MIB Viewer

LIEBERT-SITENET-INTEGRATOR-MIB

192 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1NodeenvSummaryAlarmTrapAn envSummaryAlarmTrap is generated each time a digital input State variable changes to true(1) or whenever a temperature or humidity goes above the HighLimit …
1.3.6.1.4.1.476Nodeemerson
1.3.6.1.4.1.476.1NodeliebertCorp
1.3.6.1.4.1.476.1.1NodeliebertUps
1.3.6.1.4.1.476.1.2NodeliebertEnvironment
1.3.6.1.4.1.476.1.2.1NodeleExtensions
1.3.6.1.4.1.476.1.2.1.1NodeleSiteNet01
1.3.6.1.4.1.476.1.2.1.1.1NodeenvMIB
1.3.6.1.4.1.476.1.2.1.1.1.1NodeenvIdent
1.3.6.1.4.1.476.1.2.1.1.1.1.1ScalarenvIdentManufacturerread-onlymandatoryThe Environmental Control Unit manufacturer.
1.3.6.1.4.1.476.1.2.1.1.1.1.2ScalarenvIdentModelread-writemandatoryThe Environmental Control Unit Model designation.
1.3.6.1.4.1.476.1.2.1.1.1.1.3ScalarenvIdentSoftwareVersionread-onlymandatoryThe Environmental SNMP Agent software version.
1.3.6.1.4.1.476.1.2.1.1.1.1.4ScalarenvIdentSpecificread-onlymandatoryA reference to MIB definitions specific to the particular Environmental Unit being managed. This object is used to locate the product-specific MIB for this dev…
1.3.6.1.4.1.476.1.2.1.1.1.2NodeenvDigitalInputs
1.3.6.1.4.1.476.1.2.1.1.1.2.1NodeenvDigInput1
1.3.6.1.4.1.476.1.2.1.1.1.2.1.1ScalarenvDigInput1Stateread-onlymandatoryThe state of Digital Input Number 1. When the envDigInput1Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput1Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.1.2ScalarenvDigInput1Labelread-writemandatoryA user-defined text string associated with Digital Input Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.1.3ScalarenvDigInput1Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 1. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.1.4ScalarenvDigInput1TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 1. When envDigInput1TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.2NodeenvDigInput2
1.3.6.1.4.1.476.1.2.1.1.1.2.2.1ScalarenvDigInput2Stateread-onlymandatoryThe state of Digital Input Number 2. When the envDigInput2Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput2Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.2.2ScalarenvDigInput2Labelread-writemandatoryA user-defined text string associated with Digital Input Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.2.3ScalarenvDigInput2Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 2. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.2.4ScalarenvDigInput2TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 2. When envDigInput2TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.3NodeenvDigInput3
1.3.6.1.4.1.476.1.2.1.1.1.2.3.1ScalarenvDigInput3Stateread-onlymandatoryThe state of Digital Input Number 3. When the envDigInput3Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput3Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.3.2ScalarenvDigInput3Labelread-writemandatoryA user-defined text string associated with Digital Input Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.3.3ScalarenvDigInput3Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 3. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.3.4ScalarenvDigInput3TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 3. When envDigInput3TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.4NodeenvDigInput4
1.3.6.1.4.1.476.1.2.1.1.1.2.4.1ScalarenvDigInput4Stateread-onlymandatoryThe state of Digital Input Number 4. When the envDigInput4Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput4Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.4.2ScalarenvDigInput4Labelread-writemandatoryA user-defined text string associated with Digital Input Number 4. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.4.3ScalarenvDigInput4Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 4. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.4.4ScalarenvDigInput4TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 4. When envDigInput4TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.5NodeenvDigInput5
1.3.6.1.4.1.476.1.2.1.1.1.2.5.1ScalarenvDigInput5Stateread-onlymandatoryThe state of Digital Input Number 5. When the envDigInput5Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput5Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.5.2ScalarenvDigInput5Labelread-writemandatoryA user-defined text string associated with Digital Input Number 5. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.5.3ScalarenvDigInput5Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 5. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.5.4ScalarenvDigInput5TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 5. When envDigInput5TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.6NodeenvDigInput6
