NETBOTZ-PRD-BOT-MIB
229 objects
No module-level DESCRIPTION found.
Imported Objects
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.5528.30.10.1 | NodenetBotz-prd-bot-low-trap | Netbotz Low Trap. This trap indicates that a lower limit has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.10.1 | ScalarnetBotz-prd-bot-temp | read-only | mandatory | The reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.2 | NodenetBotz-prd-bot-high-trap | Netbotz High Trap. This trap indicates that an upper limit has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.10.2 | ScalarnetBotz-prd-bot-humidity | read-only | mandatory | The reading of the humidity probe, in percent. |
| 1.3.6.1.4.1.5528.30.10.3 | ScalarnetBotz-prd-bot-airflow | read-only | mandatory | The reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity. |
| 1.3.6.1.4.1.5528.30.10.3 | NodenetBotz-prd-bot-trap-clear | Netbotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.10.4 | ScalarnetBotz-prd-bot-audio | read-only | mandatory | The reading of the audio alarm probe on/off. |
| 1.3.6.1.4.1.5528.30.10.4 | NodenetBotz-prd-bot-offline-trap | Netbotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline. | ||
| 1.3.6.1.4.1.5528.30.10.5 | ScalarnetBotz-prd-bot-doorajar | read-only | mandatory | The reading of the door switch probe open(0) or closed(1). |
| 1.3.6.1.4.1.5528.30.10.5 | NodenetBotz-prd-bot-online-trap | Netbotz Device Online Trap. This trap indicates that a device or function has been determined to be online. | ||
| 1.3.6.1.4.1.5528.30.10.6 | ScalarnetBotz-prd-bot-temp-min | read-write | mandatory | The temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.7 | ScalarnetBotz-prd-bot-temp-max | read-write | mandatory | The temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.8 | ScalarnetBotz-prd-bot-humidity-min | read-write | mandatory | The humidity probe minimum, from 10 to 90 percent. |
| 1.3.6.1.4.1.5528.30.10.9 | ScalarnetBotz-prd-bot-humidity-max | read-write | mandatory | The humidity probe maximum, from 10 to 90 percent. |
| 1.3.6.1.4.1.5528.30.10.10 | ScalarnetBotz-prd-bot-airflow-mins | read-write | mandatory | Minutes without airflow before alarm set. |
| 1.3.6.1.4.1.5528.30.10.11 | ScalarnetBotz-prd-bot-audio-secs | read-write | mandatory | Seconds of alarm audio before alarm set. |
| 1.3.6.1.4.1.5528.30.10.12 | ScalarnetBotz-prd-bot-temp-enabled | read-write | mandatory | Temperature probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.13 | ScalarnetBotz-prd-bot-hum-enabled | read-write | mandatory | Humidity probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.14 | ScalarnetBotz-prd-bot-air-enabled | read-write | mandatory | Airflow probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.15 | ScalarnetBotz-prd-bot-audio-enabled | read-write | mandatory | Audio probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.16 | ScalarnetBotz-prd-bot-switch-state | read-write | mandatory | Switch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to … |
| 1.3.6.1.4.1.5528.30.10.17 | ScalarnetBotz-prd-bot-switch-enabled | read-write | mandatory | Door switch enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.18 | ScalarnetBotz-prd-bot-audio-level | read-write | mandatory | Audio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent. |
| 1.3.6.1.4.1.5528.30.10.19 | ScalarnetBotz-prd-bot-doorpic-delay | read-write | mandatory | Number of seconds between door alert and first picture. |
| 1.3.6.1.4.1.5528.30.10.20 | ScalarnetBotz-prd-bot-trap-index | read-only | mandatory | The crawler ID of the last trap. |
| 1.3.6.1.4.1.5528.30.10.21 | ScalarnetBotz-prd-bot-trap-address | read-only | mandatory | The IP address of the last trap. |
| 1.3.6.1.4.1.5528.30.10.22 | ScalarnetBotz-prd-bot-trap-oid | read-only | mandatory | The object id of the last trap. |
| 1.3.6.1.4.1.5528.30.10.23 | ScalarnetBotz-prd-bot-trap-value | read-only | mandatory | The value of the last object trap. |
