LIEBERT-UPS-MIB
277 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | Counter enterprises Gauge TimeTicks |
| RFC1213-MIB | DisplayString sysUpTime |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.476 | Nodeemerson | |||
| 1.3.6.1.4.1.476.1 | NodeliebertCorp | |||
| 1.3.6.1.4.1.476.1.1 | NodeliebertUps | |||
| 1.3.6.1.4.1.476.1.1.1 | NodeluExtensions | |||
| 1.3.6.1.4.1.476.1.1.1.1 | NodeluCore | |||
| 1.3.6.1.4.1.476.1.1.1.1.1 | NodelcUpsIdent | |||
| 1.3.6.1.4.1.476.1.1.1.1.1.1 | ScalarlcUpsIdentManufacturer | read-only | optional | The UPS manufacturer. |
| 1.3.6.1.4.1.476.1.1.1.1.1.2 | ScalarlcUpsIdentModel | read-write | optional | The UPS Model designation. |
| 1.3.6.1.4.1.476.1.1.1.1.1.3 | ScalarlcUpsIdentSoftwareVersion | read-only | optional | The UPS SNMP Agent software version. |
| 1.3.6.1.4.1.476.1.1.1.1.1.4 | ScalarlcUpsIdentSpecific | read-only | optional | A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this in… |
| 1.3.6.1.4.1.476.1.1.1.1.1.5 | ScalarlcUpsIdentFirmwareVersion | read-only | optional | The firmware revision level of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.1.6 | ScalarlcUpsIdentSerialNumber | read-only | optional | The serial number of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.1.7 | ScalarlcUpsIdentManufactureDate | read-only | optional | The date of manufacture of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.2 | NodelcUpsBattery | |||
| 1.3.6.1.4.1.476.1.1.1.1.2.1 | ScalarlcUpsBatTimeRemaining | read-only | optional | The estimated time to depletion of battery charge. (Unit of measure: Minute) |
| 1.3.6.1.4.1.476.1.1.1.1.2.2 | ScalarlcUpsBatTemperature | read-only | optional | The battery temperature. (Unit of measure: Degree, Centigrade) |
| 1.3.6.1.4.1.476.1.1.1.1.2.3 | ScalarlcUpsBatVoltage | read-only | optional | The current battery voltage. (Unit of measure: volt) |
| 1.3.6.1.4.1.476.1.1.1.1.2.4 | ScalarlcUpsBatCurrent | read-only | optional | The current battery discharging/charging current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.1.2.6 | ScalarlcUpsBatCapacity | read-only | optional | The current battery capacity in percentage of total available. |
| 1.3.6.1.4.1.476.1.1.1.1.2.7 | ScalarlcUpsBatTotalDischCounts | read-only | optional | The number of discharges the UPS has experienced. |
| 1.3.6.1.4.1.476.1.1.1.1.2.8 | ScalarlcUpsBatCycleDurationInSeconds | read-only | optional | The total accumulated discharge time in seconds. |
| 1.3.6.1.4.1.476.1.1.1.1.2.9 | ScalarlcUpsBatAmpHours | read-only | optional | The number of amp hours withdrawn from battery. |
| 1.3.6.1.4.1.476.1.1.1.1.2.10 | ScalarlcUpsBatKWhours | read-only | optional | The number of Kilowatt-hours withdrawn from battery. |
| 1.3.6.1.4.1.476.1.1.1.1.2.11 | ScalarlcUpsBatWattHours | read-only | optional | The number of Watt-hours withdrawn from battery. |
| 1.3.6.1.4.1.476.1.1.1.1.3 | NodelcUpsInput | |||
| 1.3.6.1.4.1.476.1.1.1.1.3.1 | ScalarlcUpsInputFrequency | read-only | optional | The current input frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.3.2 | ScalarlcUpsInputBrownOuts | read-only | optional | The number of brown-out conditions the UPS has experienced. |
| 1.3.6.1.4.1.476.1.1.1.1.3.3 | ScalarlcUpsInputBlackOuts | read-only | optional | The number of black-out conditions the UPS has experienced. |
| 1.3.6.1.4.1.476.1.1.1.1.3.4 | ScalarlcUpsInputTransients | read-only | optional | The number of transient (surge and spike) conditions the UPS has experienced. |
| 1.3.6.1.4.1.476.1.1.1.1.3.5 | ScalarlcUpsInputNumLines | read-only | optional | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| 1.3.6.1.4.1.476.1.1.1.1.3.6 | TablelcUpsInputTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1 | RowlcUpsInputEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1.1 | ColumnlcUpsInputLine | read-only | optional | The input Line. |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1.2 | ColumnlcUpsInputVoltage | read-only | optional | The input voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1.3 | ColumnlcUpsInputCurrent | read-only | optional | The input current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1.4 | ColumnlcUpsInputVA | read-only | optional | The input volt-amps. |