1.3.6.1.4.1.476.1.2.1.1.1.2.6.1ScalarenvDigInput6Stateread-onlymandatoryThe state of Digital Input Number 6. When the envDigInput6Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput6Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.6.2ScalarenvDigInput6Labelread-writemandatoryA user-defined text string associated with Digital Input Number 6. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.6.3ScalarenvDigInput6Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 6. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.6.4ScalarenvDigInput6TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 6. When envDigInput6TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.7NodeenvDigInput7
1.3.6.1.4.1.476.1.2.1.1.1.2.7.1ScalarenvDigInput7Stateread-onlymandatoryThe state of Digital Input Number 7. When the envDigInput7Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput7Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.7.2ScalarenvDigInput7Labelread-writemandatoryA user-defined text string associated with Digital Input Number 7. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.7.3ScalarenvDigInput7Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 7. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.7.4ScalarenvDigInput7TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 7. When envDigInput7TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.8NodeenvDigInput8
1.3.6.1.4.1.476.1.2.1.1.1.2.8.1ScalarenvDigInput8Stateread-onlymandatoryThe state of Digital Input Number 8. When the envDigInput8Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput8Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.8.2ScalarenvDigInput8Labelread-writemandatoryA user-defined text string associated with Digital Input Number 8. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.8.3ScalarenvDigInput8Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 8. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.8.4ScalarenvDigInput8TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 8. When envDigInput8TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.9NodeenvDigInput9
1.3.6.1.4.1.476.1.2.1.1.1.2.9.1ScalarenvDigInput9Stateread-onlymandatoryThe state of Digital Input Number 9. When the envDigInput9Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput9Polarity…
1.3.6.1.4.1.476.1.2.1.1.1.2.9.2ScalarenvDigInput9Labelread-writemandatoryA user-defined text string associated with Digital Input Number 9. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.9.3ScalarenvDigInput9Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 9. It controls the value returned by the State variable. When Polarity is set to…
1.3.6.1.4.1.476.1.2.1.1.1.2.9.4ScalarenvDigInput9TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 9. When envDigInput9TrapEnabled is set to true(1), a TRAP message will be generated w…
1.3.6.1.4.1.476.1.2.1.1.1.2.10NodeenvDigInput10
1.3.6.1.4.1.476.1.2.1.1.1.2.10.1ScalarenvDigInput10Stateread-onlymandatoryThe state of Digital Input Number 10. When the envDigInput10Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput10Polar…
1.3.6.1.4.1.476.1.2.1.1.1.2.10.2ScalarenvDigInput10Labelread-writemandatoryA user-defined text string associated with Digital Input Number 10. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.2.10.3ScalarenvDigInput10Polarityread-writemandatoryThe Polarity to be associated with the State variable for Digital Input Number 10. It controls the value returned by the State variable. When Polarity is set t…
1.3.6.1.4.1.476.1.2.1.1.1.2.10.4ScalarenvDigInput10TrapEnabledread-writemandatoryA TRAP may be associated with the State variable for Digital Input Number 10. When envDigInput10TrapEnabled is set to true(1), a TRAP message will be generated…
1.3.6.1.4.1.476.1.2.1.1.1.3NodeenvRelays
1.3.6.1.4.1.476.1.2.1.1.1.3.1NodeenvRelay1
1.3.6.1.4.1.476.1.2.1.1.1.3.1.1ScalarenvRelay1Stateread-writemandatoryThe state of Output Relay Number 1. When State is set to on(1) Output Relay Number 1 is activated and the normally open contacts are closed. When State is set …
1.3.6.1.4.1.476.1.2.1.1.1.3.1.2ScalarenvRelay1Labelread-writemandatoryA user-defined text string associated with Output Relay Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.3.1.3ScalarenvRelay1Controlread-writemandatoryIf Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting …
1.3.6.1.4.1.476.1.2.1.1.1.3.2NodeenvRelay2
1.3.6.1.4.1.476.1.2.1.1.1.3.2.1ScalarenvRelay2Stateread-writemandatoryThe state of Output Relay Number 2. When State is set to on(1) Output Relay Number 2 is activated and the normally open contacts are closed. When State is set …
1.3.6.1.4.1.476.1.2.1.1.1.3.2.2ScalarenvRelay2Labelread-writemandatoryA user-defined text string associated with Output Relay Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.3.2.3ScalarenvRelay2Controlread-writemandatoryIf Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting …
1.3.6.1.4.1.476.1.2.1.1.1.4NodeenvOutputs
1.3.6.1.4.1.476.1.2.1.1.1.4.1NodeenvAudible
1.3.6.1.4.1.476.1.2.1.1.1.4.1.1ScalarenvAudibleStateread-writemandatoryThe state of the Audible Output. When State is set to on(1) the Audible will be sounded. When State is set to off(2) the Audible is muted.