| 1.3.6.1.4.1.5528.30.10.24 | ScalarnetBotz-prd-bot-trap-date | read-only | mandatory | The date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970 |
| 1.3.6.1.4.1.5528.30.10.26 | ScalarnetBotz-prd-bot-refresh | read-write | mandatory | Rate of web page refresh, in seconds. This must be greater than 5 seconds. |
| 1.3.6.1.4.1.5528.30.10.27 | ScalarnetBotz-prd-bot-airflow-level | read-write | mandatory | Airflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 1… |
| 1.3.6.1.4.1.5528.30.10.28 | ScalarnetBotz-prd-bot-doorpic-count | read-write | mandatory | Number of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures. |
| 1.3.6.1.4.1.5528.30.10.29 | ScalarnetBotz-prd-bot-amps1 | read-only | mandatory | The reading of the first amperage probe, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.30 | ScalarnetBotz-prd-bot-amps1-enabled | read-write | mandatory | Amperage[1] probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.31 | ScalarnetBotz-prd-bot-amps1-min | read-write | mandatory | The amperage[1] probe minimum, from 0 to 30000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.32 | ScalarnetBotz-prd-bot-amps1-max | read-write | mandatory | The amperage[1] probe maximum, from 0 to 30000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.34 | ScalarnetBotz-prd-bot-amps2 | read-only | mandatory | The reading of the second amperage probe, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.35 | ScalarnetBotz-prd-bot-amps2-enabled | read-write | mandatory | Amperage[2] probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.36 | ScalarnetBotz-prd-bot-amps2-min | read-write | mandatory | The amperage[2] probe minimum, from 0 to 30000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.37 | ScalarnetBotz-prd-bot-amps2-max | read-write | mandatory | The amperage[2] probe maximum, from 0 to 30000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.39 | ScalarnetBotz-prd-bot-amps3 | read-only | mandatory | The reading of the third amperage probe, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.40 | ScalarnetBotz-prd-bot-amps3-enabled | read-write | mandatory | Amperage[3] probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.41 | ScalarnetBotz-prd-bot-amps3-min | read-write | mandatory | The amperage[3] probe minimum, from 0 to 30000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.42 | ScalarnetBotz-prd-bot-amps3-max | read-write | mandatory | The amperage[3] probe maximum, from 0 to 30000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.44 | ScalarnetBotz-prd-bot-amps-total | read-only | mandatory | The total of the readings of all amperage probes, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.45 | ScalarnetBotz-prd-bot-amps-total-enabled | read-write | mandatory | Total amperage alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.46 | ScalarnetBotz-prd-bot-amps-total-min | read-write | mandatory | The total amperage minimum, from 0 to 90000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.47 | ScalarnetBotz-prd-bot-amps-total-max | read-write | mandatory | The total amperage maximum, from 0 to 90000 milliamps. |
| 1.3.6.1.4.1.5528.30.10.48 | ScalarnetBotz-prd-bot-amps-total-support-enabled | read-write | mandatory | Total Amperage Support enabled(Y) or disabled(N). |
| 1.3.6.1.4.1.5528.30.10.49 | ScalarnetBotz-prd-bot-amps1-uV-per-10mA | read-write | mandatory | The scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based… |
| 1.3.6.1.4.1.5528.30.10.50 | ScalarnetBotz-prd-bot-amps2-uV-per-10mA | read-write | mandatory | The scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set base… |
| 1.3.6.1.4.1.5528.30.10.51 | ScalarnetBotz-prd-bot-amps3-uV-per-mA | read-write | mandatory | The scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based… |
| 1.3.6.1.4.1.5528.30.10.52 | ScalarnetBotz-prd-bot-amps1-max-range | read-write | mandatory | The maximum RMS milliamps measureable by the first Amp Detect. |
| 1.3.6.1.4.1.5528.30.10.53 | ScalarnetBotz-prd-bot-amps2-max-range | read-write | mandatory | The maximum RMS milliamps measureable by the second Amp Detect. |
