MIB Viewer

RLE-FALCON-MIB

350 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.3184Noderle
1.3.6.1.4.1.3184.1Nodeproducts
1.3.6.1.4.1.3184.1.1Nodefalcon
1.3.6.1.4.1.3184.1.1.1NodefalconMIB
1.3.6.1.4.1.3184.1.1.1.1NodefalconIdent
1.3.6.1.4.1.3184.1.1.1.1.1ScalarfalconIdentManufacturerread-onlymandatoryThe Monitor Control Unit manufacturer.
1.3.6.1.4.1.3184.1.1.1.1.2ScalarfalconIdentModelread-onlymandatoryThe Monitor Control Unit Model designation.
1.3.6.1.4.1.3184.1.1.1.1.3ScalarfalconIdentSoftwareVersionread-onlymandatoryThe falcon SNMP Agent software version.
1.3.6.1.4.1.3184.1.1.1.1.4ScalarfalconIdentSpecificread-onlymandatoryA reference to MIB definitions specific to the particular Monitor Unit being managed. This object is used to locate the product-specific MIB for this device. I…
1.3.6.1.4.1.3184.1.1.1.2NodefalconSystem
1.3.6.1.4.1.3184.1.1.1.2.1ScalarfalconClockread-writemandatoryThe falcon internal clock settings. Displayed as MM/DD/YY HH:MM:SS
1.3.6.1.4.1.3184.1.1.1.2.2ScalarfalconDoorAlarmBypassread-writemandatoryThe falcon door alarm bypass switch. This allows the alarm to be bypassed upon valid keypad access. Zero disables this, or use 1 thru 8 for the corresponding f…
1.3.6.1.4.1.3184.1.1.1.2.3NodefalconKeypad
1.3.6.1.4.1.3184.1.1.1.2.3.1ScalarfalconKeypadCode1read-writemandatoryThe falcon keypad access code for user #1. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.2ScalarfalconKeypadName1read-writemandatoryThe falcon keypad access name for user #1. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.3ScalarfalconKeypadCode2read-writemandatoryThe falcon keypad access code for user #2. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.4ScalarfalconKeypadName2read-writemandatoryThe falcon keypad access name for user #2. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.5ScalarfalconKeypadCode3read-writemandatoryThe falcon keypad access code for user #3. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.6ScalarfalconKeypadName3read-writemandatoryThe falcon keypad access name for user #3. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.7ScalarfalconKeypadCode4read-writemandatoryThe falcon keypad access code for user #4. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.8ScalarfalconKeypadName4read-writemandatoryThe falcon keypad access name for user #4. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.9ScalarfalconKeypadCode5read-writemandatoryThe falcon keypad access code for user #5. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.10ScalarfalconKeypadName5read-writemandatoryThe falcon keypad access name for user #5. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.11ScalarfalconKeypadCode6read-writemandatoryThe falcon keypad access code for user #6. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.12ScalarfalconKeypadName6read-writemandatoryThe falcon keypad access name for user #6. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.13ScalarfalconKeypadCode7read-writemandatoryThe falcon keypad access code for user #7. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.14ScalarfalconKeypadName7read-writemandatoryThe falcon keypad access name for user #7. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.15ScalarfalconKeypadCode8read-writemandatoryThe falcon keypad access code for user #8. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.16ScalarfalconKeypadName8read-writemandatoryThe falcon keypad access name for user #8. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.17ScalarfalconKeypadCode9read-writemandatoryThe falcon keypad access code for user #9. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.18ScalarfalconKeypadName9read-writemandatoryThe falcon keypad access name for user #9. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.19ScalarfalconKeypadCode10read-writemandatoryThe falcon keypad access code for user #10. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.20ScalarfalconKeypadName10read-writemandatoryThe falcon keypad access name for user #10. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.21ScalarfalconKeypadCode11read-writemandatoryThe falcon keypad access code for user #11. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.22ScalarfalconKeypadName11read-writemandatoryThe falcon keypad access name for user #11. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.23ScalarfalconKeypadCode12read-writemandatoryThe falcon keypad access code for user #12. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.24ScalarfalconKeypadName12read-writemandatoryThe falcon keypad access name for user #12. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.25ScalarfalconKeypadCode13read-writemandatoryThe falcon keypad access code for user #13. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.26ScalarfalconKeypadName13read-writemandatoryThe falcon keypad access name for user #13. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.27ScalarfalconKeypadCode14read-writemandatoryThe falcon keypad access code for user #14. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.28ScalarfalconKeypadName14read-writemandatoryThe falcon keypad access name for user #14. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.29ScalarfalconKeypadCode15read-writemandatoryThe falcon keypad access code for user #15. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.30ScalarfalconKeypadName15read-writemandatoryThe falcon keypad access name for user #15. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.31ScalarfalconKeypadCode16read-writemandatoryThe falcon keypad access code for user #16. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.32ScalarfalconKeypadName16read-writemandatoryThe falcon keypad access name for user #16. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.33ScalarfalconKeypadCode17read-writemandatoryThe falcon keypad access code for user #17. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.34ScalarfalconKeypadName17read-writemandatoryThe falcon keypad access name for user #17. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.35ScalarfalconKeypadCode18read-writemandatoryThe falcon keypad access code for user #18. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.36ScalarfalconKeypadName18read-writemandatoryThe falcon keypad access name for user #18. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.37ScalarfalconKeypadCode19read-writemandatoryThe falcon keypad access code for user #19. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.38ScalarfalconKeypadName19read-writemandatoryThe falcon keypad access name for user #19. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.3.39ScalarfalconKeypadCode20read-writemandatoryThe falcon keypad access code for user #20. This can be up to six numberic characters.
1.3.6.1.4.1.3184.1.1.1.2.3.40ScalarfalconKeypadName20read-writemandatoryThe falcon keypad access name for user #20. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.1.1.2.4ScalarfalconInputVoltageread-onlymandatoryThe falcon input voltage (DC Power).
1.3.6.1.4.1.3184.1.1.1.2.5ScalarfalconOnBatteryread-writemandatoryThe state of use of the On Battery Alarm. When the State is set to installed(1), the On Battery and Low Battery alarms are enabled. This variable is stored in …
1.3.6.1.4.1.3184.1.1.1.2.6ScalarfalconLowBatteryThresholdread-writemandatoryThe low voltage trip point for the low battery alarm. When the input voltage goes below this voltage, the Low Battery alarm is set. This variable is stored in …
1.3.6.1.4.1.3184.1.1.1.2.7ScalarfalconAnalogAverageread-writemandatoryThis is the analog averaging duration in seconds. The analog input readings are averaged for this time period before updating. This value must be set to 1,2,3,…
1.3.6.1.4.1.3184.1.1.1.3NodefalconInputs
1.3.6.1.4.1.3184.1.1.1.3.1NodefalconInput1
1.3.6.1.4.1.3184.1.1.1.3.1.1ScalarfalconInput1Stateread-writemandatoryThe state of use of Input Number 1. When a sensor is connected to Input 1 set State to installed(2) to indicate that the value of falconReading1 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.1.2ScalarfalconInput1Readingread-onlymandatoryThe reading for sensor 1. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.1.3ScalarfalconInput1Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 1 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.1.4ScalarfalconInput1Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 1 to obtain the value of the Input1…
1.3.6.1.4.1.3184.1.1.1.3.1.5ScalarfalconInput1Labelread-writemandatoryA user-defined text string associated with Input Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.1.6ScalarfalconInput1UOMread-writemandatoryA user-defined text string associated with Input Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.1.7ScalarfalconInput1HighLimit2read-writemandatoryWhen input 1 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 1. The HighLimit2 variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.1.8ScalarfalconInput1HighLimitread-writemandatoryWhen input 1 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 1. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.1.9ScalarfalconInput1LowLimitread-writemandatoryWhen input 1 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 1. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.1.10ScalarfalconInput1LowLimit2read-writemandatoryWhen input 1 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 1. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.1.11ScalarfalconInput1RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.1.12ScalarfalconInput1Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.1.13ScalarfalconInput1Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.2NodefalconInput2
1.3.6.1.4.1.3184.1.1.1.3.2.1ScalarfalconInput2Stateread-writemandatoryThe state of use of Input Number 2. When a sensor is connected to Input 2 set State to installed(2) to indicate that the value of falconReading2 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.2.2ScalarfalconInput2Readingread-onlymandatoryThe reading for sensor 2. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.2.3ScalarfalconInput2Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 2 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.2.4ScalarfalconInput2Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 2 to obtain the value of the Input2…
1.3.6.1.4.1.3184.1.1.1.3.2.5ScalarfalconInput2Labelread-writemandatoryA user-defined text string associated with Input Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.2.6ScalarfalconInput2UOMread-writemandatoryA user-defined text string associated with Input Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.2.7ScalarfalconInput2HighLimit2read-writemandatoryWhen input 2 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 2. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.2.8ScalarfalconInput2HighLimitread-writemandatoryWhen input 2 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 2. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.2.9ScalarfalconInput2LowLimitread-writemandatoryWhen input 2 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 2. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.2.10ScalarfalconInput2LowLimit2read-writemandatoryWhen input 2 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 2. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.2.11ScalarfalconInput2RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.2.12ScalarfalconInput2Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.2.13ScalarfalconInput2Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.3NodefalconInput3