| 1.3.6.1.4.1.476.1.1.1.1.4 | NodelcUpsOutput | |||
| 1.3.6.1.4.1.476.1.1.1.1.4.1 | ScalarlcUpsOutputFrequency | read-only | optional | The current output frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.4.2 | ScalarlcUpsOutputLoad | read-only | optional | The current output load percentage. |
| 1.3.6.1.4.1.476.1.1.1.1.4.3 | ScalarlcUpsOutputNumLines | read-only | optional | The number of output lines utilized in this device. This entry indicates the number of rows in the output table. |
| 1.3.6.1.4.1.476.1.1.1.1.4.4 | TablelcUpsOutputTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1 | RowlcUpsOutputEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.1 | ColumnlcUpsOutputLine | read-only | optional | The output Line. |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.2 | ColumnlcUpsOutputVoltage | read-only | optional | The output voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.3 | ColumnlcUpsOutputCurrent | read-only | optional | The output current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.4 | ColumnlcUpsOutputVA | read-only | optional | The output volt-amps. |
| 1.3.6.1.4.1.476.1.1.1.1.4.5 | ScalarlcUpsOutputWatts | read-only | optional | The output power in watts. |
| 1.3.6.1.4.1.476.1.1.1.1.5 | NodelcUpsInverter | |||
| 1.3.6.1.4.1.476.1.1.1.1.5.1 | ScalarlcUpsInverterStatus | read-only | optional | The state of the inverter. Unknown is returned if the state can not be determined. |
| 1.3.6.1.4.1.476.1.1.1.1.5.2 | ScalarlcUpsInverterTemp | read-only | optional | The temperature of the inverter. (Unit of measure: degree, Centigrade) |
| 1.3.6.1.4.1.476.1.1.1.1.6 | NodelcUpsAlarm | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.1 | ScalarlcUpsAlarms | read-only | optional | The current number of alarm conditions. |
| 1.3.6.1.4.1.476.1.1.1.1.6.2 | TablelcUpsAlarmTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1 | RowlcUpsAlarmEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1.1 | ColumnlcUpsAlarmId | read-only | optional | A unique identifier for an alarm condition. This value must remain constant between agent initializations. |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1.2 | ColumnlcUpsAlarmDescr | read-only | optional | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1.3 | ColumnlcUpsAlarmTime | read-only | optional | The value of sysUpTime when the alarm condition occured. |
| 1.3.6.1.4.1.476.1.1.1.1.6.3 | NodelcUpsAlarmConditions | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.1 | NodelcUpsAlarmLowBatteryWarning | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.2 | NodelcUpsAlarmLowBatteryShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.3 | NodelcUpsAlarmUtilFailed | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.4 | NodelcUpsAlarmOverTempWarning | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.5 | NodelcUpsAlarmOverTempShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.6 | NodelcUpsAlarmOutputOverloadWarning | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.7 | NodelcUpsAlarmOutputOverloadShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.8 | NodelcUpsAlarmInputOverVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.9 | NodelcUpsAlarmBatteryBad | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.10 | NodelcUpsAlarmOnBattery | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.11 | NodelcUpsAlarmStopNoticeIssued | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.12 | NodelcUpsAlarmUpsOff | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.13 | NodelcUpsAlarmInputFreqError | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.15 | NodelcUpsAlarmOutputUnderVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.16 | NodelcUpsAlarmOutputOverVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.17 | NodelcUpsBadBypassPower | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.18 | NodelcUpsAlarmDCOverVoltageShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.23 | NodelcUpsAlarmHardwareShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.24 | NodelcUpsAlarmEmergencyXferToBypass | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.25 | NodelcUpsAlarmInverterFault | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.26 | NodelcUpsAlarmPhaseRotationError | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.28 | NodelcUpsAlarmFuseBlown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.29 | NodelcUpsAlarmAmbientOverTemp | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.30 | NodelcUpsAlarmEmergencyPowerOff | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.31 | NodelcUpsAlarmFanFailed | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.32 | NodelcUpsAlarmControlPowerFailed | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.33 | NodelcUpsAlarmReversePower | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.34 | NodelcUpsAlarmDCgroundFault | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.35 | NodelcUpsAlarmLoadOnBypass | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.37 | NodelcUpsAlarmBatteryCbOpen | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.38 | NodelcUpsAlarmInputCbOpen | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.39 | NodelcUpsAlarmOutputCbOpen | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.40 | NodelcUpsAlarmOutputFreqError | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.41 | NodelcUpsAlarmStaticSwUnable | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.42 | NodelcUpsAlarmManualResetXfer | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.43 | NodelcUpsAlarmAutoRexferPrimed | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.44 | NodelcUpsAlarmBattCycleBuffWarn | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.45 | NodelcUpsAlarmModuleSummary | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.46 | NodelcUpsLineCorrectionActive | |||
| 1.3.6.1.4.1.476.1.1.1.1.7 | NodelcUpsTest | |||
| 1.3.6.1.4.1.476.1.1.1.1.7.1 | ScalarlcUpsTestBattery | read-write | optional | Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, other… |
| 1.3.6.1.4.1.476.1.1.1.1.7.2 | ScalarlcUpsTestBatteryStatus | read-only | optional | The status of the battery test. |
| 1.3.6.1.4.1.476.1.1.1.1.7.3 | ScalarlcUpsTestDiag | read-write | optional | Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress… |
| 1.3.6.1.4.1.476.1.1.1.1.7.4 | ScalarlcUpsTestDiagStatus | read-only | optional | The status of the diagnostics test. |
| 1.3.6.1.4.1.476.1.1.1.1.8 | NodelcUpsControl | |||
| 1.3.6.1.4.1.476.1.1.1.1.8.1 | ScalarlcUpsControlOutputOffDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seco… |
| 1.3.6.1.4.1.476.1.1.1.1.8.2 | ScalarlcUpsControlOutputOnDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of secon… |
| 1.3.6.1.4.1.476.1.1.1.1.8.3 | ScalarlcUpsControlOutputOffTrapDelay | read-write | optional | When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will… |
| 1.3.6.1.4.1.476.1.1.1.1.8.4 | ScalarlcUpsControlOutputOnTrapDelay | read-write | optional | When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will b… |
| 1.3.6.1.4.1.476.1.1.1.1.8.5 | ScalarlcUpsControlUnixShutdownDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of sec… |
| 1.3.6.1.4.1.476.1.1.1.1.8.6 | ScalarlcUpsControlUnixShutdownTrapDelay | read-write | optional | When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this objec… |
| 1.3.6.1.4.1.476.1.1.1.1.8.7 | ScalarlcUpsControlCancelCommands | read-write | optional | Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUp… |
| 1.3.6.1.4.1.476.1.1.1.1.8.8 | ScalarlcUpsControlRebootAgentDelay | read-write | optional | Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. |
| 1.3.6.1.4.1.476.1.1.1.1.9 | NodelcUpsNominal | |||