| 1.3.6.1.4.1.5528.30.10.54 | ScalarnetBotz-prd-bot-amps3-max-range | read-write | mandatory | The maximum RMS milliamps measureable by the third Amp Detect. |
| 1.3.6.1.4.1.5528.30.10.55 | ScalarnetBotz-prd-bot-amps4 | read-only | mandatory | The reading of the fourth amperage probe, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.56 | ScalarnetBotz-prd-bot-amps4-enabled | read-write | mandatory | Amperage[4] probe alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.57 | ScalarnetBotz-prd-bot-amps4-min | read-write | mandatory | The amperage[4] probe minimum, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.58 | ScalarnetBotz-prd-bot-amps4-max | read-write | mandatory | The amperage[4] probe maximum, in milliamps. |
| 1.3.6.1.4.1.5528.30.10.60 | ScalarnetBotz-prd-bot-amps4-uV-per-10mA | read-write | mandatory | The scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set base… |
| 1.3.6.1.4.1.5528.30.10.61 | ScalarnetBotz-prd-bot-amps4-max-range | read-write | mandatory | The maximum RMS milliamps measureable by the fourth Amp Detect. |
| 1.3.6.1.4.1.5528.30.10.62 | ScalarnetBotz-prd-bot-ext-temp1 | read-only | mandatory | The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.63 | ScalarnetBotz-prd-bot-ext-temp2 | read-only | mandatory | The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.64 | ScalarnetBotz-prd-bot-ext-temp3 | read-only | mandatory | The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.65 | ScalarnetBotz-prd-bot-ext-temp4 | read-only | mandatory | The reading of the external temperature probe on port 4, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.66 | ScalarnetBotz-prd-bot-ext-temp1-enabled | read-write | mandatory | External temperature probe on port 1 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.67 | ScalarnetBotz-prd-bot-ext-temp1-min | read-write | mandatory | The external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.68 | ScalarnetBotz-prd-bot-ext-temp1-max | read-write | mandatory | The external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.69 | ScalarnetBotz-prd-bot-ext-temp2-enabled | read-write | mandatory | External temperature probe on port 2 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.70 | ScalarnetBotz-prd-bot-ext-temp2-min | read-write | mandatory | The external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.71 | ScalarnetBotz-prd-bot-ext-temp2-max | read-write | mandatory | The external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.72 | ScalarnetBotz-prd-bot-ext-temp3-enabled | read-write | mandatory | External temperature probe on port 3 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.73 | ScalarnetBotz-prd-bot-ext-temp3-min | read-write | mandatory | The external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.74 | ScalarnetBotz-prd-bot-ext-temp3-max | read-write | mandatory | The external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.75 | ScalarnetBotz-prd-bot-ext-temp4-enabled | read-write | mandatory | External temperature probe on port 4 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.76 | ScalarnetBotz-prd-bot-ext-temp4-min | read-write | mandatory | The external temperature probe on port 4 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.77 | ScalarnetBotz-prd-bot-ext-temp4-max | read-write | mandatory | The external temperature probe on port 4 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). |
| 1.3.6.1.4.1.5528.30.10.78 | ScalarnetBotz-prd-bot-ext-temp1-uV-per-degreeC | read-write | mandatory | The scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set… |
| 1.3.6.1.4.1.5528.30.10.79 | ScalarnetBotz-prd-bot-ext-temp1-uV-at-0-degreeC | read-write | mandatory | The offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the… |
