An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1)
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.12148IdentityeltekAn ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Intern…
1.3.6.1.4.1.12148.9NodeeltekDistributedPlantV3
1.3.6.1.4.1.12148.9.1NodecontrolSystem
1.3.6.1.4.1.12148.9.1.1NodesystemTime
1.3.6.1.4.1.12148.9.1.1.1ScalarsystemTimeTimeread-onlycurrentThe system date and time. Used for event timestamps and logging
1.3.6.1.4.1.12148.9.1.2ScalarsystemInfoRefreshread-writecurrentThis is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make su…
1.3.6.1.4.1.12148.9.1.3ScalarsystemTrapRepeatRateread-writecurrentThis object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
1.3.6.1.4.1.12148.9.1.4ScalarsystemSendOffTrapread-writecurrentA separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
1.3.6.1.4.1.12148.9.1.5ScalarsystemNumOfControlUnitsread-onlycurrentThe number of SmartPacks in a distributed system.
1.3.6.1.4.1.12148.9.1.6ScalarsystemControlUnitIndexaccessible-for-notifycurrentIndex used for navigating in the table for configurable inputs.
1.3.6.1.4.1.12148.9.1.7TablesystemControlUnitTablenot-accessiblecurrentThis table contains the status of the programmable inputs. There is one row for each SmartPack.
1.3.6.1.4.1.12148.9.1.7.1RowsystemControlUnitEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.1.7.1.1ColumninputControlUnitIDread-onlycurrentThe ID of which SmartPack to be read.
1.3.6.1.4.1.12148.9.1.7.1.2ColumninputUserConfigurable1read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.3ColumninputUserConfigurable2read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.4ColumninputUserConfigurable3read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.5ColumninputUserConfigurable4read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.6ColumninputUserConfigurable5read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.7ColumninputUserConfigurable6read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.8ColumninputUserConfigurable7read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.9ColumninputUserConfigurable8read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.10ColumninputUserConfigurable9read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.7.1.11ColumninputUserConfigurable10read-onlycurrentProgrammable input status. The description of the input is found in the systemControlUnitInputTable
1.3.6.1.4.1.12148.9.1.8ScalarsystemLinkStatusread-onlycurrentA flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag s…
1.3.6.1.4.1.12148.9.1.9ScalarsystemInitiateEEPROMread-writedeprecatedPushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used…
1.3.6.1.4.1.12148.9.1.10ScalarsystemLastDigInputaccessible-for-notifycurrentThe last Prog.Input that generated a trap. Used by Traps only.
1.3.6.1.4.1.12148.9.1.11ScalarsystemTrapCounteraccessible-for-notifycurrentThe number of times a trap has been repeated.. Only acessible for Traps.
1.3.6.1.4.1.12148.9.1.12ScalarsystemHeartBeatTrapRepeatRateread-writecurrentThe repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap.
1.3.6.1.4.1.12148.9.1.13ScalarsystemResetManualAlarmsread-writecurrentA pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this.
1.3.6.1.4.1.12148.9.1.14ScalarsystemControlUnitInputIndexaccessible-for-notifycurrentIndex used for navigating in the table for configurable inputs.
1.3.6.1.4.1.12148.9.1.15TablesystemControlUnitInputTablenot-accessiblecurrentThis table contains the description of the programmable inputs. There is one row for each SmartPack. Programmable input alarms will have description attached t…
1.3.6.1.4.1.12148.9.1.15.1RowsystemControlUnitInputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.1.15.1.1ColumninputUnitIDread-onlycurrentThe ID of which SmartPack to be read.
1.3.6.1.4.1.12148.9.1.15.1.2ColumninputUserConfigurableText1read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.1.
1.3.6.1.4.1.12148.9.1.15.1.3ColumninputUserConfigurableText2read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.2.
1.3.6.1.4.1.12148.9.1.15.1.4ColumninputUserConfigurableText3read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.3.