1.3.6.1.4.1.476.1.2.1.1.1.4.1.2ScalarenvAudibleControlread-writemandatoryIf Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting …
1.3.6.1.4.1.476.1.2.1.1.1.4.2NodeenvLED1
1.3.6.1.4.1.476.1.2.1.1.1.4.2.1ScalarenvLED1Stateread-writemandatoryThe state of Output LED Number 1. When State is set to on(1) LED Number 1 will be lighted. When State is set to off(2) LED Number 1 will not be lighted.
1.3.6.1.4.1.476.1.2.1.1.1.4.2.2ScalarenvLED1Labelread-writemandatoryA user-defined text string associated with Output LED Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.4.2.3ScalarenvLED1Controlread-writemandatoryIf Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting …
1.3.6.1.4.1.476.1.2.1.1.1.4.3NodeenvLED2
1.3.6.1.4.1.476.1.2.1.1.1.4.3.1ScalarenvLED2Stateread-writemandatoryThe state of Output LED Number 2. When State is set to on(1) LED Number 2 will be lighted. When State is set to off(2) LED Number 2 will not be lighted.
1.3.6.1.4.1.476.1.2.1.1.1.4.3.2ScalarenvLED2Labelread-writemandatoryA user-defined text string associated with Output LED Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.4.3.3ScalarenvLED2Controlread-writemandatoryIf Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting …
1.3.6.1.4.1.476.1.2.1.1.1.4.4NodeenvLED3
1.3.6.1.4.1.476.1.2.1.1.1.4.4.1ScalarenvLED3Stateread-writemandatoryThe state of Output LED Number 3. When State is set to on(1) LED Number 3 will be lighted. When State is set to off(2) LED Number 3 will not be lighted.
1.3.6.1.4.1.476.1.2.1.1.1.4.4.2ScalarenvLED3Labelread-writemandatoryA user-defined text string associated with Output LED Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.4.4.3ScalarenvLED3Controlread-writemandatoryIf Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting …
1.3.6.1.4.1.476.1.2.1.1.1.5NodeenvReceptacles
1.3.6.1.4.1.476.1.2.1.1.1.5.1NodeenvReceptacle1
1.3.6.1.4.1.476.1.2.1.1.1.5.1.1ScalarenvReceptacle1Stateread-writemandatoryThe state of the Receptacle Number 1. When State is set to on(1) power will be live on Receptacle Number 1. When State is set to off(2) no power is available f…
1.3.6.1.4.1.476.1.2.1.1.1.5.1.2ScalarenvReceptacle1Labelread-writemandatoryA user-defined text string associated with Receptacle Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.5.2NodeenvReceptacle2
1.3.6.1.4.1.476.1.2.1.1.1.5.2.1ScalarenvReceptacle2Stateread-writemandatoryThe state of the Receptacle Number 2. When State is set to on(1) power will be live on Receptacle Number 2. When State is set to off(2) no power is available f…
1.3.6.1.4.1.476.1.2.1.1.1.5.2.2ScalarenvReceptacle2Labelread-writemandatoryA user-defined text string associated with Receptacle Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.5.3NodeenvReceptacle3
1.3.6.1.4.1.476.1.2.1.1.1.5.3.1ScalarenvReceptacle3Stateread-writemandatoryThe state of the Receptacle Number 3. When State is set to on(1) power will be live on Receptacle Number 3. When State is set to off(2) no power is available f…
1.3.6.1.4.1.476.1.2.1.1.1.5.3.2ScalarenvReceptacle3Labelread-writemandatoryA user-defined text string associated with Receptacle Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.5.4NodeenvReceptacle4