| 1.3.6.1.4.1.5528.30.10.80 | ScalarnetBotz-prd-bot-ext-temp1-min-range | read-write | mandatory | The minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.81 | ScalarnetBotz-prd-bot-ext-temp1-max-range | read-write | mandatory | The maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.82 | ScalarnetBotz-prd-bot-ext-temp2-uV-per-degreeC | read-write | mandatory | The scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set… |
| 1.3.6.1.4.1.5528.30.10.83 | ScalarnetBotz-prd-bot-ext-temp2-uV-at-0-degreeC | read-write | mandatory | The offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the… |
| 1.3.6.1.4.1.5528.30.10.84 | ScalarnetBotz-prd-bot-ext-temp2-min-range | read-write | mandatory | The minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.85 | ScalarnetBotz-prd-bot-ext-temp2-max-range | read-write | mandatory | The maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.86 | ScalarnetBotz-prd-bot-ext-temp3-uV-per-degreeC | read-write | mandatory | The scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set… |
| 1.3.6.1.4.1.5528.30.10.87 | ScalarnetBotz-prd-bot-ext-temp3-uV-at-0-degreeC | read-write | mandatory | The offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the… |
| 1.3.6.1.4.1.5528.30.10.88 | ScalarnetBotz-prd-bot-ext-temp3-min-range | read-write | mandatory | The minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.89 | ScalarnetBotz-prd-bot-ext-temp3-max-range | read-write | mandatory | The maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.90 | ScalarnetBotz-prd-bot-ext-temp4-uV-per-degreeC | read-write | mandatory | The scaling factor used for the external temperature probe on port 4 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set… |
| 1.3.6.1.4.1.5528.30.10.91 | ScalarnetBotz-prd-bot-ext-temp4-uV-at-0-degreeC | read-write | mandatory | The offset used for the external temperature probe on port 4 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the… |
| 1.3.6.1.4.1.5528.30.10.92 | ScalarnetBotz-prd-bot-ext-temp4-min-range | read-write | mandatory | The minimum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.93 | ScalarnetBotz-prd-bot-ext-temp4-max-range | read-write | mandatory | The maximum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature se… |
| 1.3.6.1.4.1.5528.30.10.94 | ScalarnetBotz-prd-bot-ext-port1-module-id | read-write | mandatory | The module ID of the sensor module installed on port 1. Blank string indicates that no module is installed. |
| 1.3.6.1.4.1.5528.30.10.95 | ScalarnetBotz-prd-bot-ext-port1-module-type | read-write | mandatory | The type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
| 1.3.6.1.4.1.5528.30.10.96 | ScalarnetBotz-prd-bot-ext-port2-module-id | read-write | mandatory | The module ID of the sensor module installed on port 2. Blank string indicates that no module is installed. |
| 1.3.6.1.4.1.5528.30.10.97 | ScalarnetBotz-prd-bot-ext-port2-module-type | read-write | mandatory | The type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
| 1.3.6.1.4.1.5528.30.10.98 | ScalarnetBotz-prd-bot-ext-port3-module-id | read-write | mandatory | The module ID of the sensor module installed on port 3. Blank string indicates that no module is installed. |
| 1.3.6.1.4.1.5528.30.10.99 | ScalarnetBotz-prd-bot-ext-port3-module-type | read-write | mandatory | The type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
| 1.3.6.1.4.1.5528.30.10.100 | ScalarnetBotz-prd-bot-ext-port4-module-id | read-write | mandatory | The module ID of the sensor module installed on port 4. Blank string indicates that no module is installed. |
| 1.3.6.1.4.1.5528.30.10.101 | ScalarnetBotz-prd-bot-ext-port4-module-type | read-write | mandatory | The type of sensor module installed on port 4. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. |
| 1.3.6.1.4.1.5528.30.10.102 | ScalarnetBotz-prd-bot-amp1-total-amp-seconds | read-only | mandatory | The accumulated total of amp-seconds on the AmpDetect on port 1. |
| 1.3.6.1.4.1.5528.30.10.103 | ScalarnetBotz-prd-bot-amp1-total-amp-seconds-since-time | read-write | mandatory | The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute re… |