1.3.6.1.4.1.3184.1.1.1.3.3.1ScalarfalconInput3Stateread-writemandatoryThe state of use of Input Number 3. When a sensor is connected to Input 3 set State to installed(2) to indicate that the value of falconReading3 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.3.2ScalarfalconInput3Readingread-onlymandatoryThe reading for sensor 3. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.3.3ScalarfalconInput3Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 3 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.3.4ScalarfalconInput3Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 3 to obtain the value of the Input3…
1.3.6.1.4.1.3184.1.1.1.3.3.5ScalarfalconInput3Labelread-writemandatoryA user-defined text string associated with Input Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.3.6ScalarfalconInput3UOMread-writemandatoryA user-defined text string associated with Input Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.3.7ScalarfalconInput3HighLimit2read-writemandatoryWhen input 3 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 3. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.3.8ScalarfalconInput3HighLimitread-writemandatoryWhen input 3 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 3. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.3.9ScalarfalconInput3LowLimitread-writemandatoryWhen input 3 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 3. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.3.10ScalarfalconInput3LowLimit2read-writemandatoryWhen input 3 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 3. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.3.11ScalarfalconInput3RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.3.12ScalarfalconInput3Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.3.13ScalarfalconInput3Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.4NodefalconInput4
1.3.6.1.4.1.3184.1.1.1.3.4.1ScalarfalconInput4Stateread-writemandatoryThe state of use of Input Number 4. When a sensor is connected to Input 4 set State to installed(2) to indicate that the value of falconReading4 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.4.2ScalarfalconInput4Readingread-onlymandatoryThe reading for sensor 4. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.4.3ScalarfalconInput4Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 4 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.4.4ScalarfalconInput4Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 4 to obtain the value of the Input4…
1.3.6.1.4.1.3184.1.1.1.3.4.5ScalarfalconInput4Labelread-writemandatoryA user-defined text string associated with Input Number 4. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.4.6ScalarfalconInput4UOMread-writemandatoryA user-defined text string associated with Input Number 4. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.4.7ScalarfalconInput4HighLimit2read-writemandatoryWhen input 4 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 4. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.4.8ScalarfalconInput4HighLimitread-writemandatoryWhen input 4 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 4. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.4.9ScalarfalconInput4LowLimitread-writemandatoryWhen input 4 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 4. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.4.10ScalarfalconInput4LowLimit2read-writemandatoryWhen input 4 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 4. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.4.11ScalarfalconInput4RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.4.12ScalarfalconInput4Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.4.13ScalarfalconInput4Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.5NodefalconInput5
1.3.6.1.4.1.3184.1.1.1.3.5.1ScalarfalconInput5Stateread-writemandatoryThe state of use of Input Number 5. When a sensor is connected to Input 5 set State to installed(2) to indicate that the value of falconReading4 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.5.2ScalarfalconInput5Readingread-onlymandatoryThe reading for sensor 5. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.5.3ScalarfalconInput5Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 5 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.5.4ScalarfalconInput5Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 5 to obtain the value of the Input5…
