MIB Viewer

GE-SINGLEUPS

532 objects
No module-level DESCRIPTION found.
Imported Objects
SNMPv2-SMICounter32 enterprises Gauge32 Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCAutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp
OIDNameAccessStatusDescription
1.3.6.1.4.1.818Nodeimv
1.3.6.1.4.1.818.1NodegeHardware
1.3.6.1.4.1.818.1.1NodegeUPS
1.3.6.1.4.1.818.1.1.1ScalargeDiscoveredUPSsMaskread-onlycurrentReading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp bran…
1.3.6.1.4.1.818.1.1.2ScalargeRequestPacketread-writecurrentPut the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to the internally RS485 bus from a …
1.3.6.1.4.1.818.1.1.3ScalargeReplyPacketread-onlycurrentContain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made at the OID ge RequestPacket, th…
1.3.6.1.4.1.818.1.1.10NodegeGenericUPS
1.3.6.1.4.1.818.1.1.10.1NodeupsIdent-gen
1.3.6.1.4.1.818.1.1.10.1.1ScalarupsIdentManufacturer-genread-onlycurrentThe name of the UPS manufacturer.(*)
1.3.6.1.4.1.818.1.1.10.1.2ScalarupsIdentModel-genread-onlycurrentThe UPS Model designation.(*)
1.3.6.1.4.1.818.1.1.10.1.3ScalarupsIdentUPSSoftwareVersion-genread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.10.1.4ScalarupsIdentAgentSoftwareVersion-genread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)
1.3.6.1.4.1.818.1.1.10.1.5ScalarupsIdentName-genread-writecurrentA string identifying the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.10.1.6ScalarupsIdentAttachedDevices-genread-writecurrentA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)
1.3.6.1.4.1.818.1.1.10.1.7ScalarupsIdentUPSSerialNumber-genread-onlycurrentThe UPS serial number
1.3.6.1.4.1.818.1.1.10.1.8ScalarupsIdentComProtVersion-genread-onlycurrentThe IMV communication protocol version
1.3.6.1.4.1.818.1.1.10.1.9ScalarupsIdentOperatingTime-genread-onlycurrentThe present value of the operating time. total 'on' time since UPS manufactured
1.3.6.1.4.1.818.1.1.10.2NodeupsBattery-gen
1.3.6.1.4.1.818.1.1.10.2.1ScalarupsBatteryStatus-genread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.818.1.1.10.2.2ScalarupsSecondsOnBattery-genread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.818.1.1.10.2.3ScalarupsEstimatedMinutesRemaining-genread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.818.1.1.10.2.4ScalarupsEstimatedChargeRemaining-genread-onlycurrentAn estimate of the battery charge remaining expressed as a percent of full charge.(*)
1.3.6.1.4.1.818.1.1.10.2.5ScalarupsBatteryVoltage-genread-onlycurrentThe magnitude of the present battery voltage.(*)
1.3.6.1.4.1.818.1.1.10.2.6ScalarupsBatteryCurrent-genread-onlycurrentThe present battery current.(*)
1.3.6.1.4.1.818.1.1.10.2.7ScalarupsBatteryTemperature-genread-onlycurrentThe ambient temperature at or near the UPS Battery casing.(*)
1.3.6.1.4.1.818.1.1.10.3NodeupsInput-gen
1.3.6.1.4.1.818.1.1.10.3.1ScalarupsInputLineBads-genread-onlycurrentA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.818.1.1.10.3.2ScalarupsInputNumLines-genread-onlycurrentThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)
1.3.6.1.4.1.818.1.1.10.3.3TableupsInputTable-gennot-accessiblecurrentA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1RowupsInputEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular input line.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.1ColumnupsInputLineIndex-gennot-accessiblecurrentThe input line identifier.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.2ColumnupsInputFrequency-genread-onlycurrentThe present input frequency.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.3ColumnupsInputVoltage-genread-onlycurrentThe magnitude of the present input voltage.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.4ColumnupsInputCurrent-genread-onlycurrentThe magnitude of the present input current.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.5ColumnupsInputTruePower-genread-onlycurrentThe magnitude of the present input true power.(*)
1.3.6.1.4.1.818.1.1.10.3.3.1.6ColumnupsInputVoltageMin-genread-onlycurrentThe lowest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.10.3.3.1.7ColumnupsInputVoltageMax-genread-onlycurrentThe highest magnitude of the input voltage since last read out.
1.3.6.1.4.1.818.1.1.10.4NodeupsOutput-gen
1.3.6.1.4.1.818.1.1.10.4.1ScalarupsOutputSource-genread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.818.1.1.10.4.2ScalarupsOutputFrequency-genread-onlycurrentThe present output frequency.(*)
1.3.6.1.4.1.818.1.1.10.4.3ScalarupsOutputNumLines-genread-onlycurrentThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)
1.3.6.1.4.1.818.1.1.10.4.4TableupsOutputTable-gennot-accessiblecurrentA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1RowupsOutputEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular output line.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.1ColumnupsOutputLineIndex-gennot-accessiblecurrentThe output line identifier.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.2ColumnupsOutputVoltage-genread-onlycurrentThe present output voltage.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.3ColumnupsOutputCurrent-genread-onlycurrentThe present output current.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.4ColumnupsOutputPower-genread-onlycurrentThe present output true power.(*)
1.3.6.1.4.1.818.1.1.10.4.4.1.5ColumnupsOutputPercentLoad-genread-onlycurrentThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.818.1.1.10.5NodeupsBypass-gen
1.3.6.1.4.1.818.1.1.10.5.1ScalarupsBypassFrequency-genread-onlycurrentThe present bypass frequency.(*)
1.3.6.1.4.1.818.1.1.10.5.2ScalarupsBypassNumLines-genread-onlycurrentThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)
1.3.6.1.4.1.818.1.1.10.5.3TableupsBypassTable-gennot-accessiblecurrentA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1RowupsBypassEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular bypass input.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.1ColumnupsBypassLineIndex-gennot-accessiblecurrentThe bypass line identifier.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.2ColumnupsBypassVoltage-genread-onlycurrentThe present bypass voltage.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.3ColumnupsBypassCurrent-genread-onlycurrentThe present bypass current.(*)
1.3.6.1.4.1.818.1.1.10.5.3.1.4ColumnupsBypassPower-genread-onlycurrentThe present true power conveyed by the bypass.(*)
1.3.6.1.4.1.818.1.1.10.6NodeupsAlarm-gen