1.3.6.1.4.1.12148.9.1.15.1.5ColumninputUserConfigurableText4read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.4.
1.3.6.1.4.1.12148.9.1.15.1.6ColumninputUserConfigurableText5read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.5.
1.3.6.1.4.1.12148.9.1.15.1.7ColumninputUserConfigurableText6read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.6.
1.3.6.1.4.1.12148.9.1.15.1.8ColumninputUserConfigurableText7read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.7.
1.3.6.1.4.1.12148.9.1.15.1.9ColumninputUserConfigurableText8read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.8.
1.3.6.1.4.1.12148.9.1.15.1.10ColumninputUserConfigurableText9read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.9.
1.3.6.1.4.1.12148.9.1.15.1.11ColumninputUserConfigurableText10read-onlycurrentProgrammable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Smartpack ID>.10.
1.3.6.1.4.1.12148.9.1.16ScalarsystemResetCtrlSystemread-writedeprecatedA pushbutton function that resets the control system. Configuration data will be kept.
1.3.6.1.4.1.12148.9.2NodedcSystem
1.3.6.1.4.1.12148.9.2.1NodedcPlant
1.3.6.1.4.1.12148.9.2.1.3NodesystemSiteInfo
1.3.6.1.4.1.12148.9.2.1.3.1ScalarsystemSiteInfoCustomerread-onlycurrentThe Customer name (as stored in the Smartpack Control Unit).
1.3.6.1.4.1.12148.9.2.1.3.2ScalarsystemSiteInfoLocationread-onlycurrentThe system/site Location details (as stored in the Smartpack Control Unit).
1.3.6.1.4.1.12148.9.2.1.3.3ScalarsystemSiteInfoMessage1read-onlycurrentThe system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.9.2.1.3.4ScalarsystemSiteInfoMessage2read-onlycurrentThe system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes.
1.3.6.1.4.1.12148.9.2.1.3.5ScalarsystemSiteInfoInstalledDateread-onlycurrentThe system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes.
1.3.6.1.4.1.12148.9.2.1.3.6ScalarsystemSiteInfoControllerTyperead-onlycurrentThe system Controller Module currently connected. Smartpack=3
1.3.6.1.4.1.12148.9.2.1.3.7ScalarsystemSiteInfoSystemSeriaNumread-onlycurrentThe serial number for the complete system.
1.3.6.1.4.1.12148.9.2.1.3.8ScalarsystemSiteInfoControllerSeriaNumread-onlycurrentThe serial number for the SmartPack 1.
1.3.6.1.4.1.12148.9.2.1.4ScalarsystemNominalVoltageread-onlycurrentThe nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V
1.3.6.1.4.1.12148.9.2.2ScalarsystemOperationalStatusread-onlycurrentA summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery t…
1.3.6.1.4.1.12148.9.3Nodebattery
1.3.6.1.4.1.12148.9.3.1ScalarbatteryNameread-onlycurrentA descriptive name of the battery installed in the system.
1.3.6.1.4.1.12148.9.3.2ScalarbatteryVoltageread-onlycurrentThe measured battery voltage.
1.3.6.1.4.1.12148.9.3.3ScalarbatteryCurrentread-onlycurrentThe measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the …
1.3.6.1.4.1.12148.9.3.4ScalarbatteryTempread-onlycurrentThe highest value of the enabled battery temperature measurements. Depending on the global setting in the SmartPack, this value will be presented in Celsius or…
1.3.6.1.4.1.12148.9.3.5ScalarbatteryBreakerStatusread-onlycurrentThe state of the battery fuses/breakers can be either normal(0) or alarm(1).
1.3.6.1.4.1.12148.9.3.6ScalarbatteryChargeCurrentLimitCtrlread-writecurrentEnable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.9.3.7ScalarbatteryChargeCurrentLimitValueread-writecurrentBattery charging current limit value. Used only when AC source is mains feed.