1.3.6.1.4.1.3184.1.1.1.3.5.5ScalarfalconInput5Labelread-writemandatoryA user-defined text string associated with Input Number 5. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.5.6ScalarfalconInput5UOMread-writemandatoryA user-defined text string associated with Input Number 5. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.5.7ScalarfalconInput5HighLimit2read-writemandatoryWhen input 5 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 5. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.5.8ScalarfalconInput5HighLimitread-writemandatoryWhen input 5 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 5. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.5.9ScalarfalconInput5LowLimitread-writemandatoryWhen input 5 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 5. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.5.10ScalarfalconInput5LowLimit2read-writemandatoryWhen input 5 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 5. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.5.11ScalarfalconInput5RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.5.12ScalarfalconInput5Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.5.13ScalarfalconInput5Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.6NodefalconInput6
1.3.6.1.4.1.3184.1.1.1.3.6.1ScalarfalconInput6Stateread-writemandatoryThe state of use of Input Number 6. When a sensor is connected to Input 6 set State to installed(2) to indicate that the value of falconReading6 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.6.2ScalarfalconInput6Readingread-onlymandatoryThe reading for sensor 6. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.6.3ScalarfalconInput6Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 6 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.6.4ScalarfalconInput6Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 6 to obtain the value of the Input6…
1.3.6.1.4.1.3184.1.1.1.3.6.5ScalarfalconInput6Labelread-writemandatoryA user-defined text string associated with Input Number 6. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.6.6ScalarfalconInput6UOMread-writemandatoryA user-defined text string associated with Input Number 6. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.6.7ScalarfalconInput6HighLimit2read-writemandatoryWhen input 6 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 6. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.6.8ScalarfalconInput6HighLimitread-writemandatoryWhen input 6 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 6. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.6.9ScalarfalconInput6LowLimitread-writemandatoryWhen input 6 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 6. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.6.10ScalarfalconInput6LowLimit2read-writemandatoryWhen input 6 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 6. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.6.11ScalarfalconInput6RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.6.12ScalarfalconInput6Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.6.13ScalarfalconInput6Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.7NodefalconInput7
1.3.6.1.4.1.3184.1.1.1.3.7.1ScalarfalconInput7Stateread-writemandatoryThe state of use of Input Number 7. When a sensor is connected to Input 7 set State to installed(2) to indicate that the value of falconReading4 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.7.2ScalarfalconInput7Readingread-onlymandatoryThe reading for sensor 7. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.7.3ScalarfalconInput7Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 7 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.7.4ScalarfalconInput7Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 7 to obtain the value of the Input7…
1.3.6.1.4.1.3184.1.1.1.3.7.5ScalarfalconInput7Labelread-writemandatoryA user-defined text string associated with Input Number 7. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.7.6ScalarfalconInput7UOMread-writemandatoryA user-defined text string associated with Input Number 7. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.7.7ScalarfalconInput7HighLimit2read-writemandatoryWhen input 7 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 7. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.7.8ScalarfalconInput7HighLimitread-writemandatoryWhen input 7 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 7. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.7.9ScalarfalconInput7LowLimitread-writemandatoryWhen input 7 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 7. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.7.10ScalarfalconInput7LowLimit2read-writemandatoryWhen input 7 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 7. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.7.11ScalarfalconInput7RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.7.12ScalarfalconInput7Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.7.13ScalarfalconInput7Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.8NodefalconInput8
1.3.6.1.4.1.3184.1.1.1.3.8.1ScalarfalconInput8Stateread-writemandatoryThe state of use of Input Number 8. When a sensor is connected to Input 8 set State to installed(2) to indicate that the value of falconReading8 is valid. When…
1.3.6.1.4.1.3184.1.1.1.3.8.2ScalarfalconInput8Readingread-onlymandatoryThe reading for sensor 8. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.8.3ScalarfalconInput8Gainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 8 to obtain the value of the Input…
1.3.6.1.4.1.3184.1.1.1.3.8.4ScalarfalconInput8Offsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 8 to obtain the value of the Input8…
1.3.6.1.4.1.3184.1.1.1.3.8.5ScalarfalconInput8Labelread-writemandatoryA user-defined text string associated with Input Number 8. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.8.6ScalarfalconInput8UOMread-writemandatoryA user-defined text string associated with Input Number 8. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.8.7ScalarfalconInput8HighLimit2read-writemandatoryWhen input 8 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 8. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.8.8ScalarfalconInput8HighLimitread-writemandatoryWhen input 8 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 8. The HighLimit variable is stored in non-vola…
