MIB Viewer

NETBOTZ-PRD-BOT-MIB

229 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.5528.30.10.1NodenetBotz-prd-bot-low-trapNetbotz Low Trap. This trap indicates that a lower limit has been exceeded.
1.3.6.1.4.1.5528.30.10.1ScalarnetBotz-prd-bot-tempread-onlymandatoryThe reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.2NodenetBotz-prd-bot-high-trapNetbotz High Trap. This trap indicates that an upper limit has been exceeded.
1.3.6.1.4.1.5528.30.10.2ScalarnetBotz-prd-bot-humidityread-onlymandatoryThe reading of the humidity probe, in percent.
1.3.6.1.4.1.5528.30.10.3ScalarnetBotz-prd-bot-airflowread-onlymandatoryThe reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity.
1.3.6.1.4.1.5528.30.10.3NodenetBotz-prd-bot-trap-clearNetbotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.10.4ScalarnetBotz-prd-bot-audioread-onlymandatoryThe reading of the audio alarm probe on/off.
1.3.6.1.4.1.5528.30.10.4NodenetBotz-prd-bot-offline-trapNetbotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline.
1.3.6.1.4.1.5528.30.10.5ScalarnetBotz-prd-bot-doorajarread-onlymandatoryThe reading of the door switch probe open(0) or closed(1).
1.3.6.1.4.1.5528.30.10.5NodenetBotz-prd-bot-online-trapNetbotz Device Online Trap. This trap indicates that a device or function has been determined to be online.
1.3.6.1.4.1.5528.30.10.6ScalarnetBotz-prd-bot-temp-minread-writemandatoryThe temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.7ScalarnetBotz-prd-bot-temp-maxread-writemandatoryThe temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.8ScalarnetBotz-prd-bot-humidity-minread-writemandatoryThe humidity probe minimum, from 10 to 90 percent.
1.3.6.1.4.1.5528.30.10.9ScalarnetBotz-prd-bot-humidity-maxread-writemandatoryThe humidity probe maximum, from 10 to 90 percent.
1.3.6.1.4.1.5528.30.10.10ScalarnetBotz-prd-bot-airflow-minsread-writemandatoryMinutes without airflow before alarm set.
1.3.6.1.4.1.5528.30.10.11ScalarnetBotz-prd-bot-audio-secsread-writemandatorySeconds of alarm audio before alarm set.
1.3.6.1.4.1.5528.30.10.12ScalarnetBotz-prd-bot-temp-enabledread-writemandatoryTemperature probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.13ScalarnetBotz-prd-bot-hum-enabledread-writemandatoryHumidity probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.14ScalarnetBotz-prd-bot-air-enabledread-writemandatoryAirflow probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.15ScalarnetBotz-prd-bot-audio-enabledread-writemandatoryAudio probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.16ScalarnetBotz-prd-bot-switch-stateread-writemandatorySwitch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to …
1.3.6.1.4.1.5528.30.10.17ScalarnetBotz-prd-bot-switch-enabledread-writemandatoryDoor switch enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.18ScalarnetBotz-prd-bot-audio-levelread-writemandatoryAudio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent.
1.3.6.1.4.1.5528.30.10.19ScalarnetBotz-prd-bot-doorpic-delayread-writemandatoryNumber of seconds between door alert and first picture.
1.3.6.1.4.1.5528.30.10.20ScalarnetBotz-prd-bot-trap-indexread-onlymandatoryThe crawler ID of the last trap.
1.3.6.1.4.1.5528.30.10.21ScalarnetBotz-prd-bot-trap-addressread-onlymandatoryThe IP address of the last trap.
1.3.6.1.4.1.5528.30.10.22ScalarnetBotz-prd-bot-trap-oidread-onlymandatoryThe object id of the last trap.
1.3.6.1.4.1.5528.30.10.23ScalarnetBotz-prd-bot-trap-valueread-onlymandatoryThe value of the last object trap.
1.3.6.1.4.1.5528.30.10.24ScalarnetBotz-prd-bot-trap-dateread-onlymandatoryThe date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
1.3.6.1.4.1.5528.30.10.26ScalarnetBotz-prd-bot-refreshread-writemandatoryRate of web page refresh, in seconds. This must be greater than 5 seconds.
