.2.1.1.32.1Rowcps6000AlarmEntrynot-accessiblecurrentEntry of information for one Alarm
1.3.6.1.4.1.10520.2.1.1.32.1.1Columncps6000AlarmEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.32.1.2Columncps6000AlarmEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.32.1.3Columncps6000AlarmEntryAstread-onlycurrentState Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.32.1.4Columncps6000AlarmEntrySevread-writecurrentSeverity
1.3.6.1.4.1.10520.2.1.1.32.1.5Columncps6000AlarmEntryAccread-writecurrentContact Closure Values: R1, R2, R3, R4
1.3.6.1.4.1.10520.2.1.1.32.1.6Columncps6000AlarmEntryThrread-writecurrentThreshold
1.3.6.1.4.1.10520.2.1.1.32.1.7Columncps6000AlarmEntryFthread-writecurrentFloat Threshold
1.3.6.1.4.1.10520.2.1.1.32.1.8Columncps6000AlarmEntryBthread-writecurrentBoost Threshold
1.3.6.1.4.1.10520.2.1.1.32.1.9Columncps6000AlarmEntryDlyread-writecurrentNotify Delay
1.3.6.1.4.1.10520.2.1.1.32.1.10Columncps6000AlarmEntryNooread-writecurrentNotify On Occur Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.32.1.11Columncps6000AlarmEntryNorread-writecurrentNotify On Retire Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.32.1.12Columncps6000AlarmEntryNagread-writecurrentNag on Occur Values: no(0), yes(1)
1.3.6.1.4.1.10520.2.1.1.32.1.13Columncps6000AlarmEntryDstread-writecurrentNotify Destination
1.3.6.1.4.1.10520.2.1.1.32.1.14Columncps6000AlarmEntryFdsread-writecurrentFront Panel Description
1.3.6.1.4.1.10520.2.1.1.33Nodecps6000Trap
1.3.6.1.4.1.10520.2.1.1.33.1Notificationcps6000TrapDc1AmjcurrentAuxiliary Fuse Major
1.3.6.1.4.1.10520.2.1.1.33.2Notificationcps6000TrapDc1EpocurrentEmergency Power Off
1.3.6.1.4.1.10520.2.1.1.33.3Notificationcps6000TrapDc1FajcurrentExternal Fuse Major
1.3.6.1.4.1.10520.2.1.1.33.4Notificationcps6000TrapDc1FancurrentExternal Fuse Minor
1.3.6.1.4.1.10520.2.1.1.33.5Notificationcps6000TrapDc1VsfcurrentSense/Control Fuse
1.3.6.1.4.1.10520.2.1.1.33.6Notificationcps6000TrapDc1OsacurrentOpen String
1.3.6.1.4.1.10520.2.1.1.33.7Notificationcps6000TrapDc1ZidcurrentID Not Configured
1.3.6.1.4.1.10520.2.1.1.33.8Notificationcps6000TrapDc1TpacurrentThermal Probe Alarm
1.3.6.1.4.1.10520.2.1.1.33.9Notificationcps6000TrapDc1VmfcurrentVoltage Module Fail
1.3.6.1.4.1.10520.2.1.1.33.10Notificationcps6000TrapDc1CmacurrentMinor Communication Failure
1.3.6.1.4.1.10520.2.1.1.33.11Notificationcps6000TrapDc1MacfcurrentMultiple AC Failure
1.3.6.1.4.1.10520.2.1.1.33.12Notificationcps6000TrapDc1McmcurrentMajor Communication Failure
1.3.6.1.4.1.10520.2.1.1.33.13Notificationcps6000TrapDc1RfacurrentRectifier Fail
1.3.6.1.4.1.10520.2.1.1.33.14Notificationcps6000TrapDc1DidcurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.33.15Notificationcps6000TrapDc1ClmcurrentRectifier Current Limit
1.3.6.1.4.1.10520.2.1.1.33.16Notificationcps6000TrapDc1VlacurrentVery Low Voltage
1.3.6.1.4.1.10520.2.1.1.33.17Notificationcps6000TrapDc1AcfcurrentAC Fail
1.3.6.1.4.1.10520.2.1.1.33.18Notificationcps6000TrapDc1MancurrentManual Off
1.3.6.1.4.1.10520.2.1.1.33.19Notificationcps6000TrapDc1MmancurrentMultiple Manual Off
1.3.6.1.4.1.10520.2.1.1.33.20Notificationcps6000TrapDc1MfacurrentMultiple Rectifier Fail
1.3.6.1.4.1.10520.2.1.1.33.21Notificationcps6000TrapDc1RtlcurrentReserve Time Low
1.3.6.1.4.1.10520.2.1.1.33.22Notificationcps6000TrapDc1RrtlcurrentReal-time Reserve Time Low
1.3.6.1.4.1.10520.2.1.1.33.23Notificationcps6000TrapDc1RlscurrentRedundancy Loss
1.3.6.1.4.1.10520.2.1.1.33.24Notificationcps6000TrapDc1BdacurrentBattery On Discharge
1.3.6.1.4.1.10520.2.1.1.33.25Notificationcps6000TrapDc1HvacurrentHigh Voltage
1.3.6.1.4.1.10520.2.1.1.33.26Notificationcps6000TrapDc1HfvcurrentHigh Float Voltage
1.3.6.1.4.1.10520.2.1.1.33.27Notificationcps6000TrapPs1AmthcurrentHigh Ambient Temperature
1.3.6.1.4.1.10520.2.1.1.33.28Notificationcps6000TrapPs1AmtlcurrentLow Ambient Temperature
1.3.6.1.4.1.10520.2.1.1.33.29Notificationcps6000TrapPs1BblcurrentMemory Backup Battery Low
1.3.6.1.4.1.10520.2.1.1.33.30Notificationcps6000TrapPs1CchcurrentConfiguration Changed
1.3.6.1.4.1.10520.2.1.1.33.31Notificationcps6000TrapPs1ClccurrentClock Changed
1.3.6.1.4.1.10520.2.1.1.33.32Notificationcps6000TrapPs1EprcurrentExternal Password Reset
1.3.6.1.4.1.10520.2.1.1.33.33Notificationcps6000TrapPs1ExlcurrentExcessive Login Attempts
1.3.6.1.4.1.10520.2.1.1.33.34Notificationcps6000TrapPs1HclcurrentHistory Cleared
1.3.6.1.4.1.10520.2.1.1.33.35Notificationcps6000TrapPs1PfdcurrentPasswords At Default
1.3.6.1.4.1.10520.2.1.1.33.36Notificationcps6000TrapPs1PhtcurrentProcessor Halt
1.3.6.1.4.1.10520.2.1.1.33.37Notificationcps6000TrapPs1StfcurrentSelf Test Failed
1.3.6.1.4.1.10520.2.1.1.33.38Notificationcps6000TrapPs1PgicurrentProgram Line Invalid
1.3.6.1.4.1.10520.2.1.1.33.39Notificationcps6000TrapPs1Ax1currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.33.40Notificationcps6000TrapPs1Ax2currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.33.41Notificationcps6000TrapPs1Ax3currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.33.42Notificationcps6000TrapPs1Ax4currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.33.43Notificationcps6000TrapPs1Ax5currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.33.44Notificationcps6000TrapPs1Ax6currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.33.45Notificationcps6000TrapAt1AtacurrentAlarm Test Active
1.3.6.1.4.1.10520.2.1.1.33.46Notificationcps6000TrapAt1AtbcurrentAlarm Test Aborted
1.3.6.1.4.1.10520.2.1.1.33.47Notificationcps6000TrapCp1CfacurrentConverter Fail
1.3.6.1.4.1.10520.2.1.1.33.48Notificationcps6000TrapCp1DfacurrentDistribution Fail
1.3.6.1.4.1.10520.2.1.1.33.49Notificationcps6000TrapCp1DidcurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.33.50Notificationcps6000TrapCp1MfacurrentMultiple Converter Fail
1.3.6.1.4.1.10520.2.1.1.33.51Notificationcps6000TrapBs1BsacurrentBoost State Alarm
1.3.6.1.4.1.10520.2.1.1.33.52Notificationcps6000TrapBr1BtacurrentBattery Test Active
1.3.6.1.4.1.10520.2.1.1.33.53Notificationcps6000TrapBr1BfacurrentBattery Test Failed
1.3.6.1.4.1.10520.2.1.1.33.54Notificationcps6000TrapBr1BthacurrentHigh Battery Temperature
1.3.6.1.4.1.10520.2.1.1.33.55Notificationcps6000TrapBr1IsdacurrentImminent Shutdown
1.3.6.1.4.1.10520.2.1.1.33.56Notificationcps6000TrapCn1CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.33.57Notificationcps6000TrapCn1CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.33.58Notificationcps6000TrapCn2CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.33.59Notificationcps6000TrapCn2CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.33.60Notificationcps6000TrapCn3CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.33.61Notificationcps6000TrapCn3CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.33.62Notificationcps6000TrapCn4CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.33.63Notificationcps6000TrapCn4CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.33.64Notificationcps6000TrapCm1CofcurrentQueue Overflow
1.3.6.1.4.1.10520.2.1.1.33.65Notificationcps6000TrapCm1CorcurrentNumber Did Not Respond
1.3.6.1.4.1.10520.2.1.1.33.66Notificationcps6000TrapCm1NnccurrentNumber Not Configured
1.3.6.1.4.1.10520.2.1.1.33.67Notificationcps6000TrapPo1PorcurrentNumber Did Not Respond
1.3.6.1.4.1.10520.2.1.1.33.68Notificationcps6000TrapRp1RfcurrentRinger Minor Fail
1.3.6.1.4.1.10520.2.1.1.33.69Notificationcps6000TrapRp1RpffcurrentRinger Fan Fail
1.3.6.1.4.1.10520.2.1.1.33.70Notificationcps6000TrapRp1RpxjcurrentRinger Major External Fault
1.3.6.1.4.1.10520.2.1.1.33.71Notificationcps6000TrapRp1RpxncurrentRinger Minor External Fault
1.3.6.1.4.1.10520.2.1.1.33.72Notificationcps6000TrapRp1RprlcurrentRinger Redundency Loss
1.3.6.1.4.1.10520.2.1.1.33.73Notificationcps6000TrapRp1RpfjcurrentRinger Major Fail
1.3.6.1.4.1.10520.2.1.1.33.74Notificationcps6000TrapUserDefinedcurrentThis may be a user defined event, or a new controller event.
1.3.6.1.4.1.10520.2.1.1.33.75Notificationcps6000TrapDc1IcrcurrentIncompatible Rectifier
1.3.6.1.4.1.10520.2.1.1.33.76Notificationcps6000TrapDc1RfncurrentRectifier Fan Fail
1.3.6.1.4.1.10520.2.1.1.33.77Notificationcps6000TrapDc1EmdcurrentEnergy Management Disabled
1.3.6.1.4.1.10520.2.1.1.33.78Notificationcps6000TrapCp1CfncurrentConverter Fan Minor
1.3.6.1.4.1.10520.2.1.1.33.79Notificationcps6000TrapCp1CfjcurrentConverter Fan Major
1.3.6.1.4.1.10520.2.1.1.33.80Notificationcps6000TrapCp1IcccurrentIncompatible Converter Alarm
1.3.6.1.4.1.10520.2.1.1.33.81Notificationcps6000TrapCp1HvacurrentConverter High Voltage Major
1.3.6.1.4.1.10520.2.1.1.33.82Notificationcps6000TrapCp1HfvcurrentConverter High Voltage Minor
1.3.6.1.4.1.10520.2.1.1.33.83Notificationcps6000TrapCp1VlacurrentConverter Very Low Voltage
1.3.6.1.4.1.10520.2.1.1.33.84Notificationcps6000TrapCp1RlcurrentConverter Redundancy Loss
1.3.6.1.4.1.10520.2.1.1.33.85Notificationcps6000TrapBr1MdpcurrentVoltage Duplicate ID
1.3.6.1.4.1.10520.2.1.1.33.86Notificationcps6000TrapBr1MzdcurrentVoltage ID Not Configured
1.3.6.1.4.1.10520.2.1.1.33.87Notificationcps6000TrapBr1ScdacurrentShorted Cell Detected
1.3.6.1.4.1.10520.2.1.1.33.88Notificationcps6000TrapRp1RcdpcurrentRinger ID Conflict
1.3.6.1.4.1.10520.2.1.1.33.89Notificationcps6000TrapFt1FmicurrentFan Fail Minor
1.3.6.1.4.1.10520.2.1.1.33.90Notificationcps6000TrapFt1FmjcurrentFan Fail Major
1.3.6.1.4.1.10520.2.1.1.33.91Notificationcps6000TrapFt1IpicurrentInput Power Minor
1.3.6.1.4.1.10520.2.1.1.33.92Notificationcps6000TrapFt1IpjcurrentInput Power Major
1.3.6.1.4.1.10520.2.1.1.33.93Notificationcps6000TrapFt1CbtcurrentCircuit Breaker Trip
1.3.6.1.4.1.10520.2.1.1.33.94Notificationcps6000TrapFt1CtfcurrentCircuit Fail
1.3.6.1.4.1.10520.2.1.1.33.95Notificationcps6000TrapFt1MctfcurrentMultiple Circuit Fail
1.3.6.1.4.1.10520.2.1.1.33.96Notificationcps6000TrapFt1LorcurrentLoss of Redundancy
1.3.6.1.4.1.10520.2.1.1.33.97Notificationcps6000TrapFt1LdacurrentLoad Drop Alarm
1.3.6.1.4.1.10520.2.1.1.33.98Notificationcps6000TrapFt1LsacurrentLoad Share Alarm
1.3.6.1.4.1.10520.2.1.1.33.99Notificationcps6000TrapFt1LtacurrentLine Test Failed Alarm