1.3.6.1.4.1.3184.1.1.1.3.8.9ScalarfalconInput8LowLimitread-writemandatoryWhen input 8 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 8. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.8.9ScalarfalconInput8RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.8.10ScalarfalconInput8Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.8.10ScalarfalconInput8LowLimit2read-writemandatoryWhen input 8 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 8. The LowLimit variable is stored in non-vol…
1.3.6.1.4.1.3184.1.1.1.3.8.11ScalarfalconInput8Hysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in…
1.3.6.1.4.1.3184.1.1.1.3.25NodefalconInput9
1.3.6.1.4.1.3184.1.1.1.3.25.1ScalarfalconInput9Stateread-writemandatoryThe state of use of Input Number 9. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.25.2ScalarfalconInput9Readingread-onlymandatoryThe reading for input 9. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.25.3ScalarfalconInput9Labelread-writemandatoryA user-defined text string associated with Input Number 9. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.25.4ScalarfalconInput9RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.25.5ScalarfalconInput9Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.26NodefalconInput10
1.3.6.1.4.1.3184.1.1.1.3.26.1ScalarfalconInput10Stateread-writemandatoryThe state of use of Input Number 10. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.26.2ScalarfalconInput10Readingread-onlymandatoryThe reading for input 10. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.26.3ScalarfalconInput10Labelread-writemandatoryA user-defined text string associated with Input Number 10. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.26.4ScalarfalconInput10RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.26.5ScalarfalconInput10Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.27NodefalconInput11
1.3.6.1.4.1.3184.1.1.1.3.27.1ScalarfalconInput11Stateread-writemandatoryThe state of use of Input Number 11. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.27.2ScalarfalconInput11Readingread-onlymandatoryThe reading for input 11. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.27.3ScalarfalconInput11Labelread-writemandatoryA user-defined text string associated with Input Number 11. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.27.4ScalarfalconInput11RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.27.5ScalarfalconInput11Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.28NodefalconInput12
1.3.6.1.4.1.3184.1.1.1.3.28.1ScalarfalconInput12Stateread-writemandatoryThe state of use of Input Number 12. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.28.2ScalarfalconInput12Readingread-onlymandatoryThe reading for input 12. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.28.3ScalarfalconInput12Labelread-writemandatoryA user-defined text string associated with Input Number 12. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.28.4ScalarfalconInput12RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.28.5ScalarfalconInput12Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.29NodefalconInput13
1.3.6.1.4.1.3184.1.1.1.3.29.1ScalarfalconInput13Stateread-writemandatoryThe state of use of Input Number 13. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.29.2ScalarfalconInput13Readingread-onlymandatoryThe reading for input 13. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.29.3ScalarfalconInput13Labelread-writemandatoryA user-defined text string associated with Input Number 13. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.29.4ScalarfalconInput13RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.29.5ScalarfalconInput13Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.30NodefalconInput14
1.3.6.1.4.1.3184.1.1.1.3.30.1ScalarfalconInput14Stateread-writemandatoryThe state of use of Input Number 14. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.30.2ScalarfalconInput14Readingread-onlymandatoryThe reading for input 14. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.30.3ScalarfalconInput14Labelread-writemandatoryA user-defined text string associated with Input Number 14. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.30.4ScalarfalconInput14RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.30.5ScalarfalconInput14Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.31NodefalconInput15
1.3.6.1.4.1.3184.1.1.1.3.31.1ScalarfalconInput15Stateread-writemandatoryThe state of use of Input Number 15. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.31.2ScalarfalconInput15Readingread-onlymandatoryThe reading for input 15. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.31.3ScalarfalconInput15Labelread-writemandatoryA user-defined text string associated with Input Number 15. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.31.4ScalarfalconInput15RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.31.50ScalarfalconInput15Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.32NodefalconInput16