| 1.3.6.1.4.1.5528.30.10.104 | ScalarnetBotz-prd-bot-amp2-total-amp-seconds | read-only | mandatory | The accumulated total of amp-seconds on the AmpDetect on port 2. |
| 1.3.6.1.4.1.5528.30.10.105 | ScalarnetBotz-prd-bot-amp2-total-amp-seconds-since-time | read-write | mandatory | The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute re… |
| 1.3.6.1.4.1.5528.30.10.106 | ScalarnetBotz-prd-bot-amp3-total-amp-seconds | read-only | mandatory | The accumulated total of amp-seconds on the AmpDetect on port 3. |
| 1.3.6.1.4.1.5528.30.10.107 | ScalarnetBotz-prd-bot-amp3-total-amp-seconds-since-time | read-write | mandatory | The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute re… |
| 1.3.6.1.4.1.5528.30.10.108 | ScalarnetBotz-prd-bot-amp4-total-amp-seconds | read-only | mandatory | The accumulated total of amp-seconds on the AmpDetect on port 4. |
| 1.3.6.1.4.1.5528.30.10.109 | ScalarnetBotz-prd-bot-amp4-total-amp-seconds-since-time | read-write | mandatory | The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute re… |
| 1.3.6.1.4.1.5528.30.10.110 | ScalarnetBotz-prd-bot-amptotal-total-amp-seconds | read-only | mandatory | The accumulated total of amp-seconds on the total of all AmpDetects. |
| 1.3.6.1.4.1.5528.30.10.111 | ScalarnetBotz-prd-bot-amptotal-total-amp-seconds-since-time | read-write | mandatory | The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the… |
| 1.3.6.1.4.1.5528.30.10.112 | ScalarnetBotz-prd-bot-ext-dry1 | read-only | mandatory | The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A |
| 1.3.6.1.4.1.5528.30.10.113 | ScalarnetBotz-prd-bot-ext-dry2 | read-only | mandatory | The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A |
| 1.3.6.1.4.1.5528.30.10.114 | ScalarnetBotz-prd-bot-ext-dry3 | read-only | mandatory | The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A |
| 1.3.6.1.4.1.5528.30.10.115 | ScalarnetBotz-prd-bot-ext-dry4 | read-only | mandatory | The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A |
| 1.3.6.1.4.1.5528.30.10.116 | ScalarnetBotz-prd-bot-ext-dry1-alarm-value | read-write | mandatory | The value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed |
| 1.3.6.1.4.1.5528.30.10.117 | ScalarnetBotz-prd-bot-ext-dry1-enabled | read-write | mandatory | External dry contact sensor on Ext1 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.118 | ScalarnetBotz-prd-bot-ext-dry2-alarm-value | read-write | mandatory | The value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed |
| 1.3.6.1.4.1.5528.30.10.119 | ScalarnetBotz-prd-bot-ext-dry2-enabled | read-write | mandatory | External dry contact sensor on Ext2 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.120 | ScalarnetBotz-prd-bot-ext-dry3-alarm-value | read-write | mandatory | The value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed |
| 1.3.6.1.4.1.5528.30.10.121 | ScalarnetBotz-prd-bot-ext-dry3-enabled | read-write | mandatory | External dry contact sensor on Ext3 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.122 | ScalarnetBotz-prd-bot-ext-dry4-alarm-value | read-write | mandatory | The value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed |
| 1.3.6.1.4.1.5528.30.10.123 | ScalarnetBotz-prd-bot-ext-dry4-enabled | read-write | mandatory | External dry contact sensor on Ext4 alarm enabled(1) or disabled(0). |
| 1.3.6.1.4.1.5528.30.10.124 | ScalarnetBotz-prd-bot-ext-dry1-label | read-write | mandatory | The sensor name/label for the dry contact sensor on Ext1 |
| 1.3.6.1.4.1.5528.30.10.125 | ScalarnetBotz-prd-bot-ext-dry1-open-label | read-write | mandatory | The sensor name/label for the open(0) state for the dry contact sensor on Ext1 |
| 1.3.6.1.4.1.5528.30.10.126 | ScalarnetBotz-prd-bot-ext-dry1-closed-label | read-write | mandatory | The sensor name/label for the closed(0) state for the dry contact sensor on Ext1 |
| 1.3.6.1.4.1.5528.30.10.127 | ScalarnetBotz-prd-bot-ext-dry1-open-to-close-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed. |
| 1.3.6.1.4.1.5528.30.10.128 | ScalarnetBotz-prd-bot-ext-dry1-close-to-open-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open. |
| 1.3.6.1.4.1.5528.30.10.129 | ScalarnetBotz-prd-bot-ext-dry1-response | read-write | mandatory | The type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera. |
| 1.3.6.1.4.1.5528.30.10.130 | ScalarnetBotz-prd-bot-ext-dry2-label | read-write | mandatory | The sensor name/label for the dry contact sensor on Ext2 |
| 1.3.6.1.4.1.5528.30.10.131 | ScalarnetBotz-prd-bot-ext-dry2-open-label | read-write | mandatory | The sensor name/label for the open(0) state for the dry contact sensor on Ext2 |
| 1.3.6.1.4.1.5528.30.10.132 | ScalarnetBotz-prd-bot-ext-dry2-closed-label | read-write | mandatory | The sensor name/label for the closed(0) state for the dry contact sensor on Ext2 |
| 1.3.6.1.4.1.5528.30.10.133 | ScalarnetBotz-prd-bot-ext-dry2-open-to-close-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed. |
| 1.3.6.1.4.1.5528.30.10.134 | ScalarnetBotz-prd-bot-ext-dry2-close-to-open-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open. |
| 1.3.6.1.4.1.5528.30.10.135 | ScalarnetBotz-prd-bot-ext-dry2-response | read-write | mandatory | The type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera. |
| 1.3.6.1.4.1.5528.30.10.136 | ScalarnetBotz-prd-bot-ext-dry3-label | read-write | mandatory | The sensor name/label for the dry contact sensor on Ext3 |
| 1.3.6.1.4.1.5528.30.10.137 | ScalarnetBotz-prd-bot-ext-dry3-open-label | read-write | mandatory | The sensor name/label for the open(0) state for the dry contact sensor on Ext3 |
| 1.3.6.1.4.1.5528.30.10.138 | ScalarnetBotz-prd-bot-ext-dry3-closed-label | read-write | mandatory | The sensor name/label for the closed(0) state for the dry contact sensor on Ext3 |
| 1.3.6.1.4.1.5528.30.10.139 | ScalarnetBotz-prd-bot-ext-dry3-open-to-close-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed. |
| 1.3.6.1.4.1.5528.30.10.140 | ScalarnetBotz-prd-bot-ext-dry3-close-to-open-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open. |
| 1.3.6.1.4.1.5528.30.10.141 | ScalarnetBotz-prd-bot-ext-dry3-response | read-write | mandatory | The type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera. |
| 1.3.6.1.4.1.5528.30.10.142 | ScalarnetBotz-prd-bot-ext-dry4-label | read-write | mandatory | The sensor name/label for the dry contact sensor on Ext4 |
| 1.3.6.1.4.1.5528.30.10.143 | ScalarnetBotz-prd-bot-ext-dry4-open-label | read-write | mandatory | The sensor name/label for the open(0) state for the dry contact sensor on Ext4 |
| 1.3.6.1.4.1.5528.30.10.144 | ScalarnetBotz-prd-bot-ext-dry4-closed-label | read-write | mandatory | The sensor name/label for the closed(0) state for the dry contact sensor on Ext4 |
| 1.3.6.1.4.1.5528.30.10.145 | ScalarnetBotz-prd-bot-ext-dry4-open-to-close-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext4 must read closed before the state is changed from open to closed. |
| 1.3.6.1.4.1.5528.30.10.146 | ScalarnetBotz-prd-bot-ext-dry4-close-to-open-millis | read-write | mandatory | The minimum number of milliseconds that the dry contact sensor on Ext4 must read openbefore the state is changed from closed to open. |
| 1.3.6.1.4.1.5528.30.10.147 | ScalarnetBotz-prd-bot-ext-dry4-response | read-write | mandatory | The type of alert response for the dry contact sensor on Ext4: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera. |
| 1.3.6.1.4.1.5528.30.100 | NodenetBotz-prd-bot-traps | |||
| 1.3.6.1.4.1.5528.30.100.1 | NodenetBotz-prd-bot-temperature-traps | |||
| 1.3.6.1.4.1.5528.30.100.1.1 | NodenetBotz-prd-bot-temperature-low-trap | Netbotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.1.2 | NodenetBotz-prd-bot-temperature-high-trap | Netbotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.1.3 | NodenetBotz-prd-bot-temperature-trap-clear | Netbotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.2 | NodenetBotz-prd-bot-humidity-traps | |||