| 1.3.6.1.4.1.476.1.1.1.1.9.1 | ScalarlcUpsNominalOutputVoltage | read-write | optional | The nominal output voltage. (Unit of measure: volt) |
| 1.3.6.1.4.1.476.1.1.1.1.9.2 | ScalarlcUpsNominalInputVoltage | read-write | optional | The nominal input voltage. (Unit of measure: volt) |
| 1.3.6.1.4.1.476.1.1.1.1.9.3 | ScalarlcUpsNominalOutputVA | read-write | optional | The nominal Volt-Amp rating. |
| 1.3.6.1.4.1.476.1.1.1.1.9.4 | ScalarlcUpsNominalOutputWatts | read-write | optional | The nominal power rating. (Unit of measure: watt) |
| 1.3.6.1.4.1.476.1.1.1.1.9.5 | ScalarlcUpsNominalOutputFreq | read-write | optional | The nominal output frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.9.6 | ScalarlcUpsNominalInputFreq | read-write | optional | The nominal input frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.9.7 | ScalarlcUpsNominalOutputVaRating | read-write | optional | The nominal Volt-Amp rating. |
| 1.3.6.1.4.1.476.1.1.1.1.9.8 | ScalarlcUpsNominalOutputWattsRating | read-write | optional | The nominal power rating. (Unit of measure: watt) |
| 1.3.6.1.4.1.476.1.1.1.1.11 | NodelcUpsTraps | |||
| 1.3.6.1.4.1.476.1.1.1.1.11.1 | NodelcUpsOverloadWarningTrap | An lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.2 | NodelcUpsOverloadShutdownTrap | An lcUpsOverloadShutdownTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity and has shut… | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.3 | NodelcUpsOnBatteryTrap | An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.4 | NodelcUpsLowBatteryWarningTrap | An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.5 | NodelcUpsLowBatteryShutdownTrap | An lcUpsLowBatteryShutdownTrap signifies that the UPS has shut off the output due to a Low Battery state. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.6 | NodelcUpsUtilPowerFailedTrap | An lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.7 | NodelcUpsUtilPowerRestoredTrap | An lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.8 | NodelcUpsInputOverVoltageTrap | An lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.9 | NodelcUpsOverTempWarningTrap | An lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.10 | NodelcUpsOverTempShutdownTrap | An lcUpsOverTempShutdownTrap signifies that the UPS has detected a excessive temperature condition and shut off the output. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.11 | NodelcUpsAlarmTrap | An Alarm condition has occurred and is being reported in the lcUpsAlarmTable. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.12 | NodelcUpsOutputOffTrap | An lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.13 | NodelcUpsOutputOffWarningTrap | An lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.14 | NodelcUpsOutputOnTrap | An lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.15 | NodelcUpsOutputOnWarningTrap | An lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.16 | NodelcUpsUnixShutdownTrap | An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.17 | NodelcUpsUnixShutdownWarningTrap | An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.18 | NodelcUpsReceptOffTrap | An lcUpsReceptOffTrap is sent when the UPS turns an output receptacle off. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.19 | NodelcUpsReceptOffWarningTrap | An lcUpsReceptOffWarningTrap is sent when the lcUpsSwitchedReceptOffDelay reaches the value of lcUpsSwitchedReceptOffTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.20 | NodelcUpsReceptOnTrap | An lcUpsReceptOnTrap is sent when the UPS turns an output receptacle on. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.21 | NodelcUpsReceptOnWarningTrap | An lcUpsReceptOnWarningTrap is sent when the lcUpsSwitchedReceptOnDelay reaches the value of lcUpsSwitchedReceptOnTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.22 | NodelcUpsInputFreqErrorTrap | An ldUpsInputFreqErrorTrap signifies that the UPS has detected that input frequency is outside tolerable variance. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.23 | NodelcUpsDCOverVoltageShutdownTrap | An lcUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the tolarable level. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.24 | NodelcUpsOutputOverVoltageTrap | An lcUpsOutputOverVoltageTrap signifies that the UPS has detected that the output voltage is too high. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.25 | NodelcUpsFuseBlownTrap | An lcUpsFuseBlownTrap is sent when the UPS's rectifier or DC capacitor fuse has failed. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.26 | NodelcUpsEmergencyPowerOffTrap | An lcUpsEmergencyPowerOffTrap signifies that the UPS has shut off output due to an emergency condition. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.27 | NodelcUpsControlPowerFailureTrap | An lcUpsControlPowerFailureTrap signifies a failure in the secondary control power. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.28 | NodelcUpsReversePowerTrap | An lcUpsReversePowerTrap signifies that output has been shut off due to a reverse power flow condition. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.29 | NodelcUpsPhaseRotationErrorTrap | An lcUpsPhaseRotationErrorTrap signifies a phase-rotation error in the bypass power. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.30 | NodelcUpsLoadOnBypassTrap | An lcUpsLoadOnBypassTrap signifies that the load has been transferred to bypass power. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.31 | NodelcUpsEmergencyXferToBypassTrap | An lcUpsEmergencyXferToBypassTrap signifies that the UPS has automatically tranferred the load to bypass power. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.34 | NodelcUpsInverterFaultTrap | An lcUpsInverterFaultTrap signifies that the UPS detected a problem with the Inverter. | ||
| 1.3.6.1.4.1.476.1.1.1.1.12 | NodelcUpsSwitchedReceptacles | |||
| 1.3.6.1.4.1.476.1.1.1.1.12.1 | ScalarlcUpsSwitchedReceptMaxNum | read-only | optional | The maximum number of switched receptacles supported by the Ups. |
| 1.3.6.1.4.1.476.1.1.1.1.12.2 | TablelcUpsSwitchedReceptTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1 | RowlcUpsSwitchedReceptEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.1 | ColumnlcUpsSwitchedReceptIndex | read-only | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2 | ColumnlcUpsSwitchedReceptOnDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to turn on a receptacle after the indicated number of seconds. The agent counts down the number of sec… |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.3 | ColumnlcUpsSwitchedReceptOnTrapDelay | read-write | optional | When 'lcUpsSwitchedReceptOnDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOnWarningTrap will be produced and this object will … |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.4 | ColumnlcUpsSwitchedReceptOffDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to turn off a receptacle after the indicated number of seconds. The agent counts down the number of se… |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.5 | ColumnlcUpsSwitchedReceptOffTrapDelay | read-write | optional | When 'lcUpsSwitchedReceptOffDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOffWarningTrap will be produced and this object wil… |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.6 | ColumnlcUpsSwitchedReceptStatus | read-only | optional | The status of the device receptacle. Note that some devices may support Switched of device receptacles as a group only (by using lcUpsSwitchedOutputOffDelay an… |
| 1.3.6.1.4.1.476.1.1.1.1.12.2.1.7 | ColumnlcUpsSwitchedReceptLabel | read-write | optional | A user-defined text string associated with a switched receptacle. This may be used to describe the load powered from the receptacle. The text string is stored … |
| 1.3.6.1.4.1.476.1.1.1.1.13 | NodelcUpsBypass | |||
| 1.3.6.1.4.1.476.1.1.1.1.13.1 | ScalarlcUpsOnBypass | read-only | optional | Indicates that the UPS is currently on bypass. |