1.3.6.1.4.1.12148.9.3.8ScalarbatteryTempCompEnableread-writecurrentEnable (0) or Disable (1) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.9.3.9ScalarbatteryFloatVoltConfigread-writecurrentThe Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
1.3.6.1.4.1.12148.9.3.10ScalarbatteryBoostVoltConfigread-writecurrentThe Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.9.3.11ScalarbatteryHighMajorAlarmVoltageConfigread-writecurrentThe Major High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.9.3.12ScalarbatteryHighMinorAlarmVoltageConfigread-writecurrentThe Minor High Battery Voltage alarm limit set voltage
1.3.6.1.4.1.12148.9.3.13ScalarbatteryLowMajorAlarmVoltageConfigread-writecurrentThe Major Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.9.3.14ScalarbatteryLowMinorAlarmVoltageConfigread-writecurrentThe Minor Low Battery Voltage Alarm limit set voltage
1.3.6.1.4.1.12148.9.3.15ScalarbatteryStartManualTestread-writecurrentThis pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.9.3.16ScalarbatteryStartManualBoostread-writecurrentThis pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.9.3.17NodebatteryLVD
1.3.6.1.4.1.12148.9.3.17.1ScalarbatteryLVDStatusread-onlycurrentThe Battery Contactor is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.3.17.2ScalarbatteryLVDDisconnectVoltageread-writecurrentThe Battery Contactors Disconnect Voltage
1.3.6.1.4.1.12148.9.3.17.3ScalarbatteryLVDConnectVoltageread-writecurrentThe Battery Contactors Reconnect Voltage
1.3.6.1.4.1.12148.9.3.18ScalarbatteryBanksNumofBanksread-onlycurrentThe number of Smartpacks that is used to measure battery parameters.
1.3.6.1.4.1.12148.9.3.19NodebatteryBanks
1.3.6.1.4.1.12148.9.3.19.1ScalarbatterySymmetryDeltaLimitVoltageread-writecurrentThe allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.
1.3.6.1.4.1.12148.9.3.19.2ScalarbatteryBanksIndexaccessible-for-notifycurrentIndex used for navigating the rows 1..8 of batteryBanksTable
1.3.6.1.4.1.12148.9.3.19.3TablebatteryBanksTablenot-accessiblecurrentA table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments.
1.3.6.1.4.1.12148.9.3.19.3.1RowbatteryBanksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.3.19.3.1.1ColumnbatteryBankIDread-onlycurrentThe ID of the selected row in the table. i.e. the battery bank.
1.3.6.1.4.1.12148.9.3.19.3.1.2ColumnbatteryBanksSymmetry1enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.3ColumnbatteryBanksSymmetry1statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.4ColumnbatteryBanksSymmetry1deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.5ColumnbatteryBanksSymmetry2enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.6ColumnbatteryBanksSymmetry2statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.7ColumnbatteryBanksSymmetry2deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.8ColumnbatteryBanksSymmetry3enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.9ColumnbatteryBanksSymmetry3statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.10ColumnbatteryBanksSymmetry3deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.11ColumnbatteryBanksSymmetry4enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.12ColumnbatteryBanksSymmetry4statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.13ColumnbatteryBanksSymmetry4deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.14ColumnbatteryBanksSymmetry5enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.15ColumnbatteryBanksSymmetry5statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.16ColumnbatteryBanksSymmetry5deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.17ColumnbatteryBanksSymmetry6enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.18ColumnbatteryBanksSymmetry6statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.19ColumnbatteryBanksSymmetry6deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.20ColumnbatteryBanksSymmetry7enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.21ColumnbatteryBanksSymmetry7statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.22ColumnbatteryBanksSymmetry7deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.3.1.23ColumnbatteryBanksSymmetry8enableread-writecurrentEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
1.3.6.1.4.1.12148.9.3.19.3.1.24ColumnbatteryBanksSymmetry8statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.19.3.1.25ColumnbatteryBanksSymmetry8deltaVoltageread-onlycurrentThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it wi…
1.3.6.1.4.1.12148.9.3.19.4ScalarbatteryBanksNumberOfStringsread-onlycurrentNumber of strings in the power system.
