MIB Viewer

LIEBERT-UPSTATION-G-UPS-MIB

103 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.476Nodeemerson
1.3.6.1.4.1.476.1NodeliebertCorp
1.3.6.1.4.1.476.1.1NodeliebertUps
1.3.6.1.4.1.476.1.1.1NodeluExtensions
1.3.6.1.4.1.476.1.1.1.1NodeluCore
1.3.6.1.4.1.476.1.1.1.1.1NodelcUpsIdent
1.3.6.1.4.1.476.1.1.1.1.1.1ScalarlcUpsIdentManufacturerread-onlyoptionalThe UPS manufacturer.
1.3.6.1.4.1.476.1.1.1.1.1.2ScalarlcUpsIdentModelread-writeoptionalThe UPS Model designation.
1.3.6.1.4.1.476.1.1.1.1.1.3ScalarlcUpsIdentSoftwareVersionread-onlyoptionalThe UPS SNMP Agent software version.
1.3.6.1.4.1.476.1.1.1.1.1.4ScalarlcUpsIdentSpecificread-onlyoptionalA reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this in…
1.3.6.1.4.1.476.1.1.1.1.2NodelcUpsBattery
1.3.6.1.4.1.476.1.1.1.1.2.1ScalarlcUpsBatTimeRemainingread-onlyoptionalThe estimated time to depletion of battery charge. (Unit of measure: Minute)
1.3.6.1.4.1.476.1.1.1.1.2.2ScalarlcUpsBatTemperatureread-onlyoptionalThe battery temperature. (Unit of measure: Degree, Centigrade)
1.3.6.1.4.1.476.1.1.1.1.2.3ScalarlcUpsBatVoltageread-onlyoptionalThe current battery voltage. (Unit of measure: volt)
1.3.6.1.4.1.476.1.1.1.1.2.4ScalarlcUpsBatCurrentread-onlyoptionalThe current battery discharging/charging current. (Unit of measure: Amp)
1.3.6.1.4.1.476.1.1.1.1.2.6ScalarlcUpsBatCapacityread-onlyoptionalThe current battery capacity in percentage of total available.
1.3.6.1.4.1.476.1.1.1.1.3NodelcUpsInput
1.3.6.1.4.1.476.1.1.1.1.3.1ScalarlcUpsInputFrequencyread-onlyoptionalThe current input frequency. (Unit of measure: Hertz)
1.3.6.1.4.1.476.1.1.1.1.3.5ScalarlcUpsInputNumLinesread-onlyoptionalThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.4.1.476.1.1.1.1.3.6TablelcUpsInputTablenot-accessibleoptional
1.3.6.1.4.1.476.1.1.1.1.3.6.1RowlcUpsInputEntrynot-accessibleoptional
1.3.6.1.4.1.476.1.1.1.1.3.6.1.1ColumnlcUpsInputLineread-onlyoptionalThe input Line.
1.3.6.1.4.1.476.1.1.1.1.3.6.1.2ColumnlcUpsInputVoltageread-onlyoptionalThe input voltage. (Unit of measure: Volt)
1.3.6.1.4.1.476.1.1.1.1.3.6.1.3ColumnlcUpsInputCurrentread-onlyoptionalThe input current. (Unit of measure: Amp)
1.3.6.1.4.1.476.1.1.1.1.3.6.1.4ColumnlcUpsInputVAread-onlyoptionalThe input volt-amps.
1.3.6.1.4.1.476.1.1.1.1.4NodelcUpsOutput
1.3.6.1.4.1.476.1.1.1.1.4.1ScalarlcUpsOutputFrequencyread-onlyoptionalThe current output frequency. (Unit of measure: Hertz)
1.3.6.1.4.1.476.1.1.1.1.4.3ScalarlcUpsOutputNumLinesread-onlyoptionalThe number of output lines utilized in this device. This entry indicates the number of rows in the output table.
1.3.6.1.4.1.476.1.1.1.1.5NodelcUpsInverter
1.3.6.1.4.1.476.1.1.1.1.5.1ScalarlcUpsInverterStatusread-onlyoptionalThe state of the inverter. Unknown is returned if the state can not be determined.
1.3.6.1.4.1.476.1.1.1.1.5.2ScalarlcUpsInverterTempread-onlyoptionalThe temperature of the inverter. (Unit of measure: degree, Centigrade)
1.3.6.1.4.1.476.1.1.1.1.6NodelcUpsAlarm
1.3.6.1.4.1.476.1.1.1.1.6.1ScalarlcUpsAlarmsread-onlyoptionalThe current number of alarm conditions.