| 1.3.6.1.4.1.476.1.1.1.1.13.2 | ScalarlcUpsBypassFrequency | read-only | optional | The current bypass frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.13.3 | ScalarlcUpsBypassNumLines | read-only | optional | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.476.1.1.1.1.13.4 | TablelcUpsBypassTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1 | RowlcUpsBypassEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1.1 | ColumnlcUpsBypassLine | read-only | optional | The bypass Line. |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1.2 | ColumnlcUpsBypassVoltage | read-only | optional | The bypass voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1.3 | ColumnlcUpsBypassCurrent | read-only | optional | The bypass current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.1.14 | NodelcUpsConfig | |||
| 1.3.6.1.4.1.476.1.1.1.1.14.1 | ScalarlcUpsConfigType | read-only | optional | Indicates the UPS topology. |
| 1.3.6.1.4.1.476.1.1.1.1.14.2 | ScalarlcUpsConfigBypassInstalled | read-only | optional | Indicates if a bypass is installed in the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.14.3 | ScalarlcUpsConfigModuleCount | read-only | optional | A number identifying how many multi-module UPS are connected to the System Control Cabinet. |
| 1.3.6.1.4.1.476.1.1.1.1.14.4 | ScalarlcUpsConfigCurrentModule | read-write | optional | A number identifying which module of a multi-module UPS is currently being monitored. |
| 1.3.6.1.4.1.476.1.1.1.1.14.5 | ScalarlcUpsConfigAudibleStatus | read-write | optional | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this … |
| 1.3.6.1.4.1.476.1.1.1.1.14.6 | ScalarlcUpsConfigLowBattTime | read-write | optional | The value of lcUpsBatTimeRemaining at which a lowBatteryWarning condition is declared. (Unit of measure: Minute) |
| 1.3.6.1.4.1.476.1.1.1.1.14.7 | ScalarlcUpsConfigAutoRestart | read-write | optional | Setting this object will start the output after the indicated number of ticks (1 tick = 10 seconds), including starting the UPS, if necessary. Setting this obj… |
| 1.3.6.1.4.1.476.1.1.1.2 | NodeluUPStationS | |||
| 1.3.6.1.4.1.476.1.1.1.2.1 | NodelsUpsIdent | |||
| 1.3.6.1.4.1.476.1.1.1.2.1.1 | ScalarlsUpsIdentFirmwareVersion | read-only | optional | The firmware revision level of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.2.6 | NodelsUpsAlarm | |||
| 1.3.6.1.4.1.476.1.1.1.2.6.1 | NodelsUpsAlarmConditions | |||
| 1.3.6.1.4.1.476.1.1.1.2.6.1.1 | NodelsUpsAlarmCheckAirFilter | |||
| 1.3.6.1.4.1.476.1.1.1.2.11 | NodelsUpsTraps | |||
| 1.3.6.1.4.1.476.1.1.1.2.11.1 | NodelsUpsCheckAirFilterTrap | An lsUpsCheckAirFilterTrap signifies that the programmed time interval for checking the air filter has passed and it is time to check the air filter. | ||
| 1.3.6.1.4.1.476.1.1.1.2.12 | NodelsUpsConfig | |||
| 1.3.6.1.4.1.476.1.1.1.2.12.1 | ScalarlsUpsConfigBypassInstalled | read-only | optional | Indicates if a bypass is installed in the UPS. |
| 1.3.6.1.4.1.476.1.1.1.2.13 | NodelsUpsBypass | |||
| 1.3.6.1.4.1.476.1.1.1.2.13.1 | ScalarlsUpsOnBypass | read-only | optional | Indicates that the UPS is currently on bypass. |
| 1.3.6.1.4.1.476.1.1.1.2.13.2 | ScalarlsUpsBypassFrequency | read-only | optional | The current bypass frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.2.13.3 | ScalarlsUpsBypassNumLines | read-only | optional | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.476.1.1.1.2.13.4 | TablelsUpsBypassTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.2.13.4.1 | RowlsUpsBypassEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.2.13.4.1.1 | ColumnlsUpsBypassLine | read-only | optional | The bypass Line. |
| 1.3.6.1.4.1.476.1.1.1.2.13.4.1.2 | ColumnlsUpsBypassVoltage | read-only | optional | The bypass voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.2.13.4.1.3 | ColumnlsUpsBypassCurrent | read-only | optional | The bypass current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.3 | NodeluUPStationD | |||
