TOSHIBAUPS-MIB
474 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises Gauge32 IpAddress |
| SNMPv2-TC | AutonomousType DisplayString TestAndIncr TimeInterval TimeStamp |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.186 | Nodetoshiba | |||
| 1.3.6.1.4.1.186.1 | Nodeequ | |||
| 1.3.6.1.4.1.186.1.19 | NodeequUPS | |||
| 1.3.6.1.4.1.186.1.19.2 | NodeticUPS | |||
| 1.3.6.1.4.1.186.1.19.2.3 | Nodermti3 | |||
| 1.3.6.1.4.1.186.1.19.2.3.1 | NodeupsIdent | |||
| 1.3.6.1.4.1.186.1.19.2.3.1 | NodeupsTrapFault | Fault: One or more fault reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.1.1 | ScalarupsIdentManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.186.1.19.2.3.1.2 | ScalarupsIdentTypeform | read-only | mandatory | The UPS Typeform. |
| 1.3.6.1.4.1.186.1.19.2.3.1.3 | ScalarupsIdentSerialNumber | read-only | mandatory | The UPS Serial Number. |
| 1.3.6.1.4.1.186.1.19.2.3.1.4 | ScalarupsIdentMainFirmwareVersion | read-only | mandatory | The UPS firmware version of the main controller. |
| 1.3.6.1.4.1.186.1.19.2.3.1.5 | ScalarupsIdentMainBootSectorVersion | read-only | mandatory | The UPS boot sector version of the main controller. |
| 1.3.6.1.4.1.186.1.19.2.3.1.6 | ScalarupsIdentMainBootLoaderVersion | read-only | mandatory | The UPS Boot Loader version of the main controller. |
| 1.3.6.1.4.1.186.1.19.2.3.1.7 | ScalarupsIdentJobNumber | read-only | mandatory | The UPS Job Number. |
| 1.3.6.1.4.1.186.1.19.2.3.1.8 | ScalarupsIdentTestPerson | read-only | mandatory | The test person. |
| 1.3.6.1.4.1.186.1.19.2.3.1.9 | ScalarupsIdentTestDate | read-only | mandatory | The test date displayed as YYYYMMDD format. |
| 1.3.6.1.4.1.186.1.19.2.3.1.10 | ScalarupsIdentHardwareBuildDate | read-only | mandatory | The date that the UPS was built in YYYYMMDD format. |
| 1.3.6.1.4.1.186.1.19.2.3.1.11 | ScalarupsIdentEEPROMVersion | read-only | mandatory | The UPS Main controller's EEPROM version. |
| 1.3.6.1.4.1.186.1.19.2.3.1.12 | ScalarupsIdentSysName | read-write | mandatory | A string identifying the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.1.13 | ScalarupsIdentAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.1.14 | ScalarupsIdentInstallationDate | read-write | mandatory | The UPS installation date in YYYYMMDD format. |
| 1.3.6.1.4.1.186.1.19.2.3.2 | NodeupsInput | |||
| 1.3.6.1.4.1.186.1.19.2.3.2 | NodeupsTrapFaultClear | Fault Clear: One or more fault reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.2.1 | ScalarupsInputPowerSupplyConfiguration | read-only | mandatory | This parameter summarizes the measured and collected data describing the input power supply. |
| 1.3.6.1.4.1.186.1.19.2.3.2.2 | ScalarupsInputNumLines | read-only | mandatory | The number of input lines utilized in this device. This variable indicates the number of rows in the input table. |
| 1.3.6.1.4.1.186.1.19.2.3.2.3 | TableupsInputTable | not-accessible | mandatory | A list of input table entries. The number of entries is given by the value of upsInputNumLine. |
| 1.3.6.1.4.1.186.1.19.2.3.2.3.1 | RowupsInputEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.186.1.19.2.3.2.3.1.1 | ColumnupsInputIndex | not-accessible | mandatory | The input line identifier |
| 1.3.6.1.4.1.186.1.19.2.3.2.3.1.2 | ColumnupsInputFrequency | read-only | mandatory | The present input frequency to the UPS system in 1/10 of Hz. |
| 1.3.6.1.4.1.186.1.19.2.3.2.3.1.3 | ColumnupsInputVoltage | read-only | mandatory | The input utility line voltage in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.3.2.3.1.4 | ColumnupsInputCurrent | read-only | mandatory | The magnitude of the present input Current in 1/10 RMS Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.2.4 | ScalarupsInputActivePower | read-only | mandatory | The UPS active power in Watt. -1 if value is invalid. |
| 1.3.6.1.4.1.186.1.19.2.3.2.5 | ScalarupsInputApparentPower | read-only | mandatory | The input apparent power in Volt-Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.2.6 | ScalarupsInputPowerFactor | read-only | mandatory | Ratio of actual power to apparent power. -1 if value is invalid. |
| 1.3.6.1.4.1.186.1.19.2.3.2.7 | TableupsInputRatedTable | not-accessible | mandatory | A list of input table entries. The number of entries is given by the value of upsInputNumLine. |
| 1.3.6.1.4.1.186.1.19.2.3.2.7.1 | RowupsInputRatedEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.186.1.19.2.3.2.7.1.1 | ColumnupsInputSlotIndex | not-accessible | mandatory | The input line identifier |
| 1.3.6.1.4.1.186.1.19.2.3.2.7.1.2 | ColumnupsInputRatedFrequency | read-only | mandatory | The present rated input frequency of the UPS system in 1/10 of Hz. |