1.3.6.1.4.1.476.1.1.1.1.6.2TablelcUpsAlarmTablenot-accessibleoptional
1.3.6.1.4.1.476.1.1.1.1.6.2.1RowlcUpsAlarmEntrynot-accessibleoptional
1.3.6.1.4.1.476.1.1.1.1.6.2.1.1ColumnlcUpsAlarmIdread-onlyoptionalA unique identifier for an alarm condition. This value must remain constant between agent initializations.
1.3.6.1.4.1.476.1.1.1.1.6.2.1.2ColumnlcUpsAlarmDescrread-onlyoptionalA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.476.1.1.1.1.6.2.1.3ColumnlcUpsAlarmTimeread-onlyoptionalThe value of sysUpTime when the alarm condition occured.
1.3.6.1.4.1.476.1.1.1.1.6.3NodelcUpsAlarmConditions
1.3.6.1.4.1.476.1.1.1.1.6.3.1NodelcUpsAlarmLowBatteryWarning
1.3.6.1.4.1.476.1.1.1.1.6.3.2NodelcUpsAlarmLowBatteryShutdown
1.3.6.1.4.1.476.1.1.1.1.6.3.3NodelcUpsAlarmUtilFailed
1.3.6.1.4.1.476.1.1.1.1.6.3.4NodelcUpsAlarmOverTempWarning
1.3.6.1.4.1.476.1.1.1.1.6.3.5NodelcUpsAlarmOverTempShutdown
1.3.6.1.4.1.476.1.1.1.1.6.3.7NodelcUpsAlarmOutputOverloadShutdown
1.3.6.1.4.1.476.1.1.1.1.6.3.8NodelcUpsAlarmInputOverVoltage
1.3.6.1.4.1.476.1.1.1.1.6.3.9NodelcUpsAlarmBatteryBad
1.3.6.1.4.1.476.1.1.1.1.6.3.10NodelcUpsAlarmOnBattery
1.3.6.1.4.1.476.1.1.1.1.6.3.11NodelcUpsAlarmStopNoticeIssued
1.3.6.1.4.1.476.1.1.1.1.6.3.12NodelcUpsAlarmUpsOff
1.3.6.1.4.1.476.1.1.1.1.7NodelcUpsTest
1.3.6.1.4.1.476.1.1.1.1.7.1ScalarlcUpsTestBatteryread-writeoptionalSetting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, other…
1.3.6.1.4.1.476.1.1.1.1.7.2ScalarlcUpsTestBatteryStatusread-onlyoptionalThe status of the battery test.
1.3.6.1.4.1.476.1.1.1.1.7.3ScalarlcUpsTestDiagread-writeoptionalSetting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress…
1.3.6.1.4.1.476.1.1.1.1.7.4ScalarlcUpsTestDiagStatusread-onlyoptionalThe status of the diagnostics test.
1.3.6.1.4.1.476.1.1.1.1.8NodelcUpsControl
1.3.6.1.4.1.476.1.1.1.1.8.1ScalarlcUpsControlOutputOffDelayread-writeoptionalSetting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seco…
1.3.6.1.4.1.476.1.1.1.1.8.2ScalarlcUpsControlOutputOnDelayread-writeoptionalSetting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of secon…
1.3.6.1.4.1.476.1.1.1.1.8.3ScalarlcUpsControlOutputOffTrapDelayread-writeoptionalWhen 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will…
1.3.6.1.4.1.476.1.1.1.1.8.4ScalarlcUpsControlOutputOnTrapDelayread-writeoptionalWhen 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will b…
1.3.6.1.4.1.476.1.1.1.1.8.5ScalarlcUpsControlUnixShutdownDelayread-writeoptionalSetting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of sec…
1.3.6.1.4.1.476.1.1.1.1.8.6ScalarlcUpsControlUnixShutdownTrapDelayread-writeoptionalWhen 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this objec…
1.3.6.1.4.1.476.1.1.1.1.8.7ScalarlcUpsControlCancelCommandsread-writeoptionalSetting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUp…
1.3.6.1.4.1.476.1.1.1.1.8.8ScalarlcUpsControlRebootAgentDelayread-writeoptionalSetting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The c…
1.3.6.1.4.1.476.1.1.1.1.9NodelcUpsNominal
1.3.6.1.4.1.476.1.1.1.1.9.1ScalarlcUpsNominalOutputVoltageread-writeoptionalThe nominal output voltage. (Unit of measure: volt)
1.3.6.1.4.1.476.1.1.1.1.9.2ScalarlcUpsNominalInputVoltageread-writeoptionalThe nominal input voltage. (Unit of measure: volt)
1.3.6.1.4.1.476.1.1.1.1.9.3ScalarlcUpsNominalOutputVAread-writeoptionalThe nominal Volt-Amp rating.