1.3.6.1.4.1.12148.9.3.19.5ScalarbatteryBanksExtensionIndexaccessible-for-notifycurrentIndex used for navigating the rows 1..8 of batteryBanksExtensionTable
1.3.6.1.4.1.12148.9.3.19.6TablebatteryBanksExtensionTablenot-accessiblecurrentThis table shows the measured value on the symmetry inputs.
1.3.6.1.4.1.12148.9.3.19.6.1RowbatteryBanksExtensionEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.3.19.6.1.1ColumnbatteryBanksExtensionIDread-onlycurrentThe ID of the selected row in the table. i.e. the battery bank.
1.3.6.1.4.1.12148.9.3.19.6.1.2ColumnbatteryBanksExtensionSymmetryInputValue1read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.3ColumnbatteryBanksExtensionSymmetryInputValue2read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.4ColumnbatteryBanksExtensionSymmetryInputValue3read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.5ColumnbatteryBanksExtensionSymmetryInputValue4read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.6ColumnbatteryBanksExtensionSymmetryInputValue5read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.7ColumnbatteryBanksExtensionSymmetryInputValue6read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.8ColumnbatteryBanksExtensionSymmetryInputValue7read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.19.6.1.9ColumnbatteryBanksExtensionSymmetryInputValue8read-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.20NodebatteryCapacityData
1.3.6.1.4.1.12148.9.3.20.1ScalarbatteryTimeToDisconnectread-onlycurrentRemaining time to low voltage battery disconnect.
1.3.6.1.4.1.12148.9.3.20.2ScalarbatteryCapacityLeftread-onlycurrentAmpere hours left in the battery.
1.3.6.1.4.1.12148.9.3.20.3ScalarbatteryCapacityUsedread-onlycurrentAmpere hours consumed.
1.3.6.1.4.1.12148.9.3.20.4ScalarbatteryCapacityTotalread-onlycurrentThis is the total Ampere hours of the battery. This value is the installed capacity compensated with the last battery tests quality level
1.3.6.1.4.1.12148.9.3.20.5ScalarbatteryQualityread-onlycurrentThis is the battery quality (%) of the latest battery test.
1.3.6.1.4.1.12148.9.3.21NodebatteryMonitorUnits
1.3.6.1.4.1.12148.9.3.21.1ScalarbattmonNumberOfUnitsread-onlycurrentNumber of battery monitor units in the power system.
1.3.6.1.4.1.12148.9.3.21.2ScalarbattmonUnitsIndexaccessible-for-notifycurrentIndex used for navigating the rows 1..14 of battmonUnitsTable
1.3.6.1.4.1.12148.9.3.21.3TablebattmonUnitsTablenot-accessiblecurrentA table of up to 14 battery monitor control units.
1.3.6.1.4.1.12148.9.3.21.3.1RowbattmonUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.9.3.21.3.1.1ColumnbatteryMonitorIDread-onlycurrentThe ID of the selected row
1.3.6.1.4.1.12148.9.3.21.3.1.2ColumnbatteryMonitorSymmetry1statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.3ColumnbatteryMonitorSymmetry1InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.4ColumnbatteryMonitorSymmetry2statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.5ColumnbatteryMonitorSymmetry2InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.6ColumnbatteryMonitorSymmetry3statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.7ColumnbatteryMonitorSymmetry3InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.8ColumnbatteryMonitorSymmetry4statusread-onlycurrentContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
1.3.6.1.4.1.12148.9.3.21.3.1.9ColumnbatteryMonitorSymmetry4InputValueread-onlycurrentThe measured voltage on the symmetry input.
1.3.6.1.4.1.12148.9.3.21.3.1.10ColumnbatteryMonitorCurrentValueread-onlycurrentThe measured current to/from the battery.
1.3.6.1.4.1.12148.9.3.21.3.1.11ColumnbatteryMonitorFuseStatusread-onlycurrentThe state of the battery fuse/breaker can be either normal(0) or alarm(1).
1.3.6.1.4.1.12148.9.3.21.3.1.12ColumnbatteryMonitorTemperatureread-onlycurrentThe battery temperature.
1.3.6.1.4.1.12148.9.3.22ScalarbatteryHighMajorTempAlarmLevelread-writecurrentThis is the Major High Temperature Alarm level.
1.3.6.1.4.1.12148.9.3.23ScalarbatteryHighMinorTempAlarmLevelread-writecurrentThis is the Minor High Temperature Alarm level.
1.3.6.1.4.1.12148.9.4NodeloadDistribution
1.3.6.1.4.1.12148.9.4.1ScalarloadDistributionCurrentread-onlycurrentThe total load current
1.3.6.1.4.1.12148.9.4.2ScalarloadDistributionBreakerStatusread-onlycurrentThe state of the load fuses/breakers can be either normal(0) or alarm(1)
1.3.6.1.4.1.12148.9.4.3NodeloadDistributionLVDStatus
1.3.6.1.4.1.12148.9.4.3.1ScalarloadLVD1Enableread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.2ScalarloadLVD1Statusread-onlycurrentThe load Contactor 1 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.3ScalarloadLVD1ConnectVoltageread-writecurrentLVLD1 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.4ScalarloadLVD1DisconnectVoltageread-writecurrentLVLD1 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.5ScalarloadLVD2Enableread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.6ScalarloadLVD2Statusread-onlycurrentThe load Contactor 2 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.7ScalarloadLVD2ConnectVoltageread-writecurrentLVLD2 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.8ScalarloadLVD2DisconnectVoltageread-writecurrentLVLD2 Disconnect Voltage
1.3.6.1.4.1.12148.9.4.3.9ScalarloadLVD3Enableread-onlycurrentThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
1.3.6.1.4.1.12148.9.4.3.10ScalarloadLVD3Statusread-onlycurrentThe load Contactor 3 is connected(0), disconnected(1) or disabled(2)
1.3.6.1.4.1.12148.9.4.3.11ScalarloadLVD3ConnectVoltageread-writecurrentLVLD3 Connect Voltage
1.3.6.1.4.1.12148.9.4.3.12ScalarloadLVD3DisconnectVoltageread-writecurrentLVLD3 Disconnect Voltage
1.3.6.1.4.1.12148.9.5Noderectifier
1.3.6.1.4.1.12148.9.5.1ScalarrectifierInstalledRectifiersread-onlycurrentThe number of installed rectifiers for this DC Power System.
1.3.6.1.4.1.12148.9.5.2ScalarrectifierRectifiersActiveread-onlycurrentNot Used!
1.3.6.1.4.1.12148.9.5.3ScalarrectifierTotalCurrentread-onlycurrentThe DC system's total delivered rectifier current
1.3.6.1.4.1.12148.9.5.4ScalarrectifierUtilizationread-onlycurrentUtilization in % of available rectifier capacity
1.3.6.1.4.1.12148.9.5.5NoderectifierStatus
1.3.6.1.4.1.12148.9.5.5.1ScalarrectifierStatusNoIndexread-writecurrentAn offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first…
1.3.6.1.4.1.12148.9.5.5.2TablerectifierStatusTablenot-accessiblecurrentA table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
1.3.6.1.4.1.12148.9.5.5.2.1RowrectifierStatusEntrynot-accessiblecurrentA row of rectifier status data corresponding to the rectifierStatusNoIndex value
1.3.6.1.4.1.12148.9.5.5.2.1.1ColumnrectifierStatusIDread-onlycurrentThe rectifier ID number of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.2ColumnrectifierStatusStatusread-onlycurrentThe operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
1.3.6.1.4.1.12148.9.5.5.2.1.3ColumnrectifierStatusOutputCurrentread-onlycurrentThe output current of the rectifier
1.3.6.1.4.1.12148.9.5.5.2.1.4ColumnrectifierStatusOutputVoltageread-onlycurrentThe rectifier voltage of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.5ColumnrectifierStatusTempread-onlycurrentThe input air temperature of the rectifier.
1.3.6.1.4.1.12148.9.5.5.2.1.6ColumnrectifierStatusTyperead-onlycurrentThe rectifier article number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.7ColumnrectifierStatusSKUread-onlycurrentThe rectifier part number.
1.3.6.1.4.1.12148.9.5.5.2.1.8ColumnrectifierStatusSerialNoread-onlycurrentThe rectifier serial number string of the rectifier record.
1.3.6.1.4.1.12148.9.5.5.2.1.9ColumnrectifierStatusRevisionLevelread-onlycurrentThe rectifier HW revision number string of the rectifier record.
1.3.6.1.4.1.12148.9.6NodeacDistribution
1.3.6.1.4.1.12148.9.6.1ScalaracVoltage1read-onlycurrentThe AC Voltage of phase 1
1.3.6.1.4.1.12148.9.6.2ScalaracVoltage2read-onlycurrentThe AC Voltage of phase 2
1.3.6.1.4.1.12148.9.6.3ScalaracVoltage3read-onlycurrentThe AC Voltage of phase 3
1.3.6.1.4.1.12148.9.7NodealarmGroup
1.3.6.1.4.1.12148.9.7.1NodealarmWellknownAlarms
1.3.6.1.4.1.12148.9.7.1.1ScalaralarmMajorHighBattVoltread-onlycurrentThe Major High Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.2ScalaralarmMinorHighBattVoltread-onlycurrentThe Minor High Battery Voltage alarm
1.3.6.1.4.1.12148.9.7.1.3ScalaralarmMajorLowBattVoltread-onlycurrentThe Major Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.4ScalaralarmMinorLowBattVoltread-onlycurrentThe Minor Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.7.1.5ScalaralarmMajorBatteryHighTempread-onlycurrentThe Major High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.7.1.6ScalaralarmMinorBatteryHighTempread-onlycurrentThe Minor High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.7.1.7ScalaralarmBatteryDisconnectOpenread-onlycurrentThe Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.9.7.1.8ScalaralarmLVD1openread-onlycurrentThe load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.9ScalaralarmLVD2openread-onlycurrentThe load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.10ScalaralarmLVD3openread-onlycurrentThe load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.7.1.11ScalaralarmACmainsread-onlycurrentThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.9.7.1.12ScalaralarmBatteryBreakerOpenread-onlycurrentA battery breaker/fuse alarm.
1.3.6.1.4.1.12148.9.7.1.13ScalaralarmDistributionBreakerOpenread-onlycurrentA Load Distribution breaker/fuse alarm.
1.3.6.1.4.1.12148.9.7.1.14ScalaralarmMajorRectifierread-onlycurrentThis is a Major Rectifier alarm.
1.3.6.1.4.1.12148.9.7.1.15ScalaralarmMinorRectifierread-onlycurrentThis is a Minor Rectifier alarm.
1.3.6.1.4.1.12148.9.7.1.16ScalaralarmMajorBatterySymmetryread-onlycurrentBattery Symmetry Delta Voltage Major alarm.
1.3.6.1.4.1.12148.9.7.1.17ScalaralarmMinorBatterySymmetryread-onlycurrentBattery Symmetry Delta Voltage Minor alarm
1.3.6.1.4.1.12148.9.7.1.18ScalaralarmBatteryLifeEndedread-onlycurrentThe battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifec…
1.3.6.1.4.1.12148.9.7.1.19ScalaralarmBatteryTestmodeEnteredread-onlycurrentThe system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing…
1.3.6.1.4.1.12148.9.7.1.20ScalaralarmBatteryBoostmodeEnteredread-onlycurrentThe system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge volt…
1.3.6.1.4.1.12148.9.8GroupdcSystemTrapscurrentThis branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an as…
1.3.6.1.4.1.12148.9.8.1NotificationalarmMajorHighBattVoltTrapcurrentThe Major High Battery Voltage alarm
1.3.6.1.4.1.12148.9.8.2NotificationalarmMinorHighBattVoltTrapcurrentThe Minor High Battery Voltage alarm
1.3.6.1.4.1.12148.9.8.3NotificationalarmMajorLowBattVoltTrapcurrentThe Major Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.8.4NotificationalarmMinorLowBattVoltTrapcurrentThe Minor Low Battery Voltage Alarm
1.3.6.1.4.1.12148.9.8.5NotificationalarmMajorBatteryHighTempTrapcurrentThe Major High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.8.6NotificationalarmMinorBatteryHighTempTrapcurrentThe Minor High Battery Temperature alarm.
1.3.6.1.4.1.12148.9.8.7NotificationalarmBatteryDisconnectOpenTrapcurrentThe Battery Disconnect Contactor alarm
1.3.6.1.4.1.12148.9.8.8NotificationalarmLVD1openTrapcurrentThe load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.9NotificationalarmLVD2openTrapcurrentThe load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.10NotificationalarmLVD3openTrapcurrentThe load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
1.3.6.1.4.1.12148.9.8.11NotificationalarmACmainsTrapcurrentThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
1.3.6.1.4.1.12148.9.8.12NotificationalarmBatteryBreakerOpenTrapcurrentA battery breaker/fuse alarm.
1.3.6.1.4.1.12148.9.8.13NotificationalarmDistributionBreakerOpenTrapcurrentA Load Distribution breaker/fuse alarm.
1.3.6.1.4.1.12148.9.8.14NotificationalarmMajorRectifierTrapcurrentThis is a Major Rectifier alarm.
1.3.6.1.4.1.12148.9.8.15NotificationalarmMinorRectifierTrapcurrentThis is a Minor Rectifier alarm.
1.3.6.1.4.1.12148.9.8.16NotificationalarmMajorBatterySymmetryTrapcurrentBattery Symmetry Delta Voltage Major alarm
1.3.6.1.4.1.12148.9.8.17NotificationalarmMinorBatterySymmetryTrapcurrentBattery Symmetry Delta Voltage Minor alarm
1.3.6.1.4.1.12148.9.8.18NotificationalarmBatteryLifeEndedTrapcurrentThe battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifec…
1.3.6.1.4.1.12148.9.8.19NotificationalarmBatteryTestmodeEnteredTrapcurrentThe system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing…
1.3.6.1.4.1.12148.9.8.20NotificationalarmBatteryBoostmodeEnteredTrapcurrentThe system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge volt…
1.3.6.1.4.1.12148.9.8.21NotificationalarmController1proginputTrapcurrentProgrammable input alarm for Smartpack 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.22NotificationalarmController2proginputTrapcurrentProgrammable input alarm for Smartpack 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.23NotificationalarmController3proginputTrapcurrentProgrammable input alarm for Smartpack 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.24NotificationalarmController4proginputTrapcurrentProgrammable input alarm for Smartpack 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.25NotificationalarmController5proginputTrapcurrentProgrammable input alarm for Smartpack 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.26NotificationalarmController6proginputTrapcurrentProgrammable input alarm for Smartpack 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.27NotificationalarmController7proginputTrapcurrentProgrammable input alarm for Smartpack 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.28NotificationalarmController8proginputTrapcurrentProgrammable input alarm for Smartpack 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <…
1.3.6.1.4.1.12148.9.8.29NotificationinfoHeartBeatTrapcurrentWhen enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is ali…