1.3.6.1.4.1.476.1.2.1.1.1.5.4.1ScalarenvReceptacle4Stateread-writemandatoryThe state of the Receptacle Number 4. When State is set to on(1) power will be live on Receptacle Number 4. When State is set to off(2) no power is available f…
1.3.6.1.4.1.476.1.2.1.1.1.5.4.2ScalarenvReceptacle4Labelread-writemandatoryA user-defined text string associated with Receptacle Number 4. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.6NodeenvAlarms
1.3.6.1.4.1.476.1.2.1.1.1.6.1ScalarenvSummaryAlarmread-onlymandatoryThe envSummaryAlarm varible will be 0 when no Digital Inputs are true and no other alarm conditions exist. When alarms are active or Digital Inputs are true th…
1.3.6.1.4.1.476.1.2.1.1.1.7NodeenvTemperatureSensors
1.3.6.1.4.1.476.1.2.1.1.1.7.1NodeenvTemperature1
1.3.6.1.4.1.476.1.2.1.1.1.7.1.1ScalarenvTemperature1Stateread-writemandatoryThe state of use of Temperature Input Number 1. When a sensor is connected to Temperature Input 1 set State to installed(2) to indicate that the value of envTe…
1.3.6.1.4.1.476.1.2.1.1.1.7.1.2ScalarenvTemperature1Fread-onlymandatoryThe temperature for sensor 1 in degrees Fahrenheit.
1.3.6.1.4.1.476.1.2.1.1.1.7.1.3ScalarenvTemperature1Cread-onlymandatoryThe temperature for sensor 1 in degrees Centigrade.
1.3.6.1.4.1.476.1.2.1.1.1.7.1.4ScalarenvTemperature1Labelread-writemandatoryA user-defined text string associated with Temperature Input Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.7.1.5ScalarenvTemperature1OffsetFread-writemandatoryA temperature correction Offset associated with the envTemperature1F variable. The value of OffsetF is added to the value from Temperature Sensor Number 1 to o…
1.3.6.1.4.1.476.1.2.1.1.1.7.1.6ScalarenvTemperature1OffsetCread-writemandatoryA temperature correction Offset associated with the envTemperature1C variable. The value of OffsetC is added to the value from Temperature Sensor Number 1 to o…
1.3.6.1.4.1.476.1.2.1.1.1.7.1.7ScalarenvTemp1HighLimitFread-writemandatoryWhen envTemperature1F reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 1. The HighLimitF va…
1.3.6.1.4.1.476.1.2.1.1.1.7.1.8ScalarenvTemp1HighLimitCread-writemandatoryWhen envTemperature1C reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 1. The HighLimitC va…
1.3.6.1.4.1.476.1.2.1.1.1.7.1.9ScalarenvTemp1LowLimitFread-writemandatoryWhen envTemperature1F reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 1. The LowLimitF v…
1.3.6.1.4.1.476.1.2.1.1.1.7.1.10ScalarenvTemp1LowLimitCread-writemandatoryWhen envTemperature1C reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 1. The LowLimitC v…
1.3.6.1.4.1.476.1.2.1.1.1.7.2NodeenvTemperature2
1.3.6.1.4.1.476.1.2.1.1.1.7.2.1ScalarenvTemperature2Stateread-writemandatoryThe state of use of Temperature Input Number 2. When a sensor is connected to Temperature Input 2 set State to installed(2) to indicate that the value of envTe…
1.3.6.1.4.1.476.1.2.1.1.1.7.2.2ScalarenvTemperature2Fread-onlymandatoryThe temperature for sensor 2 in degrees Fahrenheit.
1.3.6.1.4.1.476.1.2.1.1.1.7.2.3ScalarenvTemperature2Cread-onlymandatoryThe temperature for sensor 2 in degrees Centigrade.