1.3.6.1.4.1.476.1.1.1.1.9.5ScalarlcUpsNominalOutputFreqread-writeoptionalThe nominal output frequency. (Unit of measure: Hertz)
1.3.6.1.4.1.476.1.1.1.1.9.6ScalarlcUpsNominalInputFreqread-writeoptionalThe nominal input frequency. (Unit of measure: Hertz)
1.3.6.1.4.1.476.1.1.1.1.11NodelcUpsTraps
1.3.6.1.4.1.476.1.1.1.1.11.2NodelcUpsOverloadShutdownTrapAn lcUpsOverloadShutdownTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity and has shut…
1.3.6.1.4.1.476.1.1.1.1.11.3NodelcUpsOnBatteryTrapAn lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power.
1.3.6.1.4.1.476.1.1.1.1.11.4NodelcUpsLowBatteryWarningTrapAn lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state.
1.3.6.1.4.1.476.1.1.1.1.11.5NodelcUpsLowBatteryShutdownTrapAn lcUpsLowBatteryShutdownTrap signifies that the UPS has shut off the output due to a Low Battery state.
1.3.6.1.4.1.476.1.1.1.1.11.6NodelcUpsUtilPowerFailedTrapAn lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost.
1.3.6.1.4.1.476.1.1.1.1.11.7NodelcUpsUtilPowerRestoredTrapAn lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS.
1.3.6.1.4.1.476.1.1.1.1.11.8NodelcUpsInputOverVoltageTrapAn lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition.
1.3.6.1.4.1.476.1.1.1.1.11.9NodelcUpsOverTempWarningTrapAn lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition.
1.3.6.1.4.1.476.1.1.1.1.11.10NodelcUpsOverTempShutdownTrapAn lcUpsOverTempShutdownTrap signifies that the UPS has detected a excessive temperature condition and shut off the output.
1.3.6.1.4.1.476.1.1.1.1.11.11NodelcUpsAlarmTrapAn Alarm condition has occurred and is being reported in the lcUpsAlarmTable.
1.3.6.1.4.1.476.1.1.1.1.11.12NodelcUpsOutputOffTrapAn lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay.
1.3.6.1.4.1.476.1.1.1.1.11.13NodelcUpsOutputOffWarningTrapAn lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay.
1.3.6.1.4.1.476.1.1.1.1.11.14NodelcUpsOutputOnTrapAn lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay.
1.3.6.1.4.1.476.1.1.1.1.11.15NodelcUpsOutputOnWarningTrapAn lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay.
1.3.6.1.4.1.476.1.1.1.1.11.16NodelcUpsUnixShutdownTrapAn lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown.
1.3.6.1.4.1.476.1.1.1.1.11.17NodelcUpsUnixShutdownWarningTrapAn lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay.
1.3.6.1.4.1.476.1.1.1.4NodeluUPStationG
1.3.6.1.4.1.476.1.1.1.4.6NodelgUpsAlarm
1.3.6.1.4.1.476.1.1.1.4.6.1NodelgUpsAlarmConditions
1.3.6.1.4.1.476.1.1.1.4.6.1.1NodelgUpsAlarmDCOverVoltageShutdown
1.3.6.1.4.1.476.1.1.1.4.6.1.2NodelgUpsAlarmOutputShortShutdown
1.3.6.1.4.1.476.1.1.1.4.6.1.3NodelgUpsAlarmLNReversedShutdown
1.3.6.1.4.1.476.1.1.1.4.6.1.4NodelgUpsAlarmRemoteShutdown
1.3.6.1.4.1.476.1.1.1.4.6.1.5NodelgUpsAlarmInputUVOnStartup
1.3.6.1.4.1.476.1.1.1.4.6.1.6NodelgUpsAlarmPFCFailedOnStartup
1.3.6.1.4.1.476.1.1.1.4.11NodelgUpsTraps
1.3.6.1.4.1.476.1.1.1.4.11.1NodelgUpsDCOverVoltageShutdownTrapAn lgUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the nominal level.
1.3.6.1.4.1.476.1.1.1.4.11.2NodelgUpsOutputShortShutdownTrapAn lgUpsOutputShortShutdownTrap signifies that the UPS has detected a short circuit across the output.
1.3.6.1.4.1.476.1.1.1.4.11.3NodelgUpsLNReversedShutdownTrapAn lgUpsLNReversedShutdownTrap signifies that the UPS has detected that Line and Neutral have been reversed.
1.3.6.1.4.1.476.1.1.1.4.11.4NodelgUpsInputUVOnStartupTrapAn lgUpsInputUVOnStartupTrap signifies that the UPS detected a low voltage condition upon system startup.
1.3.6.1.4.1.476.1.1.2NodeluExperimental
1.3.6.1.4.1.476.1.1.3NodeluPrivate