1.3.6.1.4.1.818.1.1.10.6.1ScalarupsAlarmsPresent-genread-onlycurrentThe present number of active alarm conditions.(*)
1.3.6.1.4.1.818.1.1.10.6.2TableupsAlarmTable-gennot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.818.1.1.10.6.2.1RowupsAlarmEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular alarm.(*)
1.3.6.1.4.1.818.1.1.10.6.2.1.1ColumnupsAlarmId-gennot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.(*)
1.3.6.1.4.1.818.1.1.10.6.2.1.2ColumnupsAlarmDescr-genread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.818.1.1.10.6.2.1.3ColumnupsAlarmTime-genread-onlycurrentThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.818.1.1.10.6.3NodeupsWellKnownAlarms-gen
1.3.6.1.4.1.818.1.1.10.6.3.1IdentityupsAlarmBatteryBad-gencurrentOne or more batteries have been determined to require replacement.(*)
1.3.6.1.4.1.818.1.1.10.6.3.2IdentityupsAlarmOnBattery-gencurrentThe UPS is drawing power from the batteries.(*)
1.3.6.1.4.1.818.1.1.10.6.3.3IdentityupsAlarmLowBattery-gencurrentThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
1.3.6.1.4.1.818.1.1.10.6.3.4IdentityupsAlarmDepletedBattery-gencurrentThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
1.3.6.1.4.1.818.1.1.10.6.3.5IdentityupsAlarmTempBad-gencurrentA temperature is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.6IdentityupsAlarmInputBad-gencurrentAn input condition is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.7IdentityupsAlarmOutputBad-gencurrentAn output condition (other than OutputOverload) is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.8IdentityupsAlarmOutputOverload-gencurrentThe output load exceeds the UPS output capacity.(*)
1.3.6.1.4.1.818.1.1.10.6.3.9IdentityupsAlarmOnBypass-gencurrentThe Bypass is presently engaged on the UPS.(*)
1.3.6.1.4.1.818.1.1.10.6.3.10IdentityupsAlarmBypassBad-gencurrentThe Bypass is out of tolerance.(*)
1.3.6.1.4.1.818.1.1.10.6.3.11IdentityupsAlarmOutputOffAsRequested-gencurrentThe UPS has shutdown as requested, i.e., the output is off.(*)
1.3.6.1.4.1.818.1.1.10.6.3.12IdentityupsAlarmUpsOffAsRequested-gencurrentThe entire UPS has shutdown as commanded.(*)
1.3.6.1.4.1.818.1.1.10.6.3.13IdentityupsAlarmChargerFailed-gencurrentAn uncorrected problem has been detected within the UPS charger subsystem.(*)
1.3.6.1.4.1.818.1.1.10.6.3.14IdentityupsAlarmUpsOutputOff-gencurrentThe output of the UPS is in the off state.(*)
1.3.6.1.4.1.818.1.1.10.6.3.15IdentityupsAlarmUpsSystemOff-gencurrentThe UPS system is in the off state.(*)
1.3.6.1.4.1.818.1.1.10.6.3.16IdentityupsAlarmFanFailure-gencurrentThe failure of one or more fans in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.10.6.3.17IdentityupsAlarmFuseFailure-gencurrentThe failure of one or more fuses has been detected.(*)
1.3.6.1.4.1.818.1.1.10.6.3.18IdentityupsAlarmGeneralFault-gencurrentA general fault in the UPS has been detected.(*)
1.3.6.1.4.1.818.1.1.10.6.3.19IdentityupsAlarmDiagnosticTestFailed-gencurrentThe result of the last diagnostic test indicates a failure.(*)
1.3.6.1.4.1.818.1.1.10.6.3.20IdentityupsAlarmCommunicationsLost-gencurrentA problem has been encountered in the communications between the agent and the UPS.(*)
1.3.6.1.4.1.818.1.1.10.6.3.21IdentityupsAlarmAwaitingPower-gencurrentThe UPS output is off and the UPS is awaiting the return of input power.(*)
1.3.6.1.4.1.818.1.1.10.6.3.22IdentityupsAlarmShutdownPending-gencurrentA upsShutdownAfterDelay countdown is underway.(*)
1.3.6.1.4.1.818.1.1.10.6.3.23IdentityupsAlarmShutdownImminent-gencurrentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
1.3.6.1.4.1.818.1.1.10.6.3.24IdentityupsAlarmTestInProgress-gencurrentA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.818.1.1.10.6.3.25IdentityupsAlarmReceptacleOff-gencurrentThe receptacle are switch off
1.3.6.1.4.1.818.1.1.10.6.4ScalarupsAlarmMaskA-genread-onlycurrentSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' com…
1.3.6.1.4.1.818.1.1.10.7NodeupsTest-gen
1.3.6.1.4.1.818.1.1.10.7.1ScalarupsTestId-genread-writecurrentThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu…
1.3.6.1.4.1.818.1.1.10.7.2ScalarupsTestSpinLock-genread-writecurrentA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.818.1.1.10.7.3ScalarupsTestResultsSummary-genread-onlycurrentThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.818.1.1.10.7.4ScalarupsTestResultsDetail-genread-onlycurrentAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)
1.3.6.1.4.1.818.1.1.10.7.5ScalarupsTestStartTime-genread-onlycurrentThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.818.1.1.10.7.6ScalarupsTestElapsedTime-genread-onlycurrentThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.818.1.1.10.7.7NodeupsWellKnownTests-gen
1.3.6.1.4.1.818.1.1.10.7.7.1IdentityupsTestNoTestsInitiated-gencurrentNo tests have been initiated and no test is in progress.(*)
1.3.6.1.4.1.818.1.1.10.7.7.2IdentityupsTestAbortTestInProgress-gencurrentThe test in progress is to be aborted / the test in progress was aborted.(*)
1.3.6.1.4.1.818.1.1.10.7.7.3IdentityupsTestGeneralSystemsTest-gencurrentThe manufacturer's standard test of UPS device systems.(*)
1.3.6.1.4.1.818.1.1.10.7.7.4IdentityupsTestQuickBatteryTest-gencurrentA test that is sufficient to determine if the battery needs replacement.(*)
1.3.6.1.4.1.818.1.1.10.7.7.5IdentityupsTestDeepBatteryCalibration-gencurrentThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.818.1.1.10.8NodeupsControl-gen
1.3.6.1.4.1.818.1.1.10.8.1ScalarupsShutdownType-genread-writecurrentThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.818.1.1.10.8.2ScalarupsShutdownAfterDelay-genread-writecurrentSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.818.1.1.10.8.3ScalarupsStartupAfterDelay-genread-writecurrentSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.818.1.1.10.8.4ScalarupsRebootWithDuration-genread-writecurrentSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.818.1.1.10.8.5ScalarupsAutoRestart-genread-writecurrentSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.818.1.1.10.8.6ScalarupsReceptaclesNum-genread-onlycurrentThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.
1.3.6.1.4.1.818.1.1.10.8.7TableupsReceptacleTable-gennot-accessiblecurrentA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
1.3.6.1.4.1.818.1.1.10.8.7.1RowupsReceptacleEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular receptacle.
1.3.6.1.4.1.818.1.1.10.8.7.1.1ColumnupsReceptacleLineIndex-gennot-accessiblecurrentThe receptacle line identifier.