1.3.6.1.4.1.476.1.2.1.1.1.7.2.4ScalarenvTemperature2Labelread-writemandatoryA user-defined text string associated with Temperature Input Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.7.2.5ScalarenvTemperature2OffsetFread-writemandatoryA temperature correction Offset associated with the envTemperature2F variable. The value of OffsetF is added to the value from Temperature Sensor Number 2 to o…
1.3.6.1.4.1.476.1.2.1.1.1.7.2.6ScalarenvTemperature2OffsetCread-writemandatoryA temperature correction Offset associated with the envTemperature2C variable. The value of OffsetC is added to the value from Temperature Sensor Number 2 to o…
1.3.6.1.4.1.476.1.2.1.1.1.7.2.7ScalarenvTemp2HighLimitFread-writemandatoryWhen envTemperature2F reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 2. The HighLimitF va…
1.3.6.1.4.1.476.1.2.1.1.1.7.2.8ScalarenvTemp2HighLimitCread-writemandatoryWhen envTemperature2C reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 2. The HighLimitC va…
1.3.6.1.4.1.476.1.2.1.1.1.7.2.9ScalarenvTemp2LowLimitFread-writemandatoryWhen envTemperature2F reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 2. The LowLimitF v…
1.3.6.1.4.1.476.1.2.1.1.1.7.2.10ScalarenvTemp2LowLimitCread-writemandatoryWhen envTemperature2C reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 2. The LowLimitC v…
1.3.6.1.4.1.476.1.2.1.1.1.7.3NodeenvTemperature3
1.3.6.1.4.1.476.1.2.1.1.1.7.3.1ScalarenvTemperature3Stateread-writemandatoryThe state of use of Temperature Input Number 3. When a water temperature sensor is connected to Temperature Input 3 set State to waterSensorInstalled(3), when …
1.3.6.1.4.1.476.1.2.1.1.1.7.3.2ScalarenvTemperature3Fread-onlymandatoryThe temperature for sensor 3 in degrees Fahrenheit.
1.3.6.1.4.1.476.1.2.1.1.1.7.3.3ScalarenvTemperature3Cread-onlymandatoryThe temperature for sensor 3 in degrees Centigrade.
1.3.6.1.4.1.476.1.2.1.1.1.7.3.4ScalarenvTemperature3Labelread-writemandatoryA user-defined text string associated with Temperature Input Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.7.3.5ScalarenvTemperature3OffsetFread-writemandatoryA temperature correction Offset associated with the envTemperature3F variable. The value of OffsetF is added to the value from Temperature Sensor Number 3 to o…
1.3.6.1.4.1.476.1.2.1.1.1.7.3.6ScalarenvTemperature3OffsetCread-writemandatoryA temperature correction Offset associated with the envTemperature3C variable. The value of OffsetC is added to the value from Temperature Sensor Number 3 to o…
1.3.6.1.4.1.476.1.2.1.1.1.7.3.7ScalarenvTemp3HighLimitFread-writemandatoryWhen envTemperature3F reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 3. The HighLimitF va…
1.3.6.1.4.1.476.1.2.1.1.1.7.3.8ScalarenvTemp3HighLimitCread-writemandatoryWhen envTemperature3C reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 3. The HighLimitC va…
1.3.6.1.4.1.476.1.2.1.1.1.7.3.9ScalarenvTemp3LowLimitFread-writemandatoryWhen envTemperature3F reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 3. The LowLimitF v…
1.3.6.1.4.1.476.1.2.1.1.1.7.3.10ScalarenvTemp3LowLimitCread-writemandatoryWhen envTemperature3C reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 3. The LowLimitC v…
1.3.6.1.4.1.476.1.2.1.1.1.7.3.11ScalarenvTemp3Calibrateread-writemandatoryA temperature Offset correction routine associated with Temperature Sensor Number 3. When Calibrate is set to on(1) and State is set to waterSensorInstalled(3)…
1.3.6.1.4.1.476.1.2.1.1.1.8NodeenvHumiditySensors
1.3.6.1.4.1.476.1.2.1.1.1.8.1NodeenvHumidity1
1.3.6.1.4.1.476.1.2.1.1.1.8.1.1ScalarenvHumidity1Stateread-writemandatoryThe state of use of Humidity Input Number 1. When a sensor is connected to Humidity Input 1 set State to installed(2) to indicate that the value of envHumidity…
1.3.6.1.4.1.476.1.2.1.1.1.8.1.2ScalarenvHumidity1RHread-onlymandatoryThe humidity for sensor 1 in percent RH.