| 1.3.6.1.4.1.476.1.1.1.3.3 | NodeldUpsInput | |||
| 1.3.6.1.4.1.476.1.1.1.3.3.1 | ScalarldUpsInputMaxVoltsSinceLastPoll | read-only | optional | The maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this obje… |
| 1.3.6.1.4.1.476.1.1.1.3.3.2 | ScalarldUpsInputMinVoltsSinceLastPoll | read-only | optional | The minimum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this obje… |
| 1.3.6.1.4.1.476.1.1.1.3.4 | NodeldUpsOutput | |||
| 1.3.6.1.4.1.476.1.1.1.3.4.1 | ScalarldUpsOutputMaxVoltsSinceLastPoll | read-only | optional | The maximum output voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this obj… |
| 1.3.6.1.4.1.476.1.1.1.3.4.2 | ScalarldUpsOutputMinVoltsSinceLastPoll | read-only | optional | The minimum output voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this obj… |
| 1.3.6.1.4.1.476.1.1.1.3.6 | NodeldUpsAlarm | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1 | NodeldUpsAlarmConditions | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.1 | NodeldUpsAlarmDCOverVoltageShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.2 | NodeldUpsAlarmOutputShortShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.3 | NodeldUpsAlarmLNReversedShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.4 | NodeldUpsAlarmImminentShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.5 | NodeldUpsAlarmInputFreqError | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.6 | NodeldUpsAlarmBoostOn | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.7 | NodeldUpsAlarmReplaceBattery | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.8 | NodeldUpsAlarmOutputOverVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.9 | NodeldUpsAlarmOutputUnderVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.3.6.1.10 | NodeldUpsAlarmChargerFailed | |||
| 1.3.6.1.4.1.476.1.1.1.3.11 | NodeldUpsTraps | |||
| 1.3.6.1.4.1.476.1.1.1.3.11.1 | NodeldUpsDCOverVoltageShutdownTrap | An ldUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the tolarable level. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.2 | NodeldUpsOutputShortShutdownTrap | An ldUpsOutputShortShutdownTrap signifies that the UPS has detected a short circuit across the output. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.3 | NodeldUpsLNReversedShutdownTrap | An ldUpsLNReversedShutdownTrap signifies that the UPS has detected that Line and Neutral have been reversed. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.4 | NodeldUpsImminentShutdownTrap | An ldUpsImminentShutdownTrap signifies that the UPS is about to turn off output power. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.5 | NodeldUpsInputFreqErrorTrap | An ldUpsInputFreqErrorTrap signifies that the UPS has detected that input frequency is outside tolerable variance. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.6 | NodeldUpsOutputOverVoltageTrap | An ldUpsOutputOverVoltageTrap signifies that the UPS has detected that the output voltage is too high. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.7 | NodeldUpsOutputUnderVoltageTrap | An ldUpsOutputUnderVoltageTrap signifies that the UPS has detected that the output voltage is too low. | ||
| 1.3.6.1.4.1.476.1.1.1.3.11.8 | NodeldUpsChargerFailedTrap | An ldUpsChargerFailedTrap signifies that the UPS has detected that the battery charger has failed. | ||
| 1.3.6.1.4.1.476.1.1.1.4 | NodeluUPStationG | |||
| 1.3.6.1.4.1.476.1.1.1.4.6 | NodelgUpsAlarm | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1 | NodelgUpsAlarmConditions | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1.1 | NodelgUpsAlarmDCOverVoltageShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1.2 | NodelgUpsAlarmOutputShortShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1.3 | NodelgUpsAlarmLNReversedShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1.4 | NodelgUpsAlarmRemoteShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1.5 | NodelgUpsAlarmInputUVOnStartup | |||