1.3.6.1.4.1.10520.2.1.1.33.100Notificationcps6000TrapDc1LsfcurrentLoadshare Fail
1.3.6.1.4.1.10520.2.1.1.34ScalartrapInfoaccessible-for-notifycurrentSupplemental alarm information
1.3.6.1.4.1.10520.2.1.1.35Nodecps6000Retire
1.3.6.1.4.1.10520.2.1.1.35.1Notificationcps6000RetireDc1AmjcurrentAuxiliary Fuse Major
1.3.6.1.4.1.10520.2.1.1.35.2Notificationcps6000RetireDc1EpocurrentEmergency Power Off
1.3.6.1.4.1.10520.2.1.1.35.3Notificationcps6000RetireDc1FajcurrentExternal Fuse Major
1.3.6.1.4.1.10520.2.1.1.35.4Notificationcps6000RetireDc1FancurrentExternal Fuse Minor
1.3.6.1.4.1.10520.2.1.1.35.5Notificationcps6000RetireDc1VsfcurrentSense/Control Fuse
1.3.6.1.4.1.10520.2.1.1.35.6Notificationcps6000RetireDc1OsacurrentOpen String
1.3.6.1.4.1.10520.2.1.1.35.7Notificationcps6000RetireDc1ZidcurrentID Not Configured
1.3.6.1.4.1.10520.2.1.1.35.8Notificationcps6000RetireDc1TpacurrentThermal Probe Alarm
1.3.6.1.4.1.10520.2.1.1.35.9Notificationcps6000RetireDc1VmfcurrentVoltage Module Fail
1.3.6.1.4.1.10520.2.1.1.35.10Notificationcps6000RetireDc1CmacurrentMinor Communication Failure
1.3.6.1.4.1.10520.2.1.1.35.11Notificationcps6000RetireDc1MacfcurrentMultiple AC Failure
1.3.6.1.4.1.10520.2.1.1.35.12Notificationcps6000RetireDc1McmcurrentMajor Communication Failure
1.3.6.1.4.1.10520.2.1.1.35.13Notificationcps6000RetireDc1RfacurrentRectifier Fail
1.3.6.1.4.1.10520.2.1.1.35.14Notificationcps6000RetireDc1DidcurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.35.15Notificationcps6000RetireDc1ClmcurrentRectifier Current Limit
1.3.6.1.4.1.10520.2.1.1.35.16Notificationcps6000RetireDc1VlacurrentVery Low Voltage
1.3.6.1.4.1.10520.2.1.1.35.17Notificationcps6000RetireDc1AcfcurrentAC Fail
1.3.6.1.4.1.10520.2.1.1.35.18Notificationcps6000RetireDc1MancurrentManual Off
1.3.6.1.4.1.10520.2.1.1.35.19Notificationcps6000RetireDc1MmancurrentMultiple Manual Off
1.3.6.1.4.1.10520.2.1.1.35.20Notificationcps6000RetireDc1MfacurrentMultiple Rectifier Fail
1.3.6.1.4.1.10520.2.1.1.35.21Notificationcps6000RetireDc1RtlcurrentReserve Time Low
1.3.6.1.4.1.10520.2.1.1.35.22Notificationcps6000RetireDc1RrtlcurrentReal-time Reserve Time Low
1.3.6.1.4.1.10520.2.1.1.35.23Notificationcps6000RetireDc1RlscurrentRedundancy Loss
1.3.6.1.4.1.10520.2.1.1.35.24Notificationcps6000RetireDc1BdacurrentBattery On Discharge
1.3.6.1.4.1.10520.2.1.1.35.25Notificationcps6000RetireDc1HvacurrentHigh Voltage
1.3.6.1.4.1.10520.2.1.1.35.26Notificationcps6000RetireDc1HfvcurrentHigh Float Voltage
1.3.6.1.4.1.10520.2.1.1.35.27Notificationcps6000RetirePs1AmthcurrentHigh Ambient Temperature
1.3.6.1.4.1.10520.2.1.1.35.28Notificationcps6000RetirePs1AmtlcurrentLow Ambient Temperature
1.3.6.1.4.1.10520.2.1.1.35.29Notificationcps6000RetirePs1BblcurrentMemory Backup Battery Low
1.3.6.1.4.1.10520.2.1.1.35.30Notificationcps6000RetirePs1CchcurrentConfiguration Changed
1.3.6.1.4.1.10520.2.1.1.35.31Notificationcps6000RetirePs1ClccurrentClock Changed
1.3.6.1.4.1.10520.2.1.1.35.32Notificationcps6000RetirePs1EprcurrentExternal Password Reset
1.3.6.1.4.1.10520.2.1.1.35.33Notificationcps6000RetirePs1ExlcurrentExcessive Login Attempts
1.3.6.1.4.1.10520.2.1.1.35.34Notificationcps6000RetirePs1HclcurrentHistory Cleared
1.3.6.1.4.1.10520.2.1.1.35.35Notificationcps6000RetirePs1PfdcurrentPasswords At Default
1.3.6.1.4.1.10520.2.1.1.35.36Notificationcps6000RetirePs1PhtcurrentProcessor Halt
1.3.6.1.4.1.10520.2.1.1.35.37Notificationcps6000RetirePs1StfcurrentSelf Test Failed