1.3.6.1.4.1.476.1.2.1.1.1.8.1.3ScalarenvHumidity1Labelread-writemandatoryA user-defined text string associated with Humidity Input Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.8.1.4ScalarenvHumidity1Offsetread-writemandatoryA humidity correction Offset associated with the envHumidity1RH variable. The value of Offset is added to the value from Humidity Sensor Number 1 to obtain the…
1.3.6.1.4.1.476.1.2.1.1.1.8.1.5ScalarenvHumidity1HighLimitread-writemandatoryWhen envHumidity1RH reaches or exceeds this value a trap will be generated signifying a high humidity condition at humidity sensor 1. The HighLimit variable is…
1.3.6.1.4.1.476.1.2.1.1.1.8.1.6ScalarenvHumidity1LowLimitread-writemandatoryWhen envHumidity1RH reaches or goes below this value a trap will be generated signifying a low humidity condition at humidity sensor 1. The LowLimit variable i…
1.3.6.1.4.1.476.1.2.1.1.1.8.2NodeenvHumidity2
1.3.6.1.4.1.476.1.2.1.1.1.8.2.1ScalarenvHumidity2Stateread-writemandatoryThe state of use of Humidity Input Number 2. When a sensor is connected to Humidity Input 2 set State to installed(2) to indicate that the value of envHumidity…
1.3.6.1.4.1.476.1.2.1.1.1.8.2.2ScalarenvHumidity2RHread-onlymandatoryThe humidity for sensor 2 in percent RH.
1.3.6.1.4.1.476.1.2.1.1.1.8.2.3ScalarenvHumidity2Labelread-writemandatoryA user-defined text string associated with Humidity Input Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.476.1.2.1.1.1.8.2.4ScalarenvHumidity2Offsetread-writemandatoryA humidity correction Offset associated with the envHumidity2RH variable. The value of Offset is added to the value from Humidity Sensor Number 2 to obtain the…
1.3.6.1.4.1.476.1.2.1.1.1.8.2.5ScalarenvHumidity2HighLimitread-writemandatoryWhen envHumidity2RH reaches or exceeds this value a trap will be generated signifying a high humidity condition at humidity sensor 2. The HighLimit variable is…
1.3.6.1.4.1.476.1.2.1.1.1.8.2.6ScalarenvHumidity2LowLimitread-writemandatoryWhen envHumidity2RH reaches or goes below this value a trap will be generated signifying a low humidity condition at humidity sensor 2. The LowLimit variable i…
1.3.6.1.4.1.476.1.2.1.1.1.11NodeenvTraps
1.3.6.1.4.1.476.1.2.2NodeleExperimental
1.3.6.1.4.1.476.1.2.3NodelePrivate
2NodeenvDigInput1TrueTrapAn envDigInput1TrueTrap signifies that envDigitalInput1State has changed from false(2) to true(1). This trap is not generated if envDigInput1TrapEnabled is not…
3NodeenvDigInput1FalseTrapAn envDigInput1FalseTrap signifies that envDigitalInput1State has changed from true(1) to false(2). This trap is not generated if envDigInput1TrapEnabled is no…
4NodeenvDigInput2TrueTrapAn envDigInput2TrueTrap signifies that envDigitalInput2State has changed from false(2) to true(1). This trap is not generated if envDigInput2TrapEnabled is not…
5NodeenvDigInput2FalseTrapAn envDigInput2FalseTrap signifies that envDigitalInput2State has changed from true(1) to false(2). This trap is not generated if envDigInput2TrapEnabled is no…
6NodeenvDigInput3TrueTrapAn envDigInput3TrueTrap signifies that envDigitalInput3State has changed from false(2) to true(1). This trap is not generated if envDigInput3TrapEnabled is not…
7NodeenvDigInput3FalseTrapAn envDigInput3FalseTrap signifies that envDigitalInput3State has changed from true(1) to false(2). This trap is not generated if envDigInput3TrapEnabled is no…
8NodeenvDigInput4TrueTrapAn envDigInput4TrueTrap signifies that envDigitalInput4State has changed from false(2) to true(1). This trap is not generated if envDigInput4TrapEnabled is not…
9NodeenvDigInput4FalseTrapAn envDigInput4FalseTrap signifies that envDigitalInput4State has changed from true(1) to false(2). This trap is not generated if envDigInput4TrapEnabled is no…
10NodeenvDigInput5TrueTrapAn envDigInput5TrueTrap signifies that envDigitalInput5State has changed from false(2) to true(1). This trap is not generated if envDigInput5TrapEnabled is not…