1.3.6.1.4.1.818.1.1.10.8.7.1.2ColumnupsReceptacleOnOff-genread-writecurrentThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptac…
1.3.6.1.4.1.818.1.1.10.8.8ScalarupsUPSMode-genread-writecurrentThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transfor…
1.3.6.1.4.1.818.1.1.10.8.9ScalarupsRectifierOnOff-genread-writecurrentThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier …
1.3.6.1.4.1.818.1.1.10.8.10ScalarupsBatteryChargeMethod-genread-writecurrentThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this objec…
1.3.6.1.4.1.818.1.1.10.8.11ScalarupsInverterOnOff-genread-writecurrentThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off…
1.3.6.1.4.1.818.1.1.10.8.12ScalarupsBypassOnOff-genread-writecurrentThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If…
1.3.6.1.4.1.818.1.1.10.8.13ScalarupsLoadSource-genread-writecurrentThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will …
1.3.6.1.4.1.818.1.1.10.9NodeupsConfig-gen
1.3.6.1.4.1.818.1.1.10.9.1ScalarupsConfigInputVoltage-genread-writecurrentThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.818.1.1.10.9.2ScalarupsConfigInputFreq-genread-writecurrentThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.818.1.1.10.9.3ScalarupsConfigOutputVoltage-genread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.818.1.1.10.9.4ScalarupsConfigOutputFreq-genread-writecurrentThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.818.1.1.10.9.5ScalarupsConfigOutputVA-genread-onlycurrentThe magnitude of the nominal Volt-Amp rating.(*)
1.3.6.1.4.1.818.1.1.10.9.6ScalarupsConfigOutputPower-genread-onlycurrentThe magnitude of the nominal true power rating.(*)
1.3.6.1.4.1.818.1.1.10.9.7ScalarupsConfigLowBattTime-genread-writecurrentThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.818.1.1.10.9.8ScalarupsConfigAudibleStatus-genread-writecurrentThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.818.1.1.10.9.9ScalarupsConfigLowVoltageTransferPoint-genread-writecurrentThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.10.9.10ScalarupsConfigHighVoltageTransferPoint-genread-writecurrentThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)
1.3.6.1.4.1.818.1.1.10.9.11ScalarupsConfigBatteryCapacity-genread-writecurrentThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.
1.3.6.1.4.1.818.1.1.10.9.12ScalarupsConfigBatteryChargeCurrent-genread-writecurrentThe maximum battery charge current, including external chargers.
1.3.6.1.4.1.818.1.1.10.9.13ScalarupsConfigNoLoadShutdown-genread-writecurrentDis- or enable 'no load' shutdown from the contact interface.
1.3.6.1.4.1.818.1.1.10.9.14ScalarupsConfigStartDelay-genread-writecurrentMinimum required autonomy time before the UPS may perform an autorestart.
1.3.6.1.4.1.818.1.1.10.10NodeupsGetSet-gen
1.3.6.1.4.1.818.1.1.10.10.1ScalarupsEventGetNext-genread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.10.10.2ScalarupsEventGetPrevious-genread-writecurrentThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The val…
1.3.6.1.4.1.818.1.1.10.10.3ScalarupsEventSetStartingTimeStamp-genread-writecurrentThe timestamp which is used as starting point for downloading events from the UPS event buffer
1.3.6.1.4.1.818.1.1.10.10.4ScalarupsEventRetreiveCurrentTimeStamp-genread-onlycurrentThe current timestamp is retreived from the UPS
1.3.6.1.4.1.818.1.1.10.10.5ScalarupsEventTableSize-genread-onlycurrentThe number of entries in the event table. This object indicates the number of rows in the event table.
1.3.6.1.4.1.818.1.1.10.10.6TableupsEventTable-gennot-accessiblecurrentA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the…
1.3.6.1.4.1.818.1.1.10.10.6.1RowupsEventEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular event.
1.3.6.1.4.1.818.1.1.10.10.6.1.1ColumnupsEventLineIndex-gennot-accessiblecurrentThe event line identifier.
1.3.6.1.4.1.818.1.1.10.10.6.1.2ColumnupsEventCode-genread-onlycurrentThe event code in numerical format.
1.3.6.1.4.1.818.1.1.10.10.6.1.3ColumnupsEventStatus-genread-onlycurrentThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status …
1.3.6.1.4.1.818.1.1.10.10.6.1.4ColumnupsEventTime-genread-onlycurrentThe timestamp of the moment the event was generated.
1.3.6.1.4.1.818.1.1.10.10.7ScalarupsParametersRead-genread-writecurrentThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value up…
1.3.6.1.4.1.818.1.1.10.10.8ScalarupsParametersWrite-genread-writecurrentThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be u…
1.3.6.1.4.1.818.1.1.10.10.9ScalarupsParametersStartAddress-genread-writecurrentThe address which is used as starting point for downloading parameters from the UPS
1.3.6.1.4.1.818.1.1.10.10.10ScalarupsParameterTableSize-genread-onlycurrentThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.
1.3.6.1.4.1.818.1.1.10.10.11TableupsParameterTable-gennot-accessiblecurrentA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of t…
1.3.6.1.4.1.818.1.1.10.10.11.1RowupsParameterEntry-gennot-accessiblecurrentAn entry containing information applicable to a particular parameter.
1.3.6.1.4.1.818.1.1.10.10.11.1.1ColumnupsParameterLineIndex-gennot-accessiblecurrentThe parameter line identifier.
1.3.6.1.4.1.818.1.1.10.10.11.1.2ColumnupsParameterValue-genread-writecurrentThe parameter value in numerical format.
1.3.6.1.4.1.818.1.1.10.10.12ScalarupsStatus-genread-onlycurrentThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other comman…
1.3.6.1.4.1.818.1.1.10.10.13ScalarupsMainsStatisticsMBfail-genread-onlycurrentCount of main bypass failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.10.10.14ScalarupsMainsStatisticsMRfail-genread-onlycurrentCount of mains rectifier failures (>200 ms), since UPS installation.
1.3.6.1.4.1.818.1.1.10.10.15ScalarupsMainsStatisticsB2-genread-onlycurrentCount of transients on the mains bypass (0..2 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.16ScalarupsMainsStatisticsB5-genread-onlycurrentCount of transients on the mains bypass (2..5 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.17ScalarupsMainsStatisticsB10-genread-onlycurrentCount of transients on the mains bypass (5..10 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.18ScalarupsMainsStatisticsB200-genread-onlycurrentCount of transients on the mains bypass (10..200 ms), during the last 7 days.
1.3.6.1.4.1.818.1.1.10.10.19ScalarupsMainsStatisticsBypRel-genread-onlycurrentBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.
1.3.6.1.4.1.818.1.1.10.10.20ScalarupsTime-genread-writecurrentThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp for…
1.3.6.1.4.1.818.1.1.10.10.21ScalarupsRequestPermission-genwrite-onlycurrentAn encrypted code is send to enable use of restricted write objects during a limited period of time.
1.3.6.1.4.1.818.1.1.10.10.22ScalarupsEventGetCode-genwrite-onlycurrentThe code which is used as starting point to downloading the events from the UPS event buffer.
1.3.6.1.4.1.818.1.1.10.10.23ScalarupsEventSpinLock-genread-writecurrentA spin lock on the event subsystem.
1.3.6.1.4.1.818.1.1.10.10.24ScalarupsParameterSpinLock-genread-writecurrentA spin lock on the parameters subsystem.
1.3.6.1.4.1.818.1.1.10.11NodegeUPSTraps-gen
1.3.6.1.4.1.818.1.1.10.11.33NodeupsAlarmBatteryBadRestored-genA Battery bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.34NodeupsAlarmOnBatteryRestored-genThe UPS is drawing power from mains again.