1.3.6.1.4.1.10520.2.1.1.35.38Notificationcps6000RetirePs1PgicurrentProgram Line Invalid
1.3.6.1.4.1.10520.2.1.1.35.39Notificationcps6000RetirePs1Ax1currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.35.40Notificationcps6000RetirePs1Ax2currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.35.41Notificationcps6000RetirePs1Ax3currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.35.42Notificationcps6000RetirePs1Ax4currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.35.43Notificationcps6000RetirePs1Ax5currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.35.44Notificationcps6000RetirePs1Ax6currentAuxilliary Event 1
1.3.6.1.4.1.10520.2.1.1.35.45Notificationcps6000RetireAt1AtacurrentAlarm Test Active
1.3.6.1.4.1.10520.2.1.1.35.46Notificationcps6000RetireAt1AtbcurrentAlarm Test Aborted
1.3.6.1.4.1.10520.2.1.1.35.47Notificationcps6000RetireCp1CfacurrentConverter Fail
1.3.6.1.4.1.10520.2.1.1.35.48Notificationcps6000RetireCp1DfacurrentDistribution Fail
1.3.6.1.4.1.10520.2.1.1.35.49Notificationcps6000RetireCp1DidcurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.35.50Notificationcps6000RetireCp1MfacurrentMultiple Converter Fail
1.3.6.1.4.1.10520.2.1.1.35.51Notificationcps6000RetireBs1BsacurrentBoost State Alarm
1.3.6.1.4.1.10520.2.1.1.35.52Notificationcps6000RetireBr1BtacurrentBattery Test Active
1.3.6.1.4.1.10520.2.1.1.35.53Notificationcps6000RetireBr1BfacurrentBattery Test Failed
1.3.6.1.4.1.10520.2.1.1.35.54Notificationcps6000RetireBr1BthacurrentHigh Battery Temperature
1.3.6.1.4.1.10520.2.1.1.35.55Notificationcps6000RetireBr1IsdacurrentImminent Shutdown
1.3.6.1.4.1.10520.2.1.1.35.56Notificationcps6000RetireCn1CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.35.57Notificationcps6000RetireCn1CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.35.58Notificationcps6000RetireCn2CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.35.59Notificationcps6000RetireCn2CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.35.60Notificationcps6000RetireCn3CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.35.61Notificationcps6000RetireCn3CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.35.62Notificationcps6000RetireCn4CnocurrentContactor Open
1.3.6.1.4.1.10520.2.1.1.35.63Notificationcps6000RetireCn4CnfcurrentContactor Failed
1.3.6.1.4.1.10520.2.1.1.35.64Notificationcps6000RetireCm1CofcurrentQueue Overflow
1.3.6.1.4.1.10520.2.1.1.35.65Notificationcps6000RetireCm1CorcurrentNumber Did Not Respond
1.3.6.1.4.1.10520.2.1.1.35.66Notificationcps6000RetireCm1NnccurrentNumber Not Configured
1.3.6.1.4.1.10520.2.1.1.35.67Notificationcps6000RetirePo1PorcurrentNumber Did Not Respond
1.3.6.1.4.1.10520.2.1.1.35.68Notificationcps6000RetireRp1RfcurrentRinger Minor Fail
1.3.6.1.4.1.10520.2.1.1.35.69Notificationcps6000RetireRp1RpffcurrentRinger Fan Fail
1.3.6.1.4.1.10520.2.1.1.35.70Notificationcps6000RetireRp1RpxjcurrentRinger Major External Fault
1.3.6.1.4.1.10520.2.1.1.35.71Notificationcps6000RetireRp1RpxncurrentRinger Minor External Fault
1.3.6.1.4.1.10520.2.1.1.35.72Notificationcps6000RetireRp1RprlcurrentRinger Redundency Loss
1.3.6.1.4.1.10520.2.1.1.35.73Notificationcps6000RetireRp1RpfjcurrentRinger Major Fail
1.3.6.1.4.1.10520.2.1.1.35.74Notificationcps6000RetireUserDefinedcurrentThis may be a user defined event, or a new controller event.
1.3.6.1.4.1.10520.2.1.1.35.75Notificationcps6000RetireDc1IcrcurrentIncompatible Rectifier
1.3.6.1.4.1.10520.2.1.1.35.76Notificationcps6000RetireDc1RfncurrentRectifier Fan Fail
1.3.6.1.4.1.10520.2.1.1.35.77Notificationcps6000RetireDc1EmdcurrentEnergy Management Disabled
1.3.6.1.4.1.10520.2.1.1.35.78Notificationcps6000RetireCp1CfncurrentConverter Fan Minor
1.3.6.1.4.1.10520.2.1.1.35.79Notificationcps6000RetireCp1CfjcurrentConverter Fan Major
1.3.6.1.4.1.10520.2.1.1.35.80Notificationcps6000RetireCp1IcccurrentIncompatible Converter Alarm
1.3.6.1.4.1.10520.2.1.1.35.81Notificationcps6000RetireCp1HvacurrentConverter High Voltage Major
1.3.6.1.4.1.10520.2.1.1.35.82Notificationcps6000RetireCp1HfvcurrentConverter High Voltage Minor
1.3.6.1.4.1.10520.2.1.1.35.83Notificationcps6000RetireCp1VlacurrentConverter Very Low Voltage
1.3.6.1.4.1.10520.2.1.1.35.84Notificationcps6000RetireCp1RlcurrentConverter Redundancy Loss
1.3.6.1.4.1.10520.2.1.1.35.85Notificationcps6000RetireBr1MdpcurrentVoltage Duplicate ID
1.3.6.1.4.1.10520.2.1.1.35.86Notificationcps6000RetireBr1MzdcurrentVoltage ID Not Configured
1.3.6.1.4.1.10520.2.1.1.35.87Notificationcps6000RetireBr1ScdacurrentShorted Cell Detected
1.3.6.1.4.1.10520.2.1.1.35.88Notificationcps6000RetireRp1RcdpcurrentRinger ID Conflict
1.3.6.1.4.1.10520.2.1.1.35.89Notificationcps6000RetireFt1FmicurrentFan Fail Minor
1.3.6.1.4.1.10520.2.1.1.35.90Notificationcps6000RetireFt1FmjcurrentFan Fail Major
1.3.6.1.4.1.10520.2.1.1.35.91Notificationcps6000RetireFt1IpicurrentInput Power Minor
1.3.6.1.4.1.10520.2.1.1.35.92Notificationcps6000RetireFt1IpjcurrentInput Power Major
1.3.6.1.4.1.10520.2.1.1.35.93Notificationcps6000RetireFt1CbtcurrentCircuit Breaker Trip
1.3.6.1.4.1.10520.2.1.1.35.94Notificationcps6000RetireFt1CtfcurrentCircuit Fail
1.3.6.1.4.1.10520.2.1.1.35.95Notificationcps6000RetireFt1MctfcurrentMultiple Circuit Fail
1.3.6.1.4.1.10520.2.1.1.35.96Notificationcps6000RetireFt1LorcurrentLoss of Redundancy
1.3.6.1.4.1.10520.2.1.1.35.97Notificationcps6000RetireFt1LdacurrentLoad Drop Alarm
1.3.6.1.4.1.10520.2.1.1.35.98Notificationcps6000RetireFt1LsacurrentLoad Share Alarm
1.3.6.1.4.1.10520.2.1.1.35.99Notificationcps6000RetireFt1LtacurrentLine Test Failed Alarm
1.3.6.1.4.1.10520.2.1.1.35.100Notificationcps6000RetireDc1LsfcurrentLoadshare Fail
1.3.6.1.4.1.10520.2.1.1.36Tablecps6000MsvTablenot-accessiblecurrentTable of all Midstring Voltage Monitor data
1.3.6.1.4.1.10520.2.1.1.36.1Rowcps6000MsvEntrynot-accessiblecurrentEntry of information for one Midstring Voltage Monitor
1.3.6.1.4.1.10520.2.1.1.36.1.1Columncps6000MsvEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.36.1.2Columncps6000MsvEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.36.1.3Columncps6000MsvEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.36.1.4Columncps6000MsvEntrySttread-onlycurrentState
1.3.6.1.4.1.10520.2.1.1.36.1.5Columncps6000MsvEntryValread-onlycurrentValue (Volts)
1.3.6.1.4.1.10520.2.1.1.36.1.6Columncps6000MsvEntryDidread-onlycurrentID Conflict
1.3.6.1.4.1.10520.2.1.1.37Nodecps6000Ft1
1.3.6.1.4.1.10520.2.1.1.37.1Scalarcps6000Ft1Ideread-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.37.2Scalarcps6000Ft1Desread-onlycurrentDescription
1.3.6.1.4.1.10520.2.1.1.37.3Scalarcps6000Ft1Sttread-onlycurrentState Values: PRESENT, NONE
1.3.6.1.4.1.10520.2.1.1.37.4Scalarcps6000Ft1Iadcread-onlycurrentInput Current (Amps)