11NodeenvDigInput5FalseTrapAn envDigInput5FalseTrap signifies that envDigitalInput5State has changed from true(1) to false(2). This trap is not generated if envDigInput5TrapEnabled is no…
12NodeenvDigInput6TrueTrapAn envDigInput6TrueTrap signifies that envDigitalInput6State has changed from false(2) to true(1). This trap is not generated if envDigInput6TrapEnabled is not…
13NodeenvDigInput6FalseTrapAn envDigInput6FalseTrap signifies that envDigitalInput6State has changed from true(1) to false(2). This trap is not generated if envDigInput6TrapEnabled is no…
14NodeenvDigInput7TrueTrapAn envDigInput7TrueTrap signifies that envDigitalInput7State has changed from false(2) to true(1). This trap is not generated if envDigInput7TrapEnabled is not…
15NodeenvDigInput7FalseTrapAn envDigInput7FalseTrap signifies that envDigitalInput7State has changed from true(1) to false(2). This trap is not generated if envDigInput7TrapEnabled is no…
16NodeenvDigInput8TrueTrapAn envDigInput8TrueTrap signifies that envDigitalInput8State has changed from false(2) to true(1). This trap is not generated if envDigInput8TrapEnabled is not…
17NodeenvDigInput8FalseTrapAn envDigInput8FalseTrap signifies that envDigitalInput8State has changed from true(1) to false(2). This trap is not generated if envDigInput8TrapEnabled is no…
18NodeenvDigInput9TrueTrapAn envDigInput9TrueTrap signifies that envDigitalInput9State has changed from false(2) to true(1). This trap is not generated if envDigInput9TrapEnabled is not…
19NodeenvDigInput9FalseTrapAn envDigInput9FalseTrap signifies that envDigitalInput9State has changed from true(1) to false(2). This trap is not generated if envDigInput9TrapEnabled is no…
20NodeenvDigInput10TrueTrapAn envDigInput10TrueTrap signifies that envDigitalInput10State has changed from false(2) to true(1). This trap is not generated if envDigInput10TrapEnabled is …
21NodeenvDigInput10FalseTrapAn envDigInput10FalseTrap signifies that envDigitalInput10State has changed from true(1) to false(2). This trap is not generated if envDigInput10TrapEnabled is…
22NodeenvTemperature1HighTrapAn envTemperature1HighTrap signifies that the sensor reading has gone above the HighLimit value.
23NodeenvTemperature1LowTrapAn envTemperature1LowTrap signifies that the sensor reading has gone below the LowLimit value.
24NodeenvTemperature1NormalTrapAn envTemperature1NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit.
25NodeenvTemperature2HighTrapAn envTemperature2HighTrap signifies that the sensor reading has gone above the HighLimit value.
26NodeenvTemperature2LowTrapAn envTemperature2LowTrap signifies that the sensor reading has gone below the LowLimit value.
27NodeenvTemperature2NormalTrapAn envTemperature2NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit.
28NodeenvTemperature3HighTrapAn envTemperature3HighTrap signifies that the sensor reading has gone above the HighLimit value.
29NodeenvTemperature3LowTrapAn envTemperature3LowTrap signifies that the sensor reading has gone below the LowLimit value.
30NodeenvTemperature3NormalTrapAn envTemperature3NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit.
31NodeenvHumidity1HighTrapAn envHumidity1HighTrap signifies that the sensor reading has gone above the HighLimit value.
32NodeenvHumidity1LowTrapAn envHumidity1LowTrap signifies that the sensor reading has gone below the LowLimit value.
33NodeenvHumidity1NormalTrapAn envHumidity1NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit.
34NodeenvHumidity2HighTrapAn envHumidity2HighTrap signifies that the sensor reading has gone above the HighLimit value.
35NodeenvHumidity2LowTrapAn envHumidity2LowTrap signifies that the sensor reading has gone below the LowLimit value.
36NodeenvHumidity2NormalTrapAn envHumidity2NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit.