MIB Viewer

PSNA-PS-psmA-MIB

94 objects
No module-level DESCRIPTION found.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.13400NodeemersonNetworkPower
1.3.6.1.4.1.13400.2Nodeproducts
1.3.6.1.4.1.13400.2.8Nodepsm
1.3.6.1.4.1.13400.2.8.1NodepsAgent
1.3.6.1.4.1.13400.2.8.1NodepsOnNormalINFORMATION: The Power System is on normal status.
1.3.6.1.4.1.13400.2.8.1.1ScalaragentRevisionread-onlymandatoryThe firmware revision of the agent.
1.3.6.1.4.1.13400.2.8.1.2ScalaragentManagersNumread-onlymandatoryThe number of managers that can manage the agent.
1.3.6.1.4.1.13400.2.8.1.3TableagentManagersTablenot-accessiblemandatoryA list of managers of the agent. The number of entries is given by the value of agentManagersNum.
1.3.6.1.4.1.13400.2.8.1.3.1RowagentManagersEntrynot-accessiblemandatoryThe managers of the agent.
1.3.6.1.4.1.13400.2.8.1.3.1.1ColumnmanagerIndexread-onlymandatoryThe index of the managers entry.
1.3.6.1.4.1.13400.2.8.1.3.1.2ColumnmanagerAddrread-writemandatoryThe IP address of the manager.
1.3.6.1.4.1.13400.2.8.1.3.1.3ColumnpublicCommunityStringread-writemandatoryThe public community name to use in the query request.
1.3.6.1.4.1.13400.2.8.1.3.1.4ColumnprivateCommunityStringread-writemandatoryThe private community name to use in the control request.
1.3.6.1.4.1.13400.2.8.1.3.1.5ColumnmanagerPrivilegeread-writemandatoryThe privilege of the manager to access the agent. setting forbidden(0) indicates the manager have no any privilege to access the agent, setting query(1) indica…
1.3.6.1.4.1.13400.2.8.1.3.1.6ColumnacceptTrapLevelread-writemandatoryThe severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greate…
1.3.6.1.4.1.13400.2.8.1.3.1.7ColumnmanagerAcceptread-writemandatoryAn entry will be added if new(1), will be modified if modify(2), and will be removed if delete(3).
1.3.6.1.4.1.13400.2.8.2NodecommunicationLostSEVERE: Communication with the Power System lost.
1.3.6.1.4.1.13400.2.8.2NodepsCommon
1.3.6.1.4.1.13400.2.8.2.1NodepsIdent
1.3.6.1.4.1.13400.2.8.2.1.1ScalarpsIdentControllerModelread-onlymandatoryThe controller model of the Power System.
1.3.6.1.4.1.13400.2.8.2.1.2ScalarpsIdentFirmwareRevisionread-onlymandatoryThe firmware revision of the controller of the Power System.
1.3.6.1.4.1.13400.2.8.2.1.3ScalarpsIdentFactoryread-onlymandatoryThe name of the Power System manufacturer.
1.3.6.1.4.1.13400.2.8.3NodecommunicationResumedINFORMATION: Communication with the Power System Resumed.
1.3.6.1.4.1.13400.2.8.3NodepsSpecial
1.3.6.1.4.1.13400.2.8.3.1Nodepsm-a
1.3.6.1.4.1.13400.2.8.3.1.2NodepsBattery
1.3.6.1.4.1.13400.2.8.3.1.2.1ScalarpsBatteryVoltageread-onlymandatoryThe voltage of battery in 0.1 VDC.
1.3.6.1.4.1.13400.2.8.3.1.2.2ScalarpsBatteryCurrentread-onlymandatoryThe total current of the batteries in 0.1 ADC.
1.3.6.1.4.1.13400.2.8.3.1.2.3ScalarpsBatteryTemperatureread-onlymandatoryThe temperature around the battery in 0.1 Celsius degree.
1.3.6.1.4.1.13400.2.8.3.1.3NodepsInput
1.3.6.1.4.1.13400.2.8.3.1.3.1ScalarpsInputLineAVoltageread-onlymandatoryThe AC line A voltage in 0.1 VAC.
1.3.6.1.4.1.13400.2.8.3.1.3.2ScalarpsInputLineBVoltageread-onlymandatoryThe AC line B voltage in 0.1 VAC.
1.3.6.1.4.1.13400.2.8.3.1.3.3ScalarpsInputLineCVoltageread-onlymandatoryThe AC line C voltage in 0.1 VAC.
1.3.6.1.4.1.13400.2.8.3.1.4NodepsOutput
1.3.6.1.4.1.13400.2.8.3.1.4.1ScalarpsOutputVoltageread-onlymandatoryThe DC voltage of the Power System in 0.1 VDC.
1.3.6.1.4.1.13400.2.8.3.1.4.2ScalarpsOutputCurrentread-onlymandatoryThe DC current of the Power System in 0.1 ADC.
1.3.6.1.4.1.13400.2.8.3.1.5NodepsStatus
1.3.6.1.4.1.13400.2.8.3.1.5.1ScalarpsStatusAlarmread-onlymandatoryThe alarm status of the Power System.
1.3.6.1.4.1.13400.2.8.3.1.5.2ScalarpsStatusCommunicationread-onlymandatoryThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
1.3.6.1.4.1.13400.2.8.3.1.5.3ScalarpsStatusControlModeread-onlymandatoryThe AUTO/MANUAL control mode of the Power System.
1.3.6.1.4.1.13400.2.8.3.1.5.4ScalarpsStatusChargingModeread-onlymandatoryThe status of battery charging, floatCharging(2), equalizeCharging(3), testing(4).
1.3.6.1.4.1.13400.2.8.3.1.6NodepsTest
1.3.6.1.4.1.13400.2.8.3.1.7NodepsControl
1.3.6.1.4.1.13400.2.8.3.1.8NodepsConfig
1.3.6.1.4.1.13400.2.8.3.2Nodepsm-a9
1.3.6.1.4.1.13400.2.8.4NodeacFailSEVERE: AC Power failed.
1.3.6.1.4.1.13400.2.8.4NodepsAlarm
1.3.6.1.4.1.13400.2.8.4.1ScalarpsAlarmPresentNumread-onlymandatoryThe present number of active alarams.
1.3.6.1.4.1.13400.2.8.4.2TablepsAlarmPresentTablenot-accessiblemandatoryA list of current alarms, The number of entries is given by the value of psAlarmPresentNum.
1.3.6.1.4.1.13400.2.8.4.2.1RowpsAlarmPresentEntrynot-accessiblemandatoryThe present alarms list.
1.3.6.1.4.1.13400.2.8.4.2.1.1ColumnpresentAlarmIndexread-onlymandatoryThe index of the present alaram entry.
1.3.6.1.4.1.13400.2.8.4.2.1.2ColumnpresentAlarmTimeread-onlymandatoryThe time of the alarm generated, format as mm/dd/yyyy hh:mm:ss
1.3.6.1.4.1.13400.2.8.4.2.1.3ColumnpresentAlarmIdread-onlymandatoryThe alarm ID.
1.3.6.1.4.1.13400.2.8.4.2.1.4ColumnpresentAlarmNameread-onlymandatoryThe name of the alarm.
1.3.6.1.4.1.13400.2.8.4.2.1.5ColumnpresentAlaramLevelread-onlymandatoryThe alarm level.
1.3.6.1.4.1.13400.2.8.4.2008ScalartrapArgsStringread-onlymandatoryThis OID allows Power System traps to be sent with an octet string argument that may not be defined in the PSNA_PS_MIB. A get of this OID will return a NULL st…
1.3.6.1.4.1.13400.2.8.5NodeacResumedINFORMATION: AC power Resumed.
1.3.6.1.4.1.13400.2.8.6NodeacVoltageoutofRangeSEVERE: AC voltage is out of normal range.
1.3.6.1.4.1.13400.2.8.7NodeacVoltageNormalINFORMATION: AC voltage is normal.
1.3.6.1.4.1.13400.2.8.8NodedcVoltageoutofRangeSEVERE: DC voltage is out of normal range.
1.3.6.1.4.1.13400.2.8.9NodedcVoltageNormalINFORMATION: DC voltage is normal.
1.3.6.1.4.1.13400.2.8.10NodellvdSEVERE: Load low voltage disconnected.