| 1.3.6.1.4.1.5528.30.100.2.1 | NodenetBotz-prd-bot-humidity-low-trap | Netbotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.2.2 | NodenetBotz-prd-bot-humidity-high-trap | Netbotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.2.3 | NodenetBotz-prd-bot-humidity-trap-clear | Netbotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.3 | NodenetBotz-prd-bot-airflow-traps | |||
| 1.3.6.1.4.1.5528.30.100.3.1 | NodenetBotz-prd-bot-airflow-low-trap | Netbotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.3.3 | NodenetBotz-prd-bot-airflow-trap-clear | Netbotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.4 | NodenetBotz-prd-bot-audio-traps | |||
| 1.3.6.1.4.1.5528.30.100.4.2 | NodenetBotz-prd-bot-audio-high-trap | Netbotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.4.3 | NodenetBotz-prd-bot-audio-trap-clear | Netbotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.5 | NodenetBotz-prd-bot-door-traps | |||
| 1.3.6.1.4.1.5528.30.100.5.2 | NodenetBotz-prd-bot-door-trap-tripped | Netbotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, clo… | ||
| 1.3.6.1.4.1.5528.30.100.5.3 | NodenetBotz-prd-bot-door-trap-clear | Netbotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on… | ||
| 1.3.6.1.4.1.5528.30.100.6 | NodenetBotz-prd-bot-amp1-traps | |||
| 1.3.6.1.4.1.5528.30.100.6.1 | NodenetBotz-prd-bot-amp1-low-trap | Netbotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.6.2 | NodenetBotz-prd-bot-amp1-high-trap | Netbotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.6.3 | NodenetBotz-prd-bot-amp1-trap-clear | Netbotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.6.6 | NodenetBotz-prd-bot-amp1-sensor-unplugged | Netbotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.6.7 | NodenetBotz-prd-bot-amp1-sensor-replugged | Netbotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.7 | NodenetBotz-prd-bot-amp2-traps | |||
| 1.3.6.1.4.1.5528.30.100.7.1 | NodenetBotz-prd-bot-amp2-low-trap | Netbotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.7.2 | NodenetBotz-prd-bot-amp2-high-trap | Netbotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.7.3 | NodenetBotz-prd-bot-amp2-trap-clear | Netbotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.7.6 | NodenetBotz-prd-bot-amp2-sensor-unplugged | Netbotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.7.7 | NodenetBotz-prd-bot-amp2-sensor-replugged | Netbotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.8 | NodenetBotz-prd-bot-amp3-traps | |||
| 1.3.6.1.4.1.5528.30.100.8.1 | NodenetBotz-prd-bot-amp3-low-trap | Netbotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.8.2 | NodenetBotz-prd-bot-amp3-high-trap | Netbotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.8.3 | NodenetBotz-prd-bot-amp3-trap-clear | Netbotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.8.6 | NodenetBotz-prd-bot-amp3-sensor-unplugged | Netbotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.8.7 | NodenetBotz-prd-bot-amp3-sensor-replugged | Netbotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.9 | NodenetBotz-prd-bot-amp4-traps | |||
| 1.3.6.1.4.1.5528.30.100.9.1 | NodenetBotz-prd-bot-amp4-low-trap | Netbotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.9.2 | NodenetBotz-prd-bot-amp4-high-trap | Netbotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.9.3 | NodenetBotz-prd-bot-amp4-trap-clear | Netbotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.9.6 | NodenetBotz-prd-bot-amp4-sensor-unplugged | Netbotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.9.7 | NodenetBotz-prd-bot-amp4-sensor-replugged | Netbotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.10 | NodenetBotz-prd-bot-amp-total-traps | |||
| 1.3.6.1.4.1.5528.30.100.10.1 | NodenetBotz-prd-bot-amp-total-low-trap | Netbotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.10.2 | NodenetBotz-prd-bot-amp-total-high-trap | Netbotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.10.3 | NodenetBotz-prd-bot-amp-total-trap-clear | Netbotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits. | ||
| 1.3.6.1.4.1.5528.30.100.11 | NodenetBotz-prd-bot-ext-temp1-traps | |||