1.3.6.1.4.1.10520.2.1.1.37.5Scalarcps6000Ft1Lteread-onlycurrentLine Test Enable Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.37.6Scalarcps6000Ft1Ltfread-onlycurrentLine Test Frequency (Days)
1.3.6.1.4.1.10520.2.1.1.37.7Scalarcps6000Ft1Fmiread-onlycurrentFan Fail Minor
1.3.6.1.4.1.10520.2.1.1.37.8Scalarcps6000Ft1Fmjread-onlycurrentFan Fail Major
1.3.6.1.4.1.10520.2.1.1.37.9Scalarcps6000Ft1Ipiread-onlycurrentInput Power Minor
1.3.6.1.4.1.10520.2.1.1.37.10Scalarcps6000Ft1Ipjread-onlycurrentInput Power Major
1.3.6.1.4.1.10520.2.1.1.37.11Scalarcps6000Ft1Cbtread-onlycurrentCircuit Breaker Trip
1.3.6.1.4.1.10520.2.1.1.37.12Scalarcps6000Ft1Ctfread-onlycurrentCircuit Fail
1.3.6.1.4.1.10520.2.1.1.37.13Scalarcps6000Ft1Mctfread-onlycurrentMultiple Circuit Fail
1.3.6.1.4.1.10520.2.1.1.37.14Scalarcps6000Ft1Lorread-onlycurrentLoss of Redundancy
1.3.6.1.4.1.10520.2.1.1.37.15Scalarcps6000Ft1Ldaread-onlycurrentLoad Drop Alarm
1.3.6.1.4.1.10520.2.1.1.37.16Scalarcps6000Ft1Lsaread-onlycurrentLoad Share Alarm
1.3.6.1.4.1.10520.2.1.1.37.17Scalarcps6000Ft1Ltaread-onlycurrentLine Test Failed Alarm
1.3.6.1.4.1.10520.2.1.1.37.18Scalarcps6000Ft1Remread-writecurrentRestart Faulted Circuits Values: disable(0), enable(1)
1.3.6.1.4.1.10520.2.1.1.37.19Scalarcps6000Ft1Tofread-writecurrentTurn Off Circuits Values: disabled(0), faulted(1), faultedAndNoLoad(2)
1.3.6.1.4.1.10520.2.1.1.38Tablecps6000GrpTablenot-accessiblecurrentTable of all Circuit Group data
1.3.6.1.4.1.10520.2.1.1.38.1Rowcps6000GrpEntrynot-accessiblecurrentEntry of information for one Circuit Group
1.3.6.1.4.1.10520.2.1.1.38.1.1Columncps6000GrpEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.38.1.2Columncps6000GrpEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.38.1.3Columncps6000GrpEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.38.1.4Columncps6000GrpEntryCctread-onlycurrentCircuits
1.3.6.1.4.1.10520.2.1.1.38.1.5Columncps6000GrpEntryTadcread-onlycurrentTotal Current (mA)
1.3.6.1.4.1.10520.2.1.1.38.1.6Columncps6000GrpEntryAadcread-onlycurrentAverage Current (mA)
1.3.6.1.4.1.10520.2.1.1.38.1.7Columncps6000GrpEntryCapread-onlycurrentCapacity (mA)
1.3.6.1.4.1.10520.2.1.1.38.1.8Columncps6000GrpEntryLrsread-onlycurrentLoss of Redundancy Status
1.3.6.1.4.1.10520.2.1.1.38.1.9Columncps6000GrpEntryOlcapread-onlycurrentOnline Capacity (mA)
1.3.6.1.4.1.10520.2.1.1.39Tablecps6000ShfTablenot-accessiblecurrentTable of all Converter Shelf data
1.3.6.1.4.1.10520.2.1.1.39.1Rowcps6000ShfEntrynot-accessiblecurrentEntry of information for one Converter Shelf
1.3.6.1.4.1.10520.2.1.1.39.1.1Columncps6000ShfEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.39.1.2Columncps6000ShfEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.39.1.3Columncps6000ShfEntryDesread-onlycurrentDescription
1.3.6.1.4.1.10520.2.1.1.39.1.4Columncps6000ShfEntrySttread-onlycurrentState Values: PRESENT, MISSING
1.3.6.1.4.1.10520.2.1.1.39.1.5Columncps6000ShfEntryIadcread-onlycurrentInput Current (Amps)
1.3.6.1.4.1.10520.2.1.1.39.1.6Columncps6000ShfEntryIa1read-onlycurrentInput Voltage A1 Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.7Columncps6000ShfEntryIa2read-onlycurrentInput Voltage A2 Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.8Columncps6000ShfEntryIb1read-onlycurrentInput Voltage B1 Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.9Columncps6000ShfEntryIb2read-onlycurrentInput Voltage B2 Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.10Columncps6000ShfEntryUfnread-onlycurrentUpper Fan Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.11Columncps6000ShfEntryLfnread-onlycurrentLower Fan Fail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.12Columncps6000ShfEntryCbaread-onlycurrentCircuit Breaker A Trip Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.13Columncps6000ShfEntryCbbread-onlycurrentCircuit Breaker B Trip Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.14Columncps6000ShfEntryCvjread-onlycurrentConverter Major Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.15Columncps6000ShfEntryCviread-onlycurrentConverter Minor Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.39.1.16Columncps6000ShfEntryNocread-onlycurrentNumber of Converters in Shelf
1.3.6.1.4.1.10520.2.1.1.40Tablecps6000CctTablenot-accessiblecurrentTable of all Circuit data
1.3.6.1.4.1.10520.2.1.1.40.1Rowcps6000CctEntrynot-accessiblecurrentEntry of information for one Circuit
1.3.6.1.4.1.10520.2.1.1.40.1.1Columncps6000CctEntryIndexread-onlycurrentTable Index
1.3.6.1.4.1.10520.2.1.1.40.1.2Columncps6000CctEntryIderead-onlycurrentIdentifier
1.3.6.1.4.1.10520.2.1.1.40.1.3Columncps6000CctEntryDesread-writecurrentDescription
1.3.6.1.4.1.10520.2.1.1.40.1.4Columncps6000CctEntryVdcread-onlycurrentVoltage (Volts)
1.3.6.1.4.1.10520.2.1.1.40.1.5Columncps6000CctEntryAdcread-onlycurrentCurrent (mA)
1.3.6.1.4.1.10520.2.1.1.40.1.6Columncps6000CctEntrySttread-writecurrentState Values: ON, STANDBY, MISSING, VACANT
1.3.6.1.4.1.10520.2.1.1.40.1.7Columncps6000CctEntryTmpread-onlycurrentTemperature (C)
1.3.6.1.4.1.10520.2.1.1.40.1.8Columncps6000CctEntryCapread-onlycurrentCapacity (mA)
1.3.6.1.4.1.10520.2.1.1.40.1.9Columncps6000CctEntryCliread-onlycurrentCLEI Code
1.3.6.1.4.1.10520.2.1.1.40.1.10Columncps6000CctEntrySnmread-onlycurrentSerial Number
1.3.6.1.4.1.10520.2.1.1.40.1.11Columncps6000CctEntryMdlread-onlycurrentModel
1.3.6.1.4.1.10520.2.1.1.40.1.12Columncps6000CctEntryCcdread-onlycurrentComcode
1.3.6.1.4.1.10520.2.1.1.40.1.13Columncps6000CctEntryCflread-onlycurrentFail Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.14Columncps6000CctEntryOvread-onlycurrentOver Voltage Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.15Columncps6000CctEntryClread-onlycurrentCurrent Limit Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.16Columncps6000CctEntryGfread-onlycurrentGround Fault Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.17Columncps6000CctEntryUvread-onlycurrentUnder Voltage Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.18Columncps6000CctEntryOtread-onlycurrentOver Temperature Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.19Columncps6000CctEntryLdsread-onlycurrentLoad Drop Status Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.20Columncps6000CctEntryLssread-onlycurrentLoad Share Status Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.21Columncps6000CctEntryLtsread-onlycurrentLine Test Status Values: inactive(0), active(1)
1.3.6.1.4.1.10520.2.1.1.40.1.22Columncps6000CctEntryIlrread-onlycurrentInitial Line Resistance (Ohms)
1.3.6.1.4.1.10520.2.1.1.40.1.23Columncps6000CctEntryAlrread-onlycurrentActual Line Resistance (Ohms)
1.3.6.1.4.1.10520.2.2Nodeprototypes