1.3.6.1.4.1.13400.2.8.11NodellvdResumedINFORMATION: Load low voltage disconnection resumed.
1.3.6.1.4.1.13400.2.8.12NodeblvdSEVERE: Battery low voltage disconnected.
1.3.6.1.4.1.13400.2.8.13NodeblvdResumedINFORMATION: Battery low voltage disconnection resumed.
1.3.6.1.4.1.13400.2.8.14NodehighTemperatureSEVERE: The temperature around battery is too high.
1.3.6.1.4.1.13400.2.8.15NodehighTemperatureResumedINFORMATION: The temperature around battery is normal.
1.3.6.1.4.1.13400.2.8.16NodedcRouteDisconnectSEVERE: Some DC route(s) disconnected.
1.3.6.1.4.1.13400.2.8.17NodedcRouteDisconnectResumedINFORMATION: DC route(s) disconnection resumed.
1.3.6.1.4.1.13400.2.8.18NodebatteryRouteDisconnectSEVERE: The battery route(s) disconnected.
1.3.6.1.4.1.13400.2.8.19NodebatteryRouteDisconnectResumedINFORMATION: The battery route(s) disconnection resumed.
1.3.6.1.4.1.13400.2.8.20NodeacSPDfaultSEVERE: AC SPD fault.
1.3.6.1.4.1.13400.2.8.21NodeacSPDfaultResumedINFORMATION: AC SPD fault resumed.
1.3.6.1.4.1.13400.2.8.22NodeacCircuitBreakerfaultSEVERE: AC circuit breaker fault.
1.3.6.1.4.1.13400.2.8.23NodeacCircuitBreakerfaultResumedINFORMATION: AC circuit breaker fault resumed.
1.3.6.1.4.1.13400.2.8.24NodebatteryCurrentOverSEVERE: Battery current is over limit.
1.3.6.1.4.1.13400.2.8.25NodebatteryCurrentOverResumedINFORMATION: Battery current over resumed.
1.3.6.1.4.1.13400.2.8.26NoderectifierFaultSEVERE: Some Rectifier(s) fault.
1.3.6.1.4.1.13400.2.8.27NoderectifierFaultResumedINFORMATION: Rectifier(s) fault resumed.
1.3.6.1.4.1.13400.2.8.28NoderectifierProtectionSEVERE: Some Rectifier(s) protection.
1.3.6.1.4.1.13400.2.8.29NoderectifierProtectionResumedINFORMATION: Rectifier(s) protection resumed.
1.3.6.1.4.1.13400.2.8.30NoderectifierFanFaultSEVERE: Some Rectifier(s) fan fault.
1.3.6.1.4.1.13400.2.8.31NoderectifierFanFaultResumedINFORMATION: Rectifier(s) fan fault resumed.
1.3.6.1.4.1.13400.2.8.32NoderectifierOverTemperatureSEVERE: Some Rectifier(s) over temperature.
1.3.6.1.4.1.13400.2.8.33NoderectifierOverTemperatureResumedINFORMATION: Rectifier(s) over temperature resumed.
1.3.6.1.4.1.13400.2.8.34NodecommunicationACDLostSEVERE: Power System communication with ACD lost.
1.3.6.1.4.1.13400.2.8.35NodecommunicationACDResumedINFORMATION: Power System communication with ACD resumed.
1.3.6.1.4.1.13400.2.8.36NodecommunicationDCDLostSEVERE: Power System communication with DCD lost.
1.3.6.1.4.1.13400.2.8.37NodecommunicationDCDResumedINFORMATION: Power System communication with DCD resumed.
1.3.6.1.4.1.13400.2.8.38NodecommunicationRectifierLostSEVERE: Power System communication with rectifier lost.
1.3.6.1.4.1.13400.2.8.39NodecommunicationRectifierResumedINFORMATION: Power System communication with rectifier resumed.
1.3.6.1.4.1.13400.2.8.40NodedcdcFaultSEVERE: DC/DC convertor fault.
1.3.6.1.4.1.13400.2.8.41NodedcdcFaultResumedINFORMATION: DC/DC convertor fault resumed.
Type Definitions
NameSyntaxStatusDescription
DisplayStringOCTET STRING