1.3.6.1.4.1.3184.1.1.1.3.32.1ScalarfalconInput16Stateread-writemandatoryThe state of use of Input Number 16. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.32.2ScalarfalconInput16Readingread-onlymandatoryThe reading for input 16. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.32.3ScalarfalconInput16Labelread-writemandatoryA user-defined text string associated with Input Number 16. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.32.4ScalarfalconInput16RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.32.5ScalarfalconInput16Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.33NodefalconInput17
1.3.6.1.4.1.3184.1.1.1.3.33.1ScalarfalconInput17Stateread-writemandatoryThe state of use of Input Number 17. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.33.2ScalarfalconInput17Readingread-onlymandatoryThe reading for input 17. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.33.3ScalarfalconInput17Labelread-writemandatoryA user-defined text string associated with Input Number 17. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.33.4ScalarfalconInput17RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.33.5ScalarfalconInput17Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.34NodefalconInput18
1.3.6.1.4.1.3184.1.1.1.3.34.1ScalarfalconInput18Stateread-writemandatoryThe state of use of Input Number 18. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.34.2ScalarfalconInput18Readingread-onlymandatoryThe reading for input 18. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.34.3ScalarfalconInput18Labelread-writemandatoryA user-defined text string associated with Input Number 18. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.34.4ScalarfalconInput18RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.34.5ScalarfalconInput18Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.35NodefalconInput19
1.3.6.1.4.1.3184.1.1.1.3.35.1ScalarfalconInput19Stateread-writemandatoryThe state of use of Input Number 19. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.35.2ScalarfalconInput19Readingread-onlymandatoryThe reading for input 19. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.35.3ScalarfalconInput19Labelread-writemandatoryA user-defined text string associated with Input Number 19. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.35.4ScalarfalconInput19RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.35.5ScalarfalconInput19Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.3.36NodefalconInput20
1.3.6.1.4.1.3184.1.1.1.3.36.1ScalarfalconInput20Stateread-writemandatoryThe state of use of Input Number 20. This variable is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.36.2ScalarfalconInput20Readingread-onlymandatoryThe reading for input 20. The reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.1.1.3.36.3ScalarfalconInput20Labelread-writemandatoryA user-defined text string associated with Input Number 20. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.3.36.4ScalarfalconInput20RlyControlread-writemandatoryThe control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2…
1.3.6.1.4.1.3184.1.1.1.3.36.5ScalarfalconInput20Delayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile…
1.3.6.1.4.1.3184.1.1.1.4NodefalconOutputs
1.3.6.1.4.1.3184.1.1.1.4.1NodefalconRelay1
1.3.6.1.4.1.3184.1.1.1.4.1.1ScalarfalconRelay1Stateread-writemandatoryThe state of use of Relay Number 1. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the k…
1.3.6.1.4.1.3184.1.1.1.4.1.2ScalarfalconRelay1Statusread-onlymandatoryThe current status for relay 1.
1.3.6.1.4.1.3184.1.1.1.4.1.3ScalarfalconRelay1Labelread-writemandatoryA user-defined text string associated with Relay Number 1. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.4.1.4ScalarfalconRelay1Timeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.1.1.4.2NodefalconRelay2
1.3.6.1.4.1.3184.1.1.1.4.2.1ScalarfalconRelay2Stateread-writemandatoryThe state of use of Relay Number 2. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the k…
1.3.6.1.4.1.3184.1.1.1.4.2.2ScalarfalconRelay2Statusread-onlymandatoryThe current status for relay 2.
1.3.6.1.4.1.3184.1.1.1.4.2.3ScalarfalconRelay2Labelread-writemandatoryA user-defined text string associated with Relay Number 2. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.4.2.4ScalarfalconRelay2Timeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.1.1.4.3NodefalconRelay3
1.3.6.1.4.1.3184.1.1.1.4.3.1ScalarfalconRelay3Stateread-writemandatoryThe state of use of Relay Number 3. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the k…
1.3.6.1.4.1.3184.1.1.1.4.3.2ScalarfalconRelay3Statusread-onlymandatoryThe current status for relay 3.
1.3.6.1.4.1.3184.1.1.1.4.3.3ScalarfalconRelay3Labelread-writemandatoryA user-defined text string associated with Relay Number 3. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.4.3.4ScalarfalconRelay3Timeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.1.1.4.4NodefalconRelay4
1.3.6.1.4.1.3184.1.1.1.4.4.1ScalarfalconRelay4Stateread-writemandatoryThe state of use of Relay Number 4. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the k…
1.3.6.1.4.1.3184.1.1.1.4.4.2ScalarfalconRelay4Statusread-onlymandatoryThe current status for relay 4.
1.3.6.1.4.1.3184.1.1.1.4.4.3ScalarfalconRelay4Labelread-writemandatoryA user-defined text string associated with Relay Number 4. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.4.4.4ScalarfalconRelay4Timeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.1.1.4.5NodefalconRelay5
1.3.6.1.4.1.3184.1.1.1.4.5.1ScalarfalconRelay5Stateread-writemandatoryThe state of use of Relay Number 5. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the k…
1.3.6.1.4.1.3184.1.1.1.4.5.2ScalarfalconRelay5Statusread-onlymandatoryThe current status for relay 5.
1.3.6.1.4.1.3184.1.1.1.4.5.3ScalarfalconRelay5Labelread-writemandatoryA user-defined text string associated with Relay Number 5. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.4.5.4ScalarfalconRelay5Timeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.1.1.4.6NodefalconRelay6
1.3.6.1.4.1.3184.1.1.1.4.6.1ScalarfalconRelay6Stateread-writemandatoryThe state of use of Relay Number 6. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the k…
1.3.6.1.4.1.3184.1.1.1.4.6.2ScalarfalconRelay6Statusread-onlymandatoryThe current status for relay 6.
1.3.6.1.4.1.3184.1.1.1.4.6.3ScalarfalconRelay6Labelread-writemandatoryA user-defined text string associated with Relay Number 6. The text string is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.4.6.4ScalarfalconRelay6Timeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.1.1.5NodefalconAlarms
1.3.6.1.4.1.3184.1.1.1.5.1ScalarfalconAlarmsPresentread-onlycurrentThe present number of active alarm conditions.
1.3.6.1.4.1.3184.1.1.1.5.2TablefalconAlarmTablenot-accessiblecurrentA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.3184.1.1.1.5.2.1RowfalconAlarmEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.3184.1.1.1.5.2.1.1ColumnfalconAlarmIdnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.3184.1.1.1.5.2.1.2ColumnfalconAlarmDescrread-onlycurrentA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.3184.1.1.1.5.3NodefalconWellKnownAlarms
1.3.6.1.4.1.3184.1.1.1.5.3.1IdentityfalconInput1HighAlarmcurrentThe reading for sensor 1 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.2IdentityfalconInput1LowAlarmcurrentThe reading for sensor 1 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.3IdentityfalconInput1High2AlarmcurrentThe reading for sensor 1 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.4IdentityfalconInput1Low2AlarmcurrentThe reading for sensor 1 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.5IdentityfalconInput2HighAlarmcurrentThe reading for sensor 2 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.6IdentityfalconInput2LowAlarmcurrentThe reading for sensor 2 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.7IdentityfalconInput2High2AlarmcurrentThe reading for sensor 2 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.8IdentityfalconInput2Low2AlarmcurrentThe reading for sensor 2 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.9IdentityfalconInput3HighAlarmcurrentThe reading for sensor 3 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.10IdentityfalconInput3LowAlarmcurrentThe reading for sensor 3 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.11IdentityfalconInput3High2AlarmcurrentThe reading for sensor 3 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.12IdentityfalconInput3Low2AlarmcurrentThe reading for sensor 3 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.13IdentityfalconInput4HighAlarmcurrentThe reading for sensor 4 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.14IdentityfalconInput4LowAlarmcurrentThe reading for sensor 4 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.15IdentityfalconInput4High2AlarmcurrentThe reading for sensor 4 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.16IdentityfalconInput4Low2AlarmcurrentThe reading for sensor 4 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.17IdentityfalconInput5HighAlarmcurrentThe reading for sensor 5 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.18IdentityfalconInput5LowAlarmcurrentThe reading for sensor 5 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.19IdentityfalconInput5High2AlarmcurrentThe reading for sensor 5 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.20IdentityfalconInput5Low2AlarmcurrentThe reading for sensor 5 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.21IdentityfalconInput6HighAlarmcurrentThe reading for sensor 6 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.22IdentityfalconInput6LowAlarmcurrentThe reading for sensor 6 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.23IdentityfalconInput6High2AlarmcurrentThe reading for sensor 6 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.24IdentityfalconInput6Low2AlarmcurrentThe reading for sensor 6 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.25IdentityfalconInput7HighAlarmcurrentThe reading for sensor 7 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.26IdentityfalconInput7LowAlarmcurrentThe reading for sensor 7 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.27IdentityfalconInput7High2AlarmcurrentThe reading for sensor 7 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.28IdentityfalconInput7Low2AlarmcurrentThe reading for sensor 7 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.29IdentityfalconInput8HighAlarmcurrentThe reading for sensor 8 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.30IdentityfalconInput8LowAlarmcurrentThe reading for sensor 8 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.31IdentityfalconInput8High2AlarmcurrentThe reading for sensor 8 has reached the high limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.32IdentityfalconInput8Low2AlarmcurrentThe reading for sensor 8 has reached the low limit value.
1.3.6.1.4.1.3184.1.1.1.5.3.81IdentityfalconInput1DigAlarmcurrentThe digital input 1 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.82IdentityfalconInput2DigAlarmcurrentThe digital input 2 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.83IdentityfalconInput3DigAlarmcurrentThe digital input 3 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.84IdentityfalconInput4DigAlarmcurrentThe digital input 4 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.85IdentityfalconInput5DigAlarmcurrentThe digital input 5 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.86IdentityfalconInput6DigAlarmcurrentThe digital input 6 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.87IdentityfalconInput7DigAlarmcurrentThe digital input 7 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.88IdentityfalconInput8DigAlarmcurrentThe digital input 8 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.89IdentityfalconInput9DigAlarmcurrentThe digital input 9 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.90IdentityfalconInput10DigAlarmcurrentThe digital input 10 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.91IdentityfalconInput11DigAlarmcurrentThe digital input 11 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.92IdentityfalconInput12DigAlarmcurrentThe digital input 12 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.93IdentityfalconInput13DigAlarmcurrentThe digital input 13 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.94IdentityfalconInput14DigAlarmcurrentThe digital input 14 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.95IdentityfalconInput15DigAlarmcurrentThe digital input 15 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.96IdentityfalconInput16DigAlarmcurrentThe digital input 16 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.97IdentityfalconInput17DigAlarmcurrentThe digital input 17 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.98IdentityfalconInput18DigAlarmcurrentThe digital input 18 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.99IdentityfalconInput19DigAlarmcurrentThe digital input 19 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.100IdentityfalconInput20DigAlarmcurrentThe digital input 20 has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.102IdentityfalconOnBatteryAlarmcurrentThe On Battery input has been activated.
1.3.6.1.4.1.3184.1.1.1.5.3.103IdentityfalconLowBatteryAlarmcurrentThe Faclon has detected a low battery condition.
1.3.6.1.4.1.3184.1.1.1.6NodefalconTraps
1.3.6.1.4.1.3184.1.1.1.6.1NodefalconAlarmEntryAddedAn AlarmEntryAdded Trap signifies that the a sensor reading has reached a high or low limit value.
1.3.6.1.4.1.3184.1.1.1.6.2NodefalconAlarmEntryRemovedAn AlarmEntryAdded Trap signifies that the a sensor reading has gone below the high limit value or above the low limit value.
1.3.6.1.4.1.3184.1.1.1.6.3NodefalconAccessGrantedAn falconAccessGranted Trap signifies that a valid key code sequence was processed by the falcon.
1.3.6.1.4.1.3184.1.1.1.6.4NodefalconAccessDeniedAn falconAccessedDenied Trap signifies that an invalid key code sequence was processed by the falcon.
1.3.6.1.4.1.3184.1.1.1.7NodefalconAlarmHistory
1.3.6.1.4.1.3184.1.1.1.7.1ScalarfalconAlarmHistoryEntriesread-onlycurrentThe present number of entries in the alarm history.
1.3.6.1.4.1.3184.1.1.1.7.2ScalarfalconAlarmHistoryClearread-writemandatorySetting this value to ClearBuffer(1) will clear the alarm history buffer.
1.3.6.1.4.1.3184.1.1.1.7.3TablefalconAlarmHistoryTablenot-accessiblecurrentA list of alarm history table entries stored in the in the non-volatile memory. The table contains zero, one, or many rows at any moment, depending upon the nu…
1.3.6.1.4.1.3184.1.1.1.7.3.1RowfalconAlarmHistoryEntrynot-accessiblecurrentAn entry containing information applicable to a particular alarm history entry.
1.3.6.1.4.1.3184.1.1.1.7.3.1.1ColumnfalconAlarmHistoryIdnot-accessiblecurrentA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.3184.1.1.1.7.3.1.2ColumnfalconAlarmHistoryTextread-onlycurrentA text desciption of the alarm history entry. Each of the strings will have the following format, AHxxx-id-type-timestamp label xxx = number entry in the table…
1.3.6.1.4.1.3184.1.1.1.8NodefalconTrapSettings
1.3.6.1.4.1.3184.1.1.1.8.1ScalarfalconPersistantTrapsread-writemandatoryThe number of minutes between persistant traps. Set this to 0 to turn off persistant traps. This value is stored in non-volatile memory.
1.3.6.1.4.1.3184.1.1.1.8.2ScalarfalconAlarmAcknowledgeread-writemandatorySetting this value to AcknowledgeAlarms(1) will stop the falcon from sending persistant traps and dial out sequences.
1.3.6.1.4.1.3184.1.1.3Nodefalcon8124