MIB Viewer

DESCH-PSC3-BASE-MIB

118 objects
MIB for managing a DC power system with PSC 3.
Imported Objects
DESCH-GLOBAL-REGdeschModules deschPsc3
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Gauge32 Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.20246.2.1.1.2IdentitydeschPsc3BaseMibModuleMIB for managing a DC power system with PSC 3.
1.3.6.1.4.1.20246.2.3.1.1.1NodedeschPsc3BaseMib
1.3.6.1.4.1.20246.2.3.1.1.1.1NodedeschControllerConfs
1.3.6.1.4.1.20246.2.3.1.1.1.1.1NodedeschControllerGroups
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1GroupdeschSystemInfoGroupcurrentThe collection of system info scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2GroupdeschSystemAlarmGroupcurrentThe collection of system alarm scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3GroupdeschSystemMonitorGroupcurrentThe collection of system monitor scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4GroupdeschRectifiersGroupcurrentThe collection of rectifier scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5GroupdeschEventHistoryTableGroupcurrentThe collection of event history table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6GroupdeschAlarmTableGroupcurrentThe collection of alarm table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7GroupdeschRectifierTableGroupcurrentThe collection of rectifier table objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8GroupdeschNotificationsGroupcurrentThe group of all controller notifications.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9GroupdeschGenericAlarmTableGroupcurrentAssignment of events to alarm table entries.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10GroupdeschBatteryGroupcurrentThe collection of battery scalar objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11GroupdeschControlEventTableGroupcurrentAssignment of control events to table entries.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12GroupdeschTrapDestinationTableGroupcurrentTrap destionation table.
1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13GroupdeschMiscGroupcurrentThe collection of miscellaneous objects.
1.3.6.1.4.1.20246.2.3.1.1.1.1.2NodedeschControllerCompl
1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1CompliancedeschControllerBasicComplcurrentThe basic implementation requirements for the controller MIB.
1.3.6.1.4.1.20246.2.3.1.1.1.2NodedeschControllerObjects
1.3.6.1.4.1.20246.2.3.1.1.1.2.1NodedcSystemInfo
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1ScalardcSiteNameread-onlycurrentAn administratively-assigned site name for this DC-power system.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2ScalardcSystemNameread-onlycurrentAn administratively-assigned system name for this DC-power system.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3ScalardcSystemDateTimeread-writecurrentISO 8601 representation of controller's local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'.
1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4ScalardcSoftwareVersionread-onlycurrentThe controller's software version e.g V2.50Build1.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2NodedcSystemAlarms
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1TabledcEventHistoryTablenot-accessiblecurrentController's event history table that shows the content of the default log file.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1RowdcEventHistoryEntrynot-accessiblecurrentA particular Event History entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1ColumndcEventHistoryIndexnot-accessiblecurrentTable index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2ColumndcEventHistoryTimestampread-onlycurrentISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3ColumndcEventHistoryMessageread-onlycurrentEvent message of a particular entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2TabledcAlarmTablenot-accessiblecurrentTable that shows all currently active alarm sources causing urgent or non-urgent alarm(s).
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1RowdcAlarmEntrynot-accessiblecurrentA particular active alarm source entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1ColumndcAlarmIndexnot-accessiblecurrentTable index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2ColumndcAlarmEventCategoryread-onlycurrentSpecifies the type of alarm source.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3ColumndcAlarmEventNameread-onlycurrentName of a particular alarm source entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4ColumndcAlarmEventIdentifierread-onlycurrentUnique alarm event identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5ColumndcAlarmEventValueread-onlycurrentEvent status that corresponds to alarm event identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3ScalardcNumberUrgentAlarmsread-onlycurrentNumber of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4ScalardcNumberNonUrgentAlarmsread-onlycurrentNumber of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5ScalardcMainsFailureAlarmread-onlycurrentMains failure alarm.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6ScalardcUrgentAlarmIdentifierread-onlycurrentCurrent unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7ScalardcUrgentAlarmValueread-onlycurrentCurrent urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8ScalardcNonUrgentAlarmIdentifierread-onlycurrentCurrent unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9ScalardcNonUrgentAlarmValueread-onlycurrentCurrent non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10ScalardcUrgentAlarmNameread-onlycurrentCurrent alarm name for urgent alarm that corresponds to urgent alarm identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11ScalardcNonUrgentAlarmNameread-onlycurrentCurrent alarm name for active non urgent alarm that corresponds to non urgent alarm identifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12TabledcGenericAlarmTablenot-accessiblecurrentTable that shows ten alarm event assignments that can be configured via WEB interface.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1RowdcGenericAlarmEntrynot-accessiblecurrentA particular generic alarm entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1ColumndcGenericAlarmIndexnot-accessiblecurrentTable index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2ColumndcGenericAlarmEventNameread-onlycurrentPlain text name of the assigned alarm event. Empty if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3ColumndcGenericAlarmEventIdentifierread-onlycurrentUnique numeric identifier of the assigned alarm event. Zero if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4ColumndcGenericAlarmEventValueread-onlycurrentCurrent value of the assigned alarm event. Value is false if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3NodedcSystemMonitor
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1ScalardcSystemVoltageread-onlycurrentThe measured system voltage. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2ScalardcLoadCurrentread-onlycurrentThe measured load current. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3ScalardcBatteryCurrentread-onlycurrentThe measured battery current. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4ScalardcBatteryTemperatureread-onlycurrentThe measured battery temperature. The max. value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5ScalardcChargeStateread-onlycurrentBattery charge state.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6ScalardcCurrentLimitread-onlycurrentBattery current limit.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7ScalardcRectifierCurrentread-onlycurrentTotal current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8ScalardcSystemPowerread-onlycurrentCalculated system power. The maximum value 4294967295 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4NodedcRectifier
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1ScalardcNumberRectifiersread-onlycurrentThe configured number of rectifiers plugged into the system. The maximum number of rectifiers is 128.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2ScalardcNumberRectifiersFailureread-onlycurrentNumber of rectifiers that are not properly working.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3ScalardcNumberRectifiersOkayread-onlycurrentNumber of rectifiers that are properly working.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4TabledcRectifierTablenot-accessiblecurrentTable that shows all currently active rectifier modules.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1RowdcRectifierEntrynot-accessiblecurrentA particular rectifier entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1ColumndcRectifierIndexnot-accessiblecurrentTable index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2ColumndcRectifierIdentifierread-onlycurrentUnique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier.