1.3.6.1.4.1.5528.30.10.27ScalarnetBotz-prd-bot-airflow-levelread-writemandatoryAirflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 1…
1.3.6.1.4.1.5528.30.10.28ScalarnetBotz-prd-bot-doorpic-countread-writemandatoryNumber of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures.
1.3.6.1.4.1.5528.30.10.29ScalarnetBotz-prd-bot-amps1read-onlymandatoryThe reading of the first amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.30ScalarnetBotz-prd-bot-amps1-enabledread-writemandatoryAmperage[1] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.31ScalarnetBotz-prd-bot-amps1-minread-writemandatoryThe amperage[1] probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.32ScalarnetBotz-prd-bot-amps1-maxread-writemandatoryThe amperage[1] probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.34ScalarnetBotz-prd-bot-amps2read-onlymandatoryThe reading of the second amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.35ScalarnetBotz-prd-bot-amps2-enabledread-writemandatoryAmperage[2] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.36ScalarnetBotz-prd-bot-amps2-minread-writemandatoryThe amperage[2] probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.37ScalarnetBotz-prd-bot-amps2-maxread-writemandatoryThe amperage[2] probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.39ScalarnetBotz-prd-bot-amps3read-onlymandatoryThe reading of the third amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.40ScalarnetBotz-prd-bot-amps3-enabledread-writemandatoryAmperage[3] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.41ScalarnetBotz-prd-bot-amps3-minread-writemandatoryThe amperage[3] probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.42ScalarnetBotz-prd-bot-amps3-maxread-writemandatoryThe amperage[3] probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.44ScalarnetBotz-prd-bot-amps-totalread-onlymandatoryThe total of the readings of all amperage probes, in milliamps.
1.3.6.1.4.1.5528.30.10.45ScalarnetBotz-prd-bot-amps-total-enabledread-writemandatoryTotal amperage alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.46ScalarnetBotz-prd-bot-amps-total-minread-writemandatoryThe total amperage minimum, from 0 to 90000 milliamps.
1.3.6.1.4.1.5528.30.10.47ScalarnetBotz-prd-bot-amps-total-maxread-writemandatoryThe total amperage maximum, from 0 to 90000 milliamps.
1.3.6.1.4.1.5528.30.10.48ScalarnetBotz-prd-bot-amps-total-support-enabledread-writemandatoryTotal Amperage Support enabled(Y) or disabled(N).
1.3.6.1.4.1.5528.30.10.49ScalarnetBotz-prd-bot-amps1-uV-per-10mAread-writemandatoryThe scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based…
1.3.6.1.4.1.5528.30.10.50ScalarnetBotz-prd-bot-amps2-uV-per-10mAread-writemandatoryThe scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set base…
1.3.6.1.4.1.5528.30.10.51ScalarnetBotz-prd-bot-amps3-uV-per-mAread-writemandatoryThe scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based…
1.3.6.1.4.1.5528.30.10.52ScalarnetBotz-prd-bot-amps1-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the first Amp Detect.
1.3.6.1.4.1.5528.30.10.53ScalarnetBotz-prd-bot-amps2-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the second Amp Detect.
1.3.6.1.4.1.5528.30.10.54ScalarnetBotz-prd-bot-amps3-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the third Amp Detect.
1.3.6.1.4.1.5528.30.10.55ScalarnetBotz-prd-bot-amps4read-onlymandatoryThe reading of the fourth amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.56ScalarnetBotz-prd-bot-amps4-enabledread-writemandatoryAmperage[4] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.57ScalarnetBotz-prd-bot-amps4-minread-writemandatoryThe amperage[4] probe minimum, in milliamps.
1.3.6.1.4.1.5528.30.10.58ScalarnetBotz-prd-bot-amps4-maxread-writemandatoryThe amperage[4] probe maximum, in milliamps.
1.3.6.1.4.1.5528.30.10.60ScalarnetBotz-prd-bot-amps4-uV-per-10mAread-writemandatoryThe scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set base…
1.3.6.1.4.1.5528.30.10.61ScalarnetBotz-prd-bot-amps4-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the fourth Amp Detect.
1.3.6.1.4.1.5528.30.10.62ScalarnetBotz-prd-bot-ext-temp1read-onlymandatoryThe reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.63ScalarnetBotz-prd-bot-ext-temp2read-onlymandatoryThe reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.64ScalarnetBotz-prd-bot-ext-temp3read-onlymandatoryThe reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.65ScalarnetBotz-prd-bot-ext-temp4read-onlymandatoryThe reading of the external temperature probe on port 4, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.66ScalarnetBotz-prd-bot-ext-temp1-enabledread-writemandatoryExternal temperature probe on port 1 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.67ScalarnetBotz-prd-bot-ext-temp1-minread-writemandatoryThe external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.68ScalarnetBotz-prd-bot-ext-temp1-maxread-writemandatoryThe external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.69ScalarnetBotz-prd-bot-ext-temp2-enabledread-writemandatoryExternal temperature probe on port 2 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.70ScalarnetBotz-prd-bot-ext-temp2-minread-writemandatoryThe external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.71ScalarnetBotz-prd-bot-ext-temp2-maxread-writemandatoryThe external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.72ScalarnetBotz-prd-bot-ext-temp3-enabledread-writemandatoryExternal temperature probe on port 3 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.73ScalarnetBotz-prd-bot-ext-temp3-minread-writemandatoryThe external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.74ScalarnetBotz-prd-bot-ext-temp3-maxread-writemandatoryThe external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.75ScalarnetBotz-prd-bot-ext-temp4-enabledread-writemandatoryExternal temperature probe on port 4 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.76ScalarnetBotz-prd-bot-ext-temp4-minread-writemandatoryThe external temperature probe on port 4 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.77ScalarnetBotz-prd-bot-ext-temp4-maxread-writemandatoryThe external temperature probe on port 4 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.78ScalarnetBotz-prd-bot-ext-temp1-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.79ScalarnetBotz-prd-bot-ext-temp1-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.80ScalarnetBotz-prd-bot-ext-temp1-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.81ScalarnetBotz-prd-bot-ext-temp1-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.82ScalarnetBotz-prd-bot-ext-temp2-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.83ScalarnetBotz-prd-bot-ext-temp2-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.84ScalarnetBotz-prd-bot-ext-temp2-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.85ScalarnetBotz-prd-bot-ext-temp2-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.86ScalarnetBotz-prd-bot-ext-temp3-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.87ScalarnetBotz-prd-bot-ext-temp3-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.88ScalarnetBotz-prd-bot-ext-temp3-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.89ScalarnetBotz-prd-bot-ext-temp3-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.90ScalarnetBotz-prd-bot-ext-temp4-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 4 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.91ScalarnetBotz-prd-bot-ext-temp4-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 4 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.92ScalarnetBotz-prd-bot-ext-temp4-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.93ScalarnetBotz-prd-bot-ext-temp4-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.94ScalarnetBotz-prd-bot-ext-port1-module-idread-writemandatoryThe module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.95ScalarnetBotz-prd-bot-ext-port1-module-typeread-writemandatoryThe type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.96ScalarnetBotz-prd-bot-ext-port2-module-idread-writemandatoryThe module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.97ScalarnetBotz-prd-bot-ext-port2-module-typeread-writemandatoryThe type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.98ScalarnetBotz-prd-bot-ext-port3-module-idread-writemandatoryThe module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.99ScalarnetBotz-prd-bot-ext-port3-module-typeread-writemandatoryThe type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.100ScalarnetBotz-prd-bot-ext-port4-module-idread-writemandatoryThe module ID of the sensor module installed on port 4. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.101ScalarnetBotz-prd-bot-ext-port4-module-typeread-writemandatoryThe type of sensor module installed on port 4. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.102ScalarnetBotz-prd-bot-amp1-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 1.
1.3.6.1.4.1.5528.30.10.103ScalarnetBotz-prd-bot-amp1-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.104ScalarnetBotz-prd-bot-amp2-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 2.
1.3.6.1.4.1.5528.30.10.105ScalarnetBotz-prd-bot-amp2-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.106ScalarnetBotz-prd-bot-amp3-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 3.
1.3.6.1.4.1.5528.30.10.107ScalarnetBotz-prd-bot-amp3-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.108ScalarnetBotz-prd-bot-amp4-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 4.
1.3.6.1.4.1.5528.30.10.109ScalarnetBotz-prd-bot-amp4-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.110ScalarnetBotz-prd-bot-amptotal-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the total of all AmpDetects.
1.3.6.1.4.1.5528.30.10.111ScalarnetBotz-prd-bot-amptotal-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the…
1.3.6.1.4.1.5528.30.10.112ScalarnetBotz-prd-bot-ext-dry1read-onlymandatoryThe current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.113ScalarnetBotz-prd-bot-ext-dry2read-onlymandatoryThe current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.114ScalarnetBotz-prd-bot-ext-dry3read-onlymandatoryThe current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.115ScalarnetBotz-prd-bot-ext-dry4read-onlymandatoryThe current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.116ScalarnetBotz-prd-bot-ext-dry1-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.117ScalarnetBotz-prd-bot-ext-dry1-enabledread-writemandatoryExternal dry contact sensor on Ext1 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.118ScalarnetBotz-prd-bot-ext-dry2-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.119ScalarnetBotz-prd-bot-ext-dry2-enabledread-writemandatoryExternal dry contact sensor on Ext2 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.120ScalarnetBotz-prd-bot-ext-dry3-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.121ScalarnetBotz-prd-bot-ext-dry3-enabledread-writemandatoryExternal dry contact sensor on Ext3 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.122ScalarnetBotz-prd-bot-ext-dry4-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.123ScalarnetBotz-prd-bot-ext-dry4-enabledread-writemandatoryExternal dry contact sensor on Ext4 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.124ScalarnetBotz-prd-bot-ext-dry1-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext1
1.3.6.1.4.1.5528.30.10.125ScalarnetBotz-prd-bot-ext-dry1-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext1
1.3.6.1.4.1.5528.30.10.126ScalarnetBotz-prd-bot-ext-dry1-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext1
1.3.6.1.4.1.5528.30.10.127ScalarnetBotz-prd-bot-ext-dry1-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.128ScalarnetBotz-prd-bot-ext-dry1-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.129ScalarnetBotz-prd-bot-ext-dry1-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.10.130ScalarnetBotz-prd-bot-ext-dry2-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext2
1.3.6.1.4.1.5528.30.10.131ScalarnetBotz-prd-bot-ext-dry2-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext2
1.3.6.1.4.1.5528.30.10.132ScalarnetBotz-prd-bot-ext-dry2-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext2
1.3.6.1.4.1.5528.30.10.133ScalarnetBotz-prd-bot-ext-dry2-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.134ScalarnetBotz-prd-bot-ext-dry2-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.135ScalarnetBotz-prd-bot-ext-dry2-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.10.136ScalarnetBotz-prd-bot-ext-dry3-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext3
1.3.6.1.4.1.5528.30.10.137ScalarnetBotz-prd-bot-ext-dry3-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext3
1.3.6.1.4.1.5528.30.10.138ScalarnetBotz-prd-bot-ext-dry3-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext3
1.3.6.1.4.1.5528.30.10.139ScalarnetBotz-prd-bot-ext-dry3-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.140ScalarnetBotz-prd-bot-ext-dry3-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.141ScalarnetBotz-prd-bot-ext-dry3-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.10.142ScalarnetBotz-prd-bot-ext-dry4-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext4
1.3.6.1.4.1.5528.30.10.143ScalarnetBotz-prd-bot-ext-dry4-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext4
1.3.6.1.4.1.5528.30.10.144ScalarnetBotz-prd-bot-ext-dry4-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext4
1.3.6.1.4.1.5528.30.10.145ScalarnetBotz-prd-bot-ext-dry4-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext4 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.146ScalarnetBotz-prd-bot-ext-dry4-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext4 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.147ScalarnetBotz-prd-bot-ext-dry4-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext4: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.100NodenetBotz-prd-bot-traps
1.3.6.1.4.1.5528.30.100.1NodenetBotz-prd-bot-temperature-traps
1.3.6.1.4.1.5528.30.100.1.1NodenetBotz-prd-bot-temperature-low-trapNetbotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded.
1.3.6.1.4.1.5528.30.100.1.2NodenetBotz-prd-bot-temperature-high-trapNetbotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded.
1.3.6.1.4.1.5528.30.100.1.3NodenetBotz-prd-bot-temperature-trap-clearNetbotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.2NodenetBotz-prd-bot-humidity-traps
1.3.6.1.4.1.5528.30.100.2.1NodenetBotz-prd-bot-humidity-low-trapNetbotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded.
1.3.6.1.4.1.5528.30.100.2.2NodenetBotz-prd-bot-humidity-high-trapNetbotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded.
1.3.6.1.4.1.5528.30.100.2.3NodenetBotz-prd-bot-humidity-trap-clearNetbotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.3NodenetBotz-prd-bot-airflow-traps
1.3.6.1.4.1.5528.30.100.3.1NodenetBotz-prd-bot-airflow-low-trapNetbotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded.
1.3.6.1.4.1.5528.30.100.3.3NodenetBotz-prd-bot-airflow-trap-clearNetbotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.4NodenetBotz-prd-bot-audio-traps
1.3.6.1.4.1.5528.30.100.4.2NodenetBotz-prd-bot-audio-high-trapNetbotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded.
1.3.6.1.4.1.5528.30.100.4.3NodenetBotz-prd-bot-audio-trap-clearNetbotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.5NodenetBotz-prd-bot-door-traps
1.3.6.1.4.1.5528.30.100.5.2NodenetBotz-prd-bot-door-trap-trippedNetbotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, clo…
1.3.6.1.4.1.5528.30.100.5.3NodenetBotz-prd-bot-door-trap-clearNetbotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on…
1.3.6.1.4.1.5528.30.100.6NodenetBotz-prd-bot-amp1-traps
1.3.6.1.4.1.5528.30.100.6.1NodenetBotz-prd-bot-amp1-low-trapNetbotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.6.2NodenetBotz-prd-bot-amp1-high-trapNetbotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.6.3NodenetBotz-prd-bot-amp1-trap-clearNetbotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.6.6NodenetBotz-prd-bot-amp1-sensor-unpluggedNetbotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.6.7NodenetBotz-prd-bot-amp1-sensor-repluggedNetbotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.7NodenetBotz-prd-bot-amp2-traps
1.3.6.1.4.1.5528.30.100.7.1NodenetBotz-prd-bot-amp2-low-trapNetbotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.7.2NodenetBotz-prd-bot-amp2-high-trapNetbotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.7.3NodenetBotz-prd-bot-amp2-trap-clearNetbotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.7.6NodenetBotz-prd-bot-amp2-sensor-unpluggedNetbotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.7.7NodenetBotz-prd-bot-amp2-sensor-repluggedNetbotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.8NodenetBotz-prd-bot-amp3-traps
1.3.6.1.4.1.5528.30.100.8.1NodenetBotz-prd-bot-amp3-low-trapNetbotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.8.2NodenetBotz-prd-bot-amp3-high-trapNetbotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.8.3NodenetBotz-prd-bot-amp3-trap-clearNetbotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.8.6NodenetBotz-prd-bot-amp3-sensor-unpluggedNetbotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.8.7NodenetBotz-prd-bot-amp3-sensor-repluggedNetbotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.9NodenetBotz-prd-bot-amp4-traps
1.3.6.1.4.1.5528.30.100.9.1NodenetBotz-prd-bot-amp4-low-trapNetbotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.9.2NodenetBotz-prd-bot-amp4-high-trapNetbotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.9.3NodenetBotz-prd-bot-amp4-trap-clearNetbotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.9.6NodenetBotz-prd-bot-amp4-sensor-unpluggedNetbotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.9.7NodenetBotz-prd-bot-amp4-sensor-repluggedNetbotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.10NodenetBotz-prd-bot-amp-total-traps
1.3.6.1.4.1.5528.30.100.10.1NodenetBotz-prd-bot-amp-total-low-trapNetbotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded.
1.3.6.1.4.1.5528.30.100.10.2NodenetBotz-prd-bot-amp-total-high-trapNetbotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded.
1.3.6.1.4.1.5528.30.100.10.3NodenetBotz-prd-bot-amp-total-trap-clearNetbotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.11NodenetBotz-prd-bot-ext-temp1-traps
1.3.6.1.4.1.5528.30.100.11.1NodenetBotz-prd-bot-ext-temp1-low-trapNetbotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded.
1.3.6.1.4.1.5528.30.100.11.2NodenetBotz-prd-bot-ext-temp1-high-trapNetbotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded.
1.3.6.1.4.1.5528.30.100.11.3NodenetBotz-prd-bot-ext-temp1-trap-clearNetbotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to accept…
1.3.6.1.4.1.5528.30.100.11.6NodenetBotz-prd-bot-ext-temp1-sensor-unpluggedNetbotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.11.7NodenetBotz-prd-bot-ext-temp1-sensor-repluggedNetbotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.12NodenetBotz-prd-bot-ext-temp2-traps
1.3.6.1.4.1.5528.30.100.12.1NodenetBotz-prd-bot-ext-temp2-low-trapNetbotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded.
1.3.6.1.4.1.5528.30.100.12.2NodenetBotz-prd-bot-ext-temp2-high-trapNetbotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded.
1.3.6.1.4.1.5528.30.100.12.3NodenetBotz-prd-bot-ext-temp2-trap-clearNetbotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to accept…
1.3.6.1.4.1.5528.30.100.12.6NodenetBotz-prd-bot-ext-temp2-sensor-unpluggedNetbotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.12.7NodenetBotz-prd-bot-ext-temp2-sensor-repluggedNetbotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.13NodenetBotz-prd-bot-ext-temp3-traps
1.3.6.1.4.1.5528.30.100.13.1NodenetBotz-prd-bot-ext-temp3-low-trapNetbotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded.
1.3.6.1.4.1.5528.30.100.13.2NodenetBotz-prd-bot-ext-temp3-high-trapNetbotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded.
1.3.6.1.4.1.5528.30.100.13.3NodenetBotz-prd-bot-ext-temp3-trap-clearNetbotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to accept…
1.3.6.1.4.1.5528.30.100.13.6NodenetBotz-prd-bot-ext-temp3-sensor-unpluggedNetbotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.13.7NodenetBotz-prd-bot-ext-temp3-sensor-repluggedNetbotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.14NodenetBotz-prd-bot-ext-temp4-traps
1.3.6.1.4.1.5528.30.100.14.1NodenetBotz-prd-bot-ext-temp4-low-trapNetbotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded.
1.3.6.1.4.1.5528.30.100.14.2NodenetBotz-prd-bot-ext-temp4-high-trapNetbotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded.
1.3.6.1.4.1.5528.30.100.14.3NodenetBotz-prd-bot-ext-temp4-trap-clearNetbotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to accept…
1.3.6.1.4.1.5528.30.100.14.6NodenetBotz-prd-bot-ext-temp4-sensor-unpluggedNetbotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.14.7NodenetBotz-prd-bot-ext-temp4-sensor-repluggedNetbotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.15NodenetBotz-prd-bot-ext-dry1-traps
1.3.6.1.4.1.5528.30.100.15.2NodenetBotz-prd-bot-ext-dry1-triggered-trapNetbotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value.
1.3.6.1.4.1.5528.30.100.15.3NodenetBotz-prd-bot-ext-dry1-trap-clearNetbotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.16NodenetBotz-prd-bot-ext-dry2-traps
1.3.6.1.4.1.5528.30.100.16.2NodenetBotz-prd-bot-ext-dry2-triggered-trapNetbotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value.
1.3.6.1.4.1.5528.30.100.16.3NodenetBotz-prd-bot-ext-dry2-trap-clearNetbotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.17NodenetBotz-prd-bot-ext-dry3-traps
1.3.6.1.4.1.5528.30.100.17.2NodenetBotz-prd-bot-ext-dry3-triggered-trapNetbotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value.
1.3.6.1.4.1.5528.30.100.17.3NodenetBotz-prd-bot-ext-dry3-trap-clearNetbotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.18NodenetBotz-prd-bot-ext-dry4-traps
1.3.6.1.4.1.5528.30.100.18.2NodenetBotz-prd-bot-ext-dry4-triggered-trapNetbotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value.
1.3.6.1.4.1.5528.30.100.18.3NodenetBotz-prd-bot-ext-dry4-trap-clearNetbotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value.