| 1.3.6.1.4.1.476.1.1.1.4.6.1.6 | NodelgUpsAlarmPFCFailedOnStartup | |||
| 1.3.6.1.4.1.476.1.1.1.4.11 | NodelgUpsTraps | |||
| 1.3.6.1.4.1.476.1.1.1.4.11.1 | NodelgUpsDCOverVoltageShutdownTrap | An lgUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the nominal level. | ||
| 1.3.6.1.4.1.476.1.1.1.4.11.2 | NodelgUpsOutputShortShutdownTrap | An lgUpsOutputShortShutdownTrap signifies that the UPS has detected a short circuit across the output. | ||
| 1.3.6.1.4.1.476.1.1.1.4.11.3 | NodelgUpsLNReversedShutdownTrap | An lgUpsLNReversedShutdownTrap signifies that the UPS has detected that Line and Neutral have been reversed. | ||
| 1.3.6.1.4.1.476.1.1.1.4.11.4 | NodelgUpsInputUVOnStartupTrap | An lgUpsInputUVOnStartupTrap signifies that the UPS detected a low voltage condition upon system startup. | ||
| 1.3.6.1.4.1.476.1.1.1.5 | NodeluSeries300 | |||
| 1.3.6.1.4.1.476.1.1.1.6 | NodeluExternal | |||
| 1.3.6.1.4.1.476.1.1.1.7 | NodeluUPStationS3 | |||
| 1.3.6.1.4.1.476.1.1.1.8 | NodeluSeries200 | |||
| 1.3.6.1.4.1.476.1.1.1.8.3 | NodeluSeries200Input | |||
| 1.3.6.1.4.1.476.1.1.1.8.3.1 | ScalarluSeries200InputMaxVoltsSinceLastPoll | read-only | optional | The maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this obje… |
| 1.3.6.1.4.1.476.1.1.1.8.3.2 | ScalarluSeries200InputMinVoltsSinceLastPoll | read-only | optional | The minimum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this obje… |
| 1.3.6.1.4.1.476.1.1.1.8.6 | NodeluSeries200Alarm | |||
| 1.3.6.1.4.1.476.1.1.1.8.6.1 | NodeluSeries200AlarmConditions | |||
| 1.3.6.1.4.1.476.1.1.1.8.6.1.1 | NodeluSeries200AlarmInputFreqError | |||
| 1.3.6.1.4.1.476.1.1.1.8.12 | NodeluSeries200Config | |||
| 1.3.6.1.4.1.476.1.1.1.8.12.1 | ScalarluSeries200ConfigBypassInstalled | read-only | optional | Indicates if a bypass is installed in the UPS. |
| 1.3.6.1.4.1.476.1.1.1.8.12.2 | ScalarluSeries200ConfigFrequencyChangerModel | read-only | optional | Indicates whether this AP200 model is a frequency changer model. |
| 1.3.6.1.4.1.476.1.1.1.8.13 | NodeluSeries200Bypass | |||
| 1.3.6.1.4.1.476.1.1.1.8.13.1 | ScalarluSeries200OnBypass | read-only | optional | Indicates that the UPS is currently on bypass. |
| 1.3.6.1.4.1.476.1.1.1.10 | NodeluSeries4300 | |||
| 1.3.6.1.4.1.476.1.1.1.10.1 | Nodels43cUpsIdent | |||
| 1.3.6.1.4.1.476.1.1.1.10.1.1 | Scalarls43cUpsIdentFirmwareVersion | read-only | optional | The firmware revision level of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.10.12 | Nodels43cUpsConfig | |||
| 1.3.6.1.4.1.476.1.1.1.10.12.1 | Scalarls43cUpsConfigBypassInstalled | read-only | optional | Indicates if a bypass is installed in the UPS. |
| 1.3.6.1.4.1.476.1.1.1.10.13 | Nodels43cUpsBypass | |||
| 1.3.6.1.4.1.476.1.1.1.10.13.1 | Scalarls43cUpsOnBypass | read-only | optional | Indicates that the UPS is currently on bypass. |
| 1.3.6.1.4.1.476.1.1.1.10.13.2 | Scalarls43cUpsBypassFrequency | read-only | optional | The current bypass frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.10.13.3 | Scalarls43cUpsBypassNumLines | read-only | optional | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.476.1.1.1.10.13.4 | Tablels43cUpsBypassTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.10.13.4.1 | Rowls43cUpsBypassEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.10.13.4.1.1 | Columnls43cUpsBypassLine | read-only | optional | The bypass Line. |
| 1.3.6.1.4.1.476.1.1.1.10.13.4.1.2 | Columnls43cUpsBypassVoltage | read-only | optional | The bypass voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.10.13.4.1.3 | Columnls43cUpsBypassCurrent | read-only | optional | The bypass current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.11 | NodeluUpsModule | |||
| 1.3.6.1.4.1.476.1.1.1.12 | NodeluSystemCabinet | |||
| 1.3.6.1.4.1.476.1.1.1.14 | NodeluUPStationGxt | |||
| 1.3.6.1.4.1.476.1.1.1.15 | NodeluPowerSure | |||
| 1.3.6.1.4.1.476.1.1.2 | NodeluExperimental | |||
| 1.3.6.1.4.1.476.1.1.3 | NodeluPrivate |