1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3ColumndcRectifierStatusread-onlycurrentSpecifies status of rectifiers.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5NodedcBattery
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1NodedcFloatCharge
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1ScalardcUsys20read-onlycurrentVoltage to regulate to at 20oC. If temperature compensation is used, this voltage will vary. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.2ScalardcTcoeffread-onlycurrentTemperature compensation coefficient for system voltage. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.3ScalardcTcLowread-onlycurrentLow limit for the area in which the temperature compensation is active. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.4ScalardcTcHighread-onlycurrentHigh limit for the area in which the temperature compensation is active. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2NodedcBatteryTest
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1NodedcBatteryTestParameter
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1ScalardcUsupportread-onlycurrentSupport charge voltage for the battery. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2ScalardcDurationread-onlycurrentBattery test duration. Zero indicates that this value is not set.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3ScalardcIntervalread-onlycurrentMinimal time between programmed battery tests. Zero indicates that this value is not set.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4ScalardcDischargeCurrentread-onlycurrentBattery discharge current. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2NodedcBatteryTestResult
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1ScalardcTestDateTimeread-onlycurrentISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test res…
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2ScalardcTestResultread-onlycurrentResult of last performed battery test.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3ScalardcTestEndVoltageread-onlycurrentSystem voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3ScalardcBatteryTestControlread-writecurrentStart/stop of battery test. This special charge mode is used to check the capacity of a battery. Please not that a battery test can be started even if the batt…
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4ScalardcBatteryTestStatusread-onlycurrentCurrent status of battery test.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5ScalardcBatteryTestFailureEventread-writecurrentReset battery test failure event.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3NodedcBatteryParameter
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1ScalardcTotalBatteryCapacityread-onlycurrentTotal battery capacity for all available batteries.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4NodedcEqualize
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1ScalardcEqualizeControlread-writecurrentStart/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells…
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2ScalardcEqualizeStatusread-onlycurrentCurrent status of battery equalize.
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5NodedcBoostCharge
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1ScalardcBoostChargeControlread-writecurrentStart/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a di…
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2ScalardcBoostChargeStatusread-onlycurrentCurrent status of boost charge.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6NodedcInputOutput
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1TabledcControlEventTablenot-accessiblecurrentTable that shows ten output event assignments that can be configured via WEB interface.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1RowdcControlEventEntrynot-accessiblecurrentA particular generic output entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1ColumndcControlEventIndexnot-accessiblecurrentTable index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2ColumndcControlEventNameread-onlycurrentPlain text name of the assigned control event. Empty if not configure.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3ColumndcControlEventIdentifierread-onlycurrentUnique numeric identifier of the assigned control event. Zero if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4ColumndcControlEventValueread-writecurrentCurrent value of the assigned control event. Value is false if not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7NodedcMisc
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1TabledcTrapDestinationTablenot-accessiblecurrentTrap table that shows all configured trap destinations.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1RowdcTrapDestinationEntrynot-accessiblecurrentA particular trap destination entry.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1ColumndcTrapDestinationIndexnot-accessiblecurrentTable index.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2ColumndcTrapDestinationIpread-writecurrentIP address of the trap destination. Value is 0.0.0.0 if IP address is not configured.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3ColumndcTrapDestinationPortread-writecurrentPort number of the trap destination. By default port 162 is used.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2ScalardcFileProcessingStatusread-onlycurrentFile processing status for software and setup up/downloads.
1.3.6.1.4.1.20246.2.3.1.1.1.2.7.3ScalardcSetupConfigurationread-writecurrentSave current setup configuration to non-volatile memory.
1.3.6.1.4.1.20246.2.3.1.1.1.3NodedeschControllerEvents
1.3.6.1.4.1.20246.2.3.1.1.1.3.1NodedeschControllerEventObjects
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0NodedeschControllerEventsV2
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1NotificationsystemNonUrgentAlarmcurrentThe controller reports that one or more elements have changed into none urgent alarm state.
1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2NotificationsystemUrgentAlarmcurrentThe controller reports that one or more elements have changed into urgent alarm state.