1.3.6.1.4.1.818.1.1.10.11.35NodeupsAlarmLowBatteryRestored-genA Low Battery condition is restored.
1.3.6.1.4.1.818.1.1.10.11.36NodeupsAlarmDepletedBatteryRestored-genA Depleted Battery condition is restored.
1.3.6.1.4.1.818.1.1.10.11.37NodeupsAlarmTempBadRestored-genA bad temperature condition is restored.
1.3.6.1.4.1.818.1.1.10.11.38NodeupsAlarmInputBadRestored-genAn input bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.39NodeupsAlarmOutputBadRestored-genAn output bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.40NodeupsAlarmOutputOverloadRestored-genAn output overload condition is restored.
1.3.6.1.4.1.818.1.1.10.11.41NodeupsAlarmOnBypassRestored-genAn On Bypass condition is restored.
1.3.6.1.4.1.818.1.1.10.11.42NodeupsAlarmBypassBadRestored-genA Bypass bad condition is restored.
1.3.6.1.4.1.818.1.1.10.11.43NodeupsAlarmOutputOffAsRequestedRestored-genA request shutdown has been restored.
1.3.6.1.4.1.818.1.1.10.11.45NodeupsAlarmChargerFailedRestored-genA Charger Failer condition is restored.
1.3.6.1.4.1.818.1.1.10.11.46NodeupsAlarmUpsOutputOn-genThe output of the UPS switched in the on state.
1.3.6.1.4.1.818.1.1.10.11.47NodeupsAlarmUpsSystemOn-genThe UPS system is switched in the on state.
1.3.6.1.4.1.818.1.1.10.11.48NodeupsAlarmFanFailureRestored-genA Fan failure condition is restored.
1.3.6.1.4.1.818.1.1.10.11.49NodeupsAlarmFuseFailureRestored-genA Fuse failure condition is restored.
1.3.6.1.4.1.818.1.1.10.11.50NodeupsAlarmGeneralFaultRestored-genA general fault is restored.
1.3.6.1.4.1.818.1.1.10.11.51NodeupsAlarmDiagnosticTestFailedRestored-genA last diagnostic test indicates a failure is restored.
1.3.6.1.4.1.818.1.1.10.11.52NodeupsAlarmCommunicationsLostRestored-genA problem in the communication between the agent and the UPS is restored.
1.3.6.1.4.1.818.1.1.10.11.53NodeupsAlarmAwaitingPowerRestored-genA awaiting power condition is restored (*).
1.3.6.1.4.1.818.1.1.10.11.54NodeupsAlarmShutdownPendingRestored-genA upsShutdownAfterDelay countdown is restored.
1.3.6.1.4.1.818.1.1.10.11.55NodeupsAlarmShutdownImminentRestored-genA shutdown imminent condition is restored.
1.3.6.1.4.1.818.1.1.10.11.56NodeupsAlarmTestInProgressRestored-genThe test is in progress is terminated.
1.3.6.1.4.1.818.1.1.10.11.57NodeupsAlarmReceptacleOnA receptacle has been switched on.
1.3.6.1.4.1.818.1.1.10.11.129NodeupsAlarmValueLow-genA measurement value reached a value below its low-level threshold.
1.3.6.1.4.1.818.1.1.10.11.130NodeupsAlarmValueHigh-genA measurement value reached a value higher than its high-level threshold.
1.3.6.1.4.1.818.1.1.10.11.133NodeupsAlarmValueLowRestored-genA ValueLow alarm condition is restored.
1.3.6.1.4.1.818.1.1.10.11.134NodeupsAlarmValueHighRestored-genA ValueHigh alarm condition is restored.
1.3.6.1.4.1.818.1.2NodegeEnvironmental
1.3.6.1.4.1.818.1.2.1NodeioInterface-First
1.3.6.1.4.1.818.1.2.1.1NodeioInterfaceInputLine-First
1.3.6.1.4.1.818.1.2.1.1.1Identityaread-onlycurrentA receptacle has been switched off.
1.3.6.1.4.1.818.1.2.1.1.2TableioInterfaceInputTable-Firstnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.1.1.2.1RowioInterfaceInputEntry-Firstnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.1.1.2.1.1ColumnioInterfaceInputLineIndex-Firstnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.1.1.2.1.2ColumnioInterfaceInputDescription-Firstread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.1.1.2.1.3ColumnioInterfaceInputStatus-Firstread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.1.1.2.1.4ColumnioInterfaceEdgeMode-Firstread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.1.1.2.1.5ColumnioInterfaceAlarmMask-Firstread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.1.1.3ScalarioInterfaceAlarmDelay-Firstread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.1.2NodeioInterfaceOutputLine-First
1.3.6.1.4.1.818.1.2.1.2.1ScalarioInterfaceNumOutput-Firstread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.1.2.2TableioInterfaceOutputTable-Firstnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.1.2.2.1RowioInterfaceOutputEntry-Firstnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.1.2.2.1.1ColumnioInterfaceOutputLineIndex-Firstnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.1.2.2.1.2ColumnioInterfaceOutputDescription-Firstread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.1.2.2.1.3ColumnioInterfaceOutputStatus-Firstread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.1.3NodeioInterfaceAnalogueLine-First
1.3.6.1.4.1.818.1.2.1.3.1ScalarioInterfaceNumAnalogue-Firstread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.1.3.2TableioInterfaceAnalogueTable-Firstnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.1.3.2.1RowioInterfaceAnalogueEntry-Firstnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.1.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Firstnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.1.3.2.1.2ColumnioInterfaceAnalogueDescription-Firstread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.1.3.2.1.3ColumnioInterfaceAnalogueStatus-Firstread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.1.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Firstread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.1.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Firstread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.1.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Firstread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.1.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Firstread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.1.4NodeioInterfaceTraps-First
1.3.6.1.4.1.818.1.2.1.4.1NodeioAlarmGenericChange-FirstAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.2NodeioInterface-Second
1.3.6.1.4.1.818.1.2.2.1NodeioInterfaceInputLine-Second
1.3.6.1.4.1.818.1.2.2.1.1ScalarioInterfaceNumInputs-Secondread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.2.1.2TableioInterfaceInputTable-Secondnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.2.1.2.1RowioInterfaceInputEntry-Secondnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.2.1.2.1.1ColumnioInterfaceInputLineIndex-Secondnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.2.1.2.1.2ColumnioInterfaceInputDescription-Secondread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.2.1.2.1.3ColumnioInterfaceInputStatus-Secondread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.2.1.2.1.4ColumnioInterfaceEdgeMode-Secondread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.2.1.2.1.5ColumnioInterfaceAlarmMask-Secondread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.2.1.2.1.6ColumnioInterfaceAlarmDelay-Secondread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.2.2NodeioInterfaceOutputLine-Second
1.3.6.1.4.1.818.1.2.2.2.1ScalarioInterfaceNumOutput-Secondread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.2.2.2TableioInterfaceOutputTable-Secondnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.2.2.2.1RowioInterfaceOutputEntry-Secondnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.2.2.2.1.1ColumnioInterfaceOutputLineIndex-Secondnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.2.2.2.1.2ColumnioInterfaceOutputDescription-Secondread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.2.2.2.1.3ColumnioInterfaceOutputStatus-Secondread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.2.3NodeioInterfaceAnalogueLine-Second
1.3.6.1.4.1.818.1.2.2.3.1ScalarioInterfaceNumAnalogue-Secondread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.2.3.2TableioInterfaceAnalogueTable-Secondnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.2.3.2.1RowioInterfaceAnalogueEntry-Secondnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.2.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Secondnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.2.3.2.1.2ColumnioInterfaceAnalogueDescription-Secondread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.2.3.2.1.3ColumnioInterfaceAnalogueStatus-Secondread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.2.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Secondread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.2.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Secondread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.2.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Secondread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.2.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Secondread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.2.4NodeioInterfaceTraps-Second
1.3.6.1.4.1.818.1.2.2.4.1NodeioAlarmGenericChange-SecondAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.3NodeioInterface-Third
1.3.6.1.4.1.818.1.2.3.1NodeioInterfaceInputLine-Third
1.3.6.1.4.1.818.1.2.3.1.1ScalarioInterfaceNumInputs-Thirdread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.3.1.2TableioInterfaceInputTable-Thirdnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.3.1.2.1RowioInterfaceInputEntry-Thirdnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.3.1.2.1.1ColumnioInterfaceInputLineIndex-Thirdnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.3.1.2.1.2ColumnioInterfaceInputDescription-Thirdread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.3.1.2.1.3ColumnioInterfaceInputStatus-Thirdread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.3.1.2.1.4ColumnioInterfaceEdgeMode-Thirdread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.3.1.2.1.5ColumnioInterfaceAlarmMask-Thirdread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.3.1.2.1.6ColumnioInterfaceAlarmDelay-Thirdread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.3.2NodeioInterfaceOutputLine-Third
1.3.6.1.4.1.818.1.2.3.2.1ScalarioInterfaceNumOutput-Thirdread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.3.2.2TableioInterfaceOutputTable-Thirdnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.3.2.2.1RowioInterfaceOutputEntry-Thirdnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.3.2.2.1.1ColumnioInterfaceOutputLineIndex-Thirdnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.3.2.2.1.2ColumnioInterfaceOutputDescription-Thirdread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.3.2.2.1.3ColumnioInterfaceOutputStatus-Thirdread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.3.3NodeioInterfaceAnalogueLine-Third
1.3.6.1.4.1.818.1.2.3.3.1ScalarioInterfaceNumAnalogue-Thirdread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.3.3.2TableioInterfaceAnalogueTable-Thirdnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.3.3.2.1RowioInterfaceAnalogueEntry-Thirdnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.3.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Thirdnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.3.3.2.1.2ColumnioInterfaceAnalogueDescription-Thirdread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.3.3.2.1.3ColumnioInterfaceAnalogueStatus-Thirdread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.3.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Thirdread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.3.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Thirdread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.3.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Thirdread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.3.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Thirdread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.3.4NodeioInterfaceTraps-Third
1.3.6.1.4.1.818.1.2.3.4.1NodeioAlarmGenericChange-ThirdAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.4NodeioInterface-Fourth
1.3.6.1.4.1.818.1.2.4.1NodeioInterfaceInputLine-Fourth
1.3.6.1.4.1.818.1.2.4.1.1ScalarioInterfaceNumInputs-Fourthread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.4.1.2TableioInterfaceInputTable-Fourthnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.4.1.2.1RowioInterfaceInputEntry-Fourthnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.4.1.2.1.1ColumnioInterfaceInputLineIndex-Fourthnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.4.1.2.1.2ColumnioInterfaceInputDescription-Fourthread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.4.1.2.1.3ColumnioInterfaceInputStatus-Fourthread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.4.1.2.1.4ColumnioInterfaceEdgeMode-Fourthread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.4.1.2.1.5ColumnioInterfaceAlarmMask-Fourthread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.4.1.2.1.6ColumnioInterfaceAlarmDelay-Fourthread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.4.2NodeioInterfaceOutputLine-Fourth
1.3.6.1.4.1.818.1.2.4.2.1ScalarioInterfaceNumOutput-Fourthread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.4.2.2TableioInterfaceOutputTable-Fourthnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.4.2.2.1RowioInterfaceOutputEntry-Fourthnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.4.2.2.1.1ColumnioInterfaceOutputLineIndex-Fourthnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.4.2.2.1.2ColumnioInterfaceOutputDescription-Fourthread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.4.2.2.1.3ColumnioInterfaceOutputStatus-Fourthread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.4.3NodeioInterfaceAnalogueLine-Fourth
1.3.6.1.4.1.818.1.2.4.3.1ScalarioInterfaceNumAnalogue-Fourthread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.4.3.2TableioInterfaceAnalogueTable-Fourthnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.4.3.2.1RowioInterfaceAnalogueEntry-Fourthnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.4.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Fourthnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.4.3.2.1.2ColumnioInterfaceAnalogueDescription-Fourthread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.4.3.2.1.3ColumnioInterfaceAnalogueStatus-Fourthread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.4.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Fourthread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.4.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Fourthread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.4.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Fourthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.4.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Fourthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.4.4NodeioInterfaceTraps-Fourth
1.3.6.1.4.1.818.1.2.4.4.1NodeioAlarmGenericChange-FourthAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.5NodeioInterface-Fifth
1.3.6.1.4.1.818.1.2.5.1NodeioInterfaceInputLine-Fifth
1.3.6.1.4.1.818.1.2.5.1.1ScalarioInterfaceNumInputs-Fifthread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.5.1.2TableioInterfaceInputTable-Fifthnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.5.1.2.1RowioInterfaceInputEntry-Fifthnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.5.1.2.1.1ColumnioInterfaceInputLineIndex-Fifthnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.5.1.2.1.2ColumnioInterfaceInputDescription-Fifthread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.5.1.2.1.3ColumnioInterfaceInputStatus-Fifthread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.5.1.2.1.4ColumnioInterfaceEdgeMode-Fifthread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.5.1.2.1.5ColumnioInterfaceAlarmMask-Fifthread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.5.1.2.1.6ColumnioInterfaceAlarmDelay-Fifthread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.5.2NodeioInterfaceOutputLine-Fifth
1.3.6.1.4.1.818.1.2.5.2.1ScalarioInterfaceNumOutput-Fifthread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.5.2.2TableioInterfaceOutputTable-Fifthnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.5.2.2.1RowioInterfaceOutputEntry-Fifthnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.5.2.2.1.1ColumnioInterfaceOutputLineIndex-Fifthnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.5.2.2.1.2ColumnioInterfaceOutputDescription-Fifthread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.5.2.2.1.3ColumnioInterfaceOutputStatus-Fifthread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.5.3NodeioInterfaceAnalogueLine-Fifth
1.3.6.1.4.1.818.1.2.5.3.1ScalarioInterfaceNumAnalogue-Fifthread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.5.3.2TableioInterfaceAnalogueTable-Fifthnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.5.3.2.1RowioInterfaceAnalogueEntry-Fifthnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.5.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Fifthnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.5.3.2.1.2ColumnioInterfaceAnalogueDescription-Fifthread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.5.3.2.1.3ColumnioInterfaceAnalogueStatus-Fifthread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.5.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Fifthread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.5.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Fifthread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.5.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Fifthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.5.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Fifthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.5.4NodeioInterfaceTraps-Fifth
1.3.6.1.4.1.818.1.2.5.4.1NodeioAlarmGenericChange-FifthAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.6NodeioInterface-Sixth
1.3.6.1.4.1.818.1.2.6.1NodeioInterfaceInputLine-Sixth
1.3.6.1.4.1.818.1.2.6.1.1ScalarioInterfaceNumInputs-Sixthread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.6.1.2TableioInterfaceInputTable-Sixthnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.6.1.2.1RowioInterfaceInputEntry-Sixthnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.6.1.2.1.1ColumnioInterfaceInputLineIndex-Sixthnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.6.1.2.1.2ColumnioInterfaceInputDescription-Sixthread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.6.1.2.1.3ColumnioInterfaceInputStatus-Sixthread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.6.1.2.1.4ColumnioInterfaceEdgeMode-Sixthread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.6.1.2.1.5ColumnioInterfaceAlarmMask-Sixthread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.6.1.2.1.6ColumnioInterfaceAlarmDelay-Sixthread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.6.2NodeioInterfaceOutputLine-Sixth
1.3.6.1.4.1.818.1.2.6.2.1ScalarioInterfaceNumOutput-Sixthread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.6.2.2TableioInterfaceOutputTable-Sixthnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.6.2.2.1RowioInterfaceOutputEntry-Sixthnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.6.2.2.1.1ColumnioInterfaceOutputLineIndex-Sixthnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.6.2.2.1.2ColumnioInterfaceOutputDescription-Sixthread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.6.2.2.1.3ColumnioInterfaceOutputStatus-Sixthread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.6.3NodeioInterfaceAnalogueLine-Sixth
1.3.6.1.4.1.818.1.2.6.3.1ScalarioInterfaceNumAnalogue-Sixthread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.6.3.2TableioInterfaceAnalogueTable-Sixthnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.6.3.2.1RowioInterfaceAnalogueEntry-Sixthnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.6.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Sixthnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.6.3.2.1.2ColumnioInterfaceAnalogueDescription-Sixthread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.6.3.2.1.3ColumnioInterfaceAnalogueStatus-Sixthread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.6.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Sixthread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.6.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Sixthread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.6.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Sixthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.6.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Sixthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.6.4NodeioInterfaceTraps-Sixth
1.3.6.1.4.1.818.1.2.6.4.1NodeioAlarmGenericChange-SixthAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.7NodeioInterface-Seventh
1.3.6.1.4.1.818.1.2.7.1NodeioInterfaceInputLine-Seventh
1.3.6.1.4.1.818.1.2.7.1.1ScalarioInterfaceNumInputs-Seventhread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.7.1.2TableioInterfaceInputTable-Seventhnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.7.1.2.1RowioInterfaceInputEntry-Seventhnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.7.1.2.1.1ColumnioInterfaceInputLineIndex-Seventhnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.7.1.2.1.2ColumnioInterfaceInputDescription-Seventhread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.7.1.2.1.3ColumnioInterfaceInputStatus-Seventhread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.7.1.2.1.4ColumnioInterfaceEdgeMode-Seventhread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.7.1.2.1.5ColumnioInterfaceAlarmMask-Seventhread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.7.1.2.1.6ColumnioInterfaceAlarmDelay-Seventhread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.7.2NodeioInterfaceOutputLine-Seventh
1.3.6.1.4.1.818.1.2.7.2.1ScalarioInterfaceNumOutput-Seventhread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.7.2.2TableioInterfaceOutputTable-Seventhnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.7.2.2.1RowioInterfaceOutputEntry-Seventhnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.7.2.2.1.1ColumnioInterfaceOutputLineIndex-Seventhnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.7.2.2.1.2ColumnioInterfaceOutputDescription-Seventhread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.7.2.2.1.3ColumnioInterfaceOutputStatus-Seventhread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.7.3NodeioInterfaceAnalogueLine-Seventh
1.3.6.1.4.1.818.1.2.7.3.1ScalarioInterfaceNumAnalogue-Seventhread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.7.3.2TableioInterfaceAnalogueTable-Seventhnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.7.3.2.1RowioInterfaceAnalogueEntry-Seventhnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.7.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Seventhnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.7.3.2.1.2ColumnioInterfaceAnalogueDescription-Seventhread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.7.3.2.1.3ColumnioInterfaceAnalogueStatus-Seventhread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.7.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Seventhread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.7.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Seventhread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.7.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Seventhread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.7.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Seventhread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.7.4NodeioInterfaceTraps-Seventh
1.3.6.1.4.1.818.1.2.7.4.1NodeioAlarmGenericChange-SeventhAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.2.8NodeioInterface-Eighth
1.3.6.1.4.1.818.1.2.8.1NodeioInterfaceInputLine-Eighth
1.3.6.1.4.1.818.1.2.8.1.1ScalarioInterfaceNumInputs-Eighthread-onlycurrentThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.818.1.2.8.1.2TableioInterfaceInputTable-Eighthnot-accessiblecurrentA list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs.
1.3.6.1.4.1.818.1.2.8.1.2.1RowioInterfaceInputEntry-Eighthnot-accessiblecurrentAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.818.1.2.8.1.2.1.1ColumnioInterfaceInputLineIndex-Eighthnot-accessiblecurrentThe input line identifier.
1.3.6.1.4.1.818.1.2.8.1.2.1.2ColumnioInterfaceInputDescription-Eighthread-writecurrentA description of the alarm monitored by this input line.
1.3.6.1.4.1.818.1.2.8.1.2.1.3ColumnioInterfaceInputStatus-Eighthread-onlycurrentThe status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.8.1.2.1.4ColumnioInterfaceEdgeMode-Eighthread-writecurrentEdge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the st…
1.3.6.1.4.1.818.1.2.8.1.2.1.5ColumnioInterfaceAlarmMask-Eighthread-writecurrentAlarm functionality for the input line can be set active or inactive.
1.3.6.1.4.1.818.1.2.8.1.2.1.6ColumnioInterfaceAlarmDelay-Eighthread-writecurrentTime delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line.
1.3.6.1.4.1.818.1.2.8.2NodeioInterfaceOutputLine-Eighth
1.3.6.1.4.1.818.1.2.8.2.1ScalarioInterfaceNumOutput-Eighthread-onlycurrentThe number of output lines utilized by this device. This entry indicates the number of rows in the output line table.
1.3.6.1.4.1.818.1.2.8.2.2TableioInterfaceOutputTable-Eighthnot-accessiblecurrentA list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs.
1.3.6.1.4.1.818.1.2.8.2.2.1RowioInterfaceOutputEntry-Eighthnot-accessiblecurrentAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.818.1.2.8.2.2.1.1ColumnioInterfaceOutputLineIndex-Eighthnot-accessiblecurrentThe output line identifier.
1.3.6.1.4.1.818.1.2.8.2.2.1.2ColumnioInterfaceOutputDescription-Eighthread-writecurrentA description of the alarm monitored by this output line.
1.3.6.1.4.1.818.1.2.8.2.2.1.3ColumnioInterfaceOutputStatus-Eighthread-writecurrentThe status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active'
1.3.6.1.4.1.818.1.2.8.3NodeioInterfaceAnalogueLine-Eighth
1.3.6.1.4.1.818.1.2.8.3.1ScalarioInterfaceNumAnalogue-Eighthread-onlycurrentThe number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table.
1.3.6.1.4.1.818.1.2.8.3.2TableioInterfaceAnalogueTable-Eighthnot-accessiblecurrentA list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue.
1.3.6.1.4.1.818.1.2.8.3.2.1RowioInterfaceAnalogueEntry-Eighthnot-accessiblecurrentAn entry containing information applicable to a particular analogue line.
1.3.6.1.4.1.818.1.2.8.3.2.1.1ColumnioInterfaceAnalogueLineIndex-Eighthnot-accessiblecurrentThe analogue line identifier.
1.3.6.1.4.1.818.1.2.8.3.2.1.2ColumnioInterfaceAnalogueDescription-Eighthread-writecurrentA description of the alarm monitored by this analogue line.
1.3.6.1.4.1.818.1.2.8.3.2.1.3ColumnioInterfaceAnalogueStatus-Eighthread-onlycurrentRead analogue value 1, when the board support such functionality
1.3.6.1.4.1.818.1.2.8.3.2.1.4ColumnioInterfaceAnalogueLowThreshold-Eighthread-writecurrentLow limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the specia…
1.3.6.1.4.1.818.1.2.8.3.2.1.5ColumnioInterfaceAnalogueHighThreshold-Eighthread-writecurrentHigh limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the…
1.3.6.1.4.1.818.1.2.8.3.2.1.6ColumnioInterfaceAnalogueResetLowThreshold-Eighthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.8.3.2.1.7ColumnioInterfaceAnalogueResetHighThreshold-Eighthread-writecurrentAfter an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis)
1.3.6.1.4.1.818.1.2.8.4NodeioInterfaceTraps-Eighth
1.3.6.1.4.1.818.1.2.8.4.1NodeioAlarmGenericChange-EighthAn generic change of a digital input/digital output/analog input has become active.
1.3.6.1.4.1.818.1.3NodegeModem
1.3.6.1.4.1.818.1.3.1ScalargeModemStatusread-onlycurrentThe status of the modem, controlled by the addressed device. The status word is a collection of bits, as specified below. The SNMP value NOSUCHNAME means 'stat…
1.3.6.1.4.1.818.1.3.2ScalargeModemNumInitStringread-onlycurrentThe number of modem init strings utilized by this ups. This entry indicates the number of rows in the init string table.
1.3.6.1.4.1.818.1.3.3TablegeModemInitStringTablenot-accessiblecurrentA list of init string table entries. The number of entries is given by the value of geModemNumInitString.
1.3.6.1.4.1.818.1.3.3.1RowgeModemInitStringEntrynot-accessiblecurrentAn entry containing information applicable to a particular Init string.
1.3.6.1.4.1.818.1.3.3.1.1ColumngeModemInitStringLineIndexnot-accessiblecurrentThe Init string line identifier.
1.3.6.1.4.1.818.1.3.3.1.2ColumngeModemInitstringread-writecurrentA modem Init string.
1.3.6.1.4.1.818.1.3.4ScalargeModemNumPhoneNumberread-onlycurrentThe number of modem phone numbers utilized by this ups. This entry indicates the number of rows in the table.
1.3.6.1.4.1.818.1.3.5TablegeModemPhoneNumberTablenot-accessiblecurrentA list of phone number table entries. The number of entries is given by the value of geModemNumPhoneNumber.
1.3.6.1.4.1.818.1.3.5.1RowgeModemPhoneNumberEntrynot-accessiblecurrentAn entry containing information applicable to a particular phone number.
1.3.6.1.4.1.818.1.3.5.1.1ColumngeModemPhoneNumberLineIndexnot-accessiblecurrentThe phone number line identifier.
1.3.6.1.4.1.818.1.3.5.1.2ColumngeModemPhoneNumberread-writecurrentA phone number.
1.3.6.1.4.1.818.1.100NodegeDevices
1.3.6.1.4.1.818.1.100.1NodegeDevicesDescriptions
1.3.6.1.4.1.818.1.100.1.1NodeadvSNMPWebIntCard
1.3.6.1.4.1.818.1.100.1.2NodesnmpWebIntCard
1.3.6.1.4.1.818.1.100.1.3NodesnmpWebIntBox
1.3.6.1.4.1.818.1.100.1.4NodesnmpSWPFAgent
1.3.6.1.4.1.818.1.100.1.5NodesnmpSWJUMPAgent
1.3.6.1.4.1.818.2NodegeSoftware
1.3.6.1.4.1.818.2.1NodegeClient
1.3.6.1.4.1.818.2.1.1ScalargeClientProcessorread-onlycurrentThe processor used by the clients machine.
1.3.6.1.4.1.818.2.1.2ScalargeClientOperatingSystemread-onlycurrentOperating system on which the client runs.
1.3.6.1.4.1.818.2.1.3ScalargeClientJavaRuntimeVersionread-onlycurrentJavaRuntimeVersion of the client machine.
1.3.6.1.4.1.818.2.1.4ScalargeClientMaxSizeOfLogfilesread-writecurrentThe max. size of the logfiles in Kb.
1.3.6.1.4.1.818.2.1.5ScalargeClientLanguageSelectionread-onlycurrentShows the currently activated language of the client.
1.3.6.1.4.1.818.2.1.6ScalargeClientInternalCommunicationPortread-writecurrentUDP port used between server and client part.
1.3.6.1.4.1.818.2.1.7ScalargeClientRebootwrite-onlycurrentsetting this object causes the protection client to reboot and activate new settings.
1.3.6.1.4.1.818.2.1.8ScalargeClientNumUPSread-onlycurrentThe number of UPSs utilized by this client. This entry indicates the number of rows in the table.
1.3.6.1.4.1.818.2.1.9TablegeClientUPSTablenot-accessiblecurrentA list of UPS table entries. The number of entries is given by the value of geClientNumUPS.
1.3.6.1.4.1.818.2.1.9.1RowgeClientUPSEntrynot-accessiblecurrentAn entry containing information applicable to a particular UPS.
1.3.6.1.4.1.818.2.1.9.1.1ColumngeClientUPSLineIndexnot-accessiblecurrentThe UPS line identifier.
1.3.6.1.4.1.818.2.1.9.1.2ColumngeClientUPSNameread-writecurrentThe administrative name of the UPS.
1.3.6.1.4.1.818.2.1.9.1.3ColumngeClientUPSCommunicationTyperead-writecurrentThe method of communication.
1.3.6.1.4.1.818.2.1.9.1.4ColumngeClientUPSCommunicationPortread-writecurrentThe communication port.
1.3.6.1.4.1.818.2.1.9.1.5ColumngeClientUPSReadCommNameread-writecurrentThe Read community string. Used when communication method is SNMP.
1.3.6.1.4.1.818.2.1.9.1.6ColumngeClientUPSWriteCommNameread-writecurrentThe Write community string. Used when communication method is SNMP.
1.3.6.1.4.1.818.2.1.9.1.7ColumngeClientUPSCommRetriesread-writecurrentNumber of retries in case an answer times out. When the max. number of retries is reached a lost communication alarm will be raised.
1.3.6.1.4.1.818.2.1.9.1.8ColumngeClientAlarmManagementread-writecurrentAlarm Management enabled or disabled.
1.3.6.1.4.1.818.2.1.9.1.9ColumngeClientPreDelayread-onlycurrentThe number of second an alarm needs to be active before action is taken.
1.3.6.1.4.1.818.2.1.9.1.10ColumngeClientSystemShutdownread-onlycurrentSpecifies whether the client should shutdown the machine when an alarm situation occurs.
1.3.6.1.4.1.818.2.1.9.1.11ColumngeClientRuntimeread-onlycurrentThe user defined preferable runtime.
1.3.6.1.4.1.818.2.1.9.1.12ColumngeClientUPSShutdownread-onlycurrentDefines whether the UPS will be shut down after an Operating System shutdown.
1.3.6.1.4.1.818.2.1.9.1.13ColumngeClientMaxScriptExecutionTimeread-onlycurrentThe max. number of seconds the script file is allowed to run.
1.3.6.1.4.1.818.2.1.9.1.14ColumngeClientGraceperiodread-onlycurrentThe time between start of the Operating System shutdown and the UPS shutdown.
1.3.6.1.4.1.818.2.1.20ScalargeClientNumTestsread-onlycurrentThe number of scheduled tests. This entry indicates the number of rows in the table.
1.3.6.1.4.1.818.2.1.21TablegeClientTestTablenot-accessiblecurrentA list of test table entries. The number of entries is given by the value of geClientNumTests.
1.3.6.1.4.1.818.2.1.21.1RowgeClientTestEntrynot-accessiblecurrentAn entry containing information applicable to a particular Test.
1.3.6.1.4.1.818.2.1.21.1.1ColumngeClientTestLineIndexnot-accessiblecurrentThe test line identifier.
1.3.6.1.4.1.818.2.1.21.1.2ColumngeClientTestIdread-writecurrentThe test Id.
1.3.6.1.4.1.818.2.1.21.1.3ColumngeClientTestDayTimeread-writecurrentThe time on which the test is due to be performed.
1.3.6.1.4.1.818.2.1.21.1.4ColumngeClientTestWeekDayread-writecurrentThe day in the week on which the test will be performed.
1.3.6.1.4.1.818.2.1.21.1.5ColumngeClientTestMonthDayread-writecurrentThe month day on which the test will be performed.
1.3.6.1.4.1.818.2.1.30ScalargeClientNumShutdownsread-onlycurrentThe number of scheduled Shutdowns. This entry indicates the number of rows in the table.
1.3.6.1.4.1.818.2.1.31TablegeClientShutdownTablenot-accessiblecurrentA list of Shutdown table entries. The number of entries is given by the value of geClientNumShutdowns.
1.3.6.1.4.1.818.2.1.31.1RowgeClientShutdownEntrynot-accessiblecurrentAn entry containing information applicable to a particular Shutdown.
1.3.6.1.4.1.818.2.1.31.1.1ColumngeClientShutdownLineIndexnot-accessiblecurrentThe Shutdown line identifier.
1.3.6.1.4.1.818.2.1.31.1.2ColumngeClientShutdownDelayread-writecurrentThe delay before start of the Shutdown.
1.3.6.1.4.1.818.2.1.31.1.3ColumngeClientShutdownDurationread-writecurrentThe duration of the Shutdown.
1.3.6.1.4.1.818.2.1.31.1.4ColumngeClientShutdownDayTimeread-writecurrentThe time on which the Shutdown is due to be performed.
1.3.6.1.4.1.818.2.1.31.1.5ColumngeClientShutdownWeekDayread-writecurrentThe day in the week on which the Shutdown will be performed.
1.3.6.1.4.1.818.2.1.31.1.6ColumngeClientShutdownMonthDayread-writecurrentThe month day on which the Shutdown will be performed.
1.3.6.1.4.1.818.2.1.31.1.7ColumngeClientShutdownPreWarnTimeread-writecurrentThe number of seconds before start of the shutdown a pre warning will be raised.
1.3.6.1.4.1.818.3NodegeAgent
1.3.6.1.4.1.818.3.1NodegeAgentConfig
1.3.6.1.4.1.818.3.1.1ScalargeAgentUDPPortread-writecurrentThe UDP port number used by agent.
1.3.6.1.4.1.818.3.1.2ScalargeAgentWebServerPortread-writecurrentThe UDP port number used by the HTTP server.
1.3.6.1.4.1.818.3.1.3ScalargeAgentComPortread-writecurrentThe COM port used by the agent.
1.3.6.1.4.1.818.3.1.4ScalargeAgentComTimeoutread-writecurrentThe Timeout delay in seconds of the serial communication.
1.3.6.1.4.1.818.3.1.5ScalargeAgentComRetriesread-writecurrentThe number of retries when serial communication fails.
1.3.6.1.4.1.818.3.1.6ScalargeAgentReadCommunityread-writecurrentThe read community string of the agent.
1.3.6.1.4.1.818.3.1.7ScalargeAgentWriteCommunityread-writecurrentThe write community string of the agent.
1.3.6.1.4.1.818.3.1.8ScalargeAgentResponsibleEmailAddressread-writecurrentThe email address of the responsible person for this agent.
1.3.6.1.4.1.818.3.1.9ScalargeRFCTrapsToSendread-writecurrentThis object defines whether RFC traps need to be send. The bit value 1 indicates that the traps needs to be send, while value 0 does not result in a trap to se…
1.3.6.1.4.1.818.3.1.10ScalargeIMVTrapsToSendread-writecurrentThis object defines for which device(s) IMV traps need to be send. The bit value 1 indicates that the trap needs to be send, while value 0 does not result in a…
1.3.6.1.4.1.818.3.2NodegeAgentTraps
1.3.6.1.4.1.818.3.2.1ScalargeAgentNumTrapsread-onlycurrentThe number of configured traps. This entry indicates the number of rows in the table.
1.3.6.1.4.1.818.3.2.2TablegeAgentTrapTablenot-accessiblecurrentA list of trap table entries. The number of entries is given by the value of geAgentNumTraps.
1.3.6.1.4.1.818.3.2.2.1RowgeAgentTrapEntrynot-accessiblecurrentAn entry containing information applicable to a particular trap target.
1.3.6.1.4.1.818.3.2.2.1.1ColumngeAgentTrapLineIndexnot-accessiblecurrentThe Trap line identifier.
1.3.6.1.4.1.818.3.2.2.1.2ColumngeAgentTrapAddressread-writecurrentThe destination IP-address of the trap.
1.3.6.1.4.1.818.3.2.2.1.3ColumngeAgentTrapCommunityread-writecurrentThe communication string used by the trap.
1.3.6.1.4.1.818.3.2.2.1.4ColumngeAgentTrapPortread-writecurrentThe UDP port on the receiving side.
Type Definitions
NameSyntaxStatusDescription
NonNegativeInteger32Integer32 (0..2147483647)currentThis data type is a non-negative value.
PositiveInteger32Integer32 (1..2147483647)currentThis data type is a non-zero and non-negative value.