| 1.3.6.1.4.1.5528.30.100.11.1 | NodenetBotz-prd-bot-ext-temp1-low-trap | Netbotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.11.2 | NodenetBotz-prd-bot-ext-temp1-high-trap | Netbotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.11.3 | NodenetBotz-prd-bot-ext-temp1-trap-clear | Netbotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to accept… | ||
| 1.3.6.1.4.1.5528.30.100.11.6 | NodenetBotz-prd-bot-ext-temp1-sensor-unplugged | Netbotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.11.7 | NodenetBotz-prd-bot-ext-temp1-sensor-replugged | Netbotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.12 | NodenetBotz-prd-bot-ext-temp2-traps | |||
| 1.3.6.1.4.1.5528.30.100.12.1 | NodenetBotz-prd-bot-ext-temp2-low-trap | Netbotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.12.2 | NodenetBotz-prd-bot-ext-temp2-high-trap | Netbotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.12.3 | NodenetBotz-prd-bot-ext-temp2-trap-clear | Netbotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to accept… | ||
| 1.3.6.1.4.1.5528.30.100.12.6 | NodenetBotz-prd-bot-ext-temp2-sensor-unplugged | Netbotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.12.7 | NodenetBotz-prd-bot-ext-temp2-sensor-replugged | Netbotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.13 | NodenetBotz-prd-bot-ext-temp3-traps | |||
| 1.3.6.1.4.1.5528.30.100.13.1 | NodenetBotz-prd-bot-ext-temp3-low-trap | Netbotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.13.2 | NodenetBotz-prd-bot-ext-temp3-high-trap | Netbotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.13.3 | NodenetBotz-prd-bot-ext-temp3-trap-clear | Netbotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to accept… | ||
| 1.3.6.1.4.1.5528.30.100.13.6 | NodenetBotz-prd-bot-ext-temp3-sensor-unplugged | Netbotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.13.7 | NodenetBotz-prd-bot-ext-temp3-sensor-replugged | Netbotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.14 | NodenetBotz-prd-bot-ext-temp4-traps | |||
| 1.3.6.1.4.1.5528.30.100.14.1 | NodenetBotz-prd-bot-ext-temp4-low-trap | Netbotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.14.2 | NodenetBotz-prd-bot-ext-temp4-high-trap | Netbotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded. | ||
| 1.3.6.1.4.1.5528.30.100.14.3 | NodenetBotz-prd-bot-ext-temp4-trap-clear | Netbotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to accept… | ||
| 1.3.6.1.4.1.5528.30.100.14.6 | NodenetBotz-prd-bot-ext-temp4-sensor-unplugged | Netbotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. | ||
| 1.3.6.1.4.1.5528.30.100.14.7 | NodenetBotz-prd-bot-ext-temp4-sensor-replugged | Netbotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. | ||
| 1.3.6.1.4.1.5528.30.100.15 | NodenetBotz-prd-bot-ext-dry1-traps | |||
| 1.3.6.1.4.1.5528.30.100.15.2 | NodenetBotz-prd-bot-ext-dry1-triggered-trap | Netbotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.15.3 | NodenetBotz-prd-bot-ext-dry1-trap-clear | Netbotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.16 | NodenetBotz-prd-bot-ext-dry2-traps | |||
| 1.3.6.1.4.1.5528.30.100.16.2 | NodenetBotz-prd-bot-ext-dry2-triggered-trap | Netbotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.16.3 | NodenetBotz-prd-bot-ext-dry2-trap-clear | Netbotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.17 | NodenetBotz-prd-bot-ext-dry3-traps | |||
| 1.3.6.1.4.1.5528.30.100.17.2 | NodenetBotz-prd-bot-ext-dry3-triggered-trap | Netbotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.17.3 | NodenetBotz-prd-bot-ext-dry3-trap-clear | Netbotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.18 | NodenetBotz-prd-bot-ext-dry4-traps | |||
| 1.3.6.1.4.1.5528.30.100.18.2 | NodenetBotz-prd-bot-ext-dry4-triggered-trap | Netbotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value. | ||
| 1.3.6.1.4.1.5528.30.100.18.3 | NodenetBotz-prd-bot-ext-dry4-trap-clear | Netbotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value. |