| 1.3.6.1.4.1.186.1.19.2.3.2.7.1.3 | ColumnupsInputRatedVoltage | read-write | mandatory | The magnitude of the rated input voltage in RMS volts. This is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.2.7.1.4 | ColumnupsInputRatedCurrent | read-only | mandatory | The magnitude of the rated input current in 1/10 RMS Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.2.8 | ScalarupsInputOverVoltage | read-only | mandatory | This is the maximum limit of the input voltage before the UPS enters the over voltage state. |
| 1.3.6.1.4.1.186.1.19.2.3.2.9 | ScalarupsInputOverVoltageRecoverylevel | read-only | mandatory | The over voltage recovery level. It is the limit at which the UPS returns from over voltage state. |
| 1.3.6.1.4.1.186.1.19.2.3.2.10 | ScalarupsInputVoltagePercent | read-only | mandatory | The input voltage displayed as a percent. |
| 1.3.6.1.4.1.186.1.19.2.3.2.11 | ScalarupsInputCurrentPercent | read-only | mandatory | The input current displayed as a percent. |
| 1.3.6.1.4.1.186.1.19.2.3.2.12 | ScalarupsInputUnderVoltageDetectlevel | read-only | mandatory | The input under voltage detection level in RMS volt. |
| 1.3.6.1.4.1.186.1.19.2.3.2.13 | ScalarupsInputUnderVoltageRecoverylevel | read-only | mandatory | The input under voltage recovery level in RMS volt. |
| 1.3.6.1.4.1.186.1.19.2.3.2.14 | ScalarupsInputRatedActivePower | read-only | mandatory | The rated input active power in Watt. |
| 1.3.6.1.4.1.186.1.19.2.3.2.15 | ScalarupsInputFreqWithErr | read-write | mandatory | The input frequency configuration in 1/10 Hz when detection error occurred. This is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.3 | NodeupsOutput | |||
| 1.3.6.1.4.1.186.1.19.2.3.3 | NodeupsTrapOpenFuse | Fault: An open fuse reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.3.1 | ScalarupsOutputPowerSupplyConfiguration | read-only | mandatory | This parameter summarizes the measured and collected data describing the output power supply. |
| 1.3.6.1.4.1.186.1.19.2.3.3.2 | ScalarupsOutputNumLines | read-only | mandatory | The number of output lines utilized in this device. This variable indicates the number of rows in the output table. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3 | TableupsOutputTable | not-accessible | mandatory | A list of Output table entries. The number of entries is given by the value of upsOutputNumLines. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1 | RowupsOutputEntry | not-accessible | mandatory | An entry containing information applicable to a particular Output line. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1.1 | ColumnupsOutputIndex | not-accessible | mandatory | The Output line identifier. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1.2 | ColumnupsOutputFrequency | read-only | mandatory | The present output frequency of the UPS system in 1/10 of Hz. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1.3 | ColumnupsOutputVoltage | read-only | mandatory | The Output voltage in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1.4 | ColumnupsOutputCurrent | read-only | mandatory | The magnitude of the present output current in 1/10 RMS Amps. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1.5 | ColumnupsOutputActivePower | read-only | mandatory | The present output active power in Watt. |
| 1.3.6.1.4.1.186.1.19.2.3.3.3.1.6 | ColumnupsOutputApparentPower | read-only | mandatory | The output apparent power in Volt-Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.3.4 | ScalarupsOutputLoadPercentage | read-only | mandatory | The present UPS ouput load percentage which is current percent or active power whichever greater. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5 | TableupsOutputRatedTable | not-accessible | mandatory | A list of Output table entries. The number of entries is given by the value of upsOutputNumLines. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1 | RowupsOutputRatedEntry | not-accessible | mandatory | An entry containing information applicable to a particular Output line. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1.1 | ColumnupsOutputSlotIndex | not-accessible | mandatory | The Output line identifier. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1.2 | ColumnupsOutputRatedFrequency | read-only | mandatory | The present output rated frequency of the UPS system in 1/10 of Hz. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1.3 | ColumnupsOutputRatedVoltage | read-write | mandatory | The rated output voltage in RMS volts. This is set by the administrator |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1.4 | ColumnupsOutputRatedCurrent | read-only | mandatory | The output rated current in 1/10 RMS Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1.5 | ColumnupsOutputRatedActivePower | read-only | mandatory | The output rated active power in Watt. |
| 1.3.6.1.4.1.186.1.19.2.3.3.5.1.6 | ColumnupsOutputRatedApparentPower | read-only | mandatory | The output rated apparent power in Volt-Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.3.6 | ScalarupsOutputUndervoltagelevel | read-only | mandatory | This parameter displays the minimum allowable voltage before it falls into under voltage range. |
| 1.3.6.1.4.1.186.1.19.2.3.3.7 | ScalarupsOutputOverVoltagelevel | read-only | mandatory | This is the maximum limit of the output voltage before the UPS enters the over voltage state. |
| 1.3.6.1.4.1.186.1.19.2.3.3.8 | ScalarupsOutputFrequencySynchRange | read-only | mandatory | The allowable range for synchronizing output frequency in 1/10 of Hz. |
| 1.3.6.1.4.1.186.1.19.2.3.3.9 | ScalarupsOutputVoltageAdjust | read-write | mandatory | This parameter allows UPS to be configured to have adjustable voltages. This is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.3.10 | ScalarupsOutputRatedPowerFactor | read-only | mandatory | The rated output power factor. |
| 1.3.6.1.4.1.186.1.19.2.3.4 | NodeupsBypass | |||
| 1.3.6.1.4.1.186.1.19.2.3.4 | NodeupsTrapOpenFuseClear | Fault Clear: An open fuse reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.4.1 | ScalarupsBypassPowerSupplyConfiguration | read-only | mandatory | This parameter summarizes the measured and collected data describing the power supply into the bypass circuit. |
| 1.3.6.1.4.1.186.1.19.2.3.4.2 | ScalarupsBypassNumLine | read-only | mandatory | The number of bypass lines utilized in this device. This variable indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.186.1.19.2.3.4.3 | TableupsBypassTable | not-accessible | mandatory | A list of Bypass table entries. The number of entries is given by the value of upsBypassNumLines. |
| 1.3.6.1.4.1.186.1.19.2.3.4.3.1 | RowupsBypassEntry | not-accessible | mandatory | An entry containing information applicable to a particular line. |
| 1.3.6.1.4.1.186.1.19.2.3.4.3.1.1 | ColumnupsBypassIndex | not-accessible | mandatory | The Bypass line identifier. |
| 1.3.6.1.4.1.186.1.19.2.3.4.3.1.2 | ColumnupsBypassFrequency | read-only | mandatory | The present Bypass frequency of the UPS system in 1/10 of Hz of each phase. |
| 1.3.6.1.4.1.186.1.19.2.3.4.3.1.3 | ColumnupsBypassVoltage | read-only | mandatory | The Bypass utility line voltage in RMS volts. |
| 1.3.6.1.4.1.186.1.19.2.3.4.3.1.4 | ColumnupsBypassCurrent | read-only | mandatory | The magnitude of the present bypass Current in 1/10 RMS Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.4.4 | ScalarupsBypassApparentPower | read-only | mandatory | The Bypass Apparent power in Volt-Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.4.5 | ScalarupsBypassUnderVoltageDetectionlevel | read-only | mandatory | This parameter displays the minimum allowable voltage before it falls into bypass undervoltage range. |
| 1.3.6.1.4.1.186.1.19.2.3.4.6 | ScalarupsBypassUnderVoltageRecoverylevel | read-only | mandatory | This parameter displays the allowable voltage that it can recover from. |
| 1.3.6.1.4.1.186.1.19.2.3.4.7 | ScalarupsBypassOverVoltageDetectionlevel | read-only | mandatory | This parameter displays the maximum allowable voltage before it falls into over voltage range. |
| 1.3.6.1.4.1.186.1.19.2.3.4.8 | ScalarupsBypassOverVoltageRecoverylevel | read-only | mandatory | This parameter displays the allowable voltage that it can recover from. |
| 1.3.6.1.4.1.186.1.19.2.3.5 | NodeupsDCBus | |||
| 1.3.6.1.4.1.186.1.19.2.3.5 | NodeupsTrapCurrentLimitFault | Fault: A current limit fault reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.5.1 | ScalarupsDCBusTotalVoltage | read-only | mandatory | The DC Bus voltage in DC volts. |
| 1.3.6.1.4.1.186.1.19.2.3.5.2 | ScalarupsDCBusPositiveVoltage | read-only | mandatory | The DC Bus positive voltage in DC volts. |
| 1.3.6.1.4.1.186.1.19.2.3.5.3 | ScalarupsDCBusNegativeVoltage | read-only | mandatory | The DC Bus negative voltage in DC volts. |
| 1.3.6.1.4.1.186.1.19.2.3.5.4 | ScalarupsDCBusRatedVoltage | read-only | mandatory | The DC Bus rated voltage in DC volts. |
| 1.3.6.1.4.1.186.1.19.2.3.6 | NodeupsBattery | |||
| 1.3.6.1.4.1.186.1.19.2.3.6 | NodeupsTrapCurrentLimitFaultClear | Fault Clear: A current limit fault reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.6.1 | ScalarupsBatteryStatus | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time sufficient to handle the… |
| 1.3.6.1.4.1.186.1.19.2.3.6.2 | ScalarupsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whiche… |
| 1.3.6.1.4.1.186.1.19.2.3.6.3 | ScalarupsBatteryVoltage | read-only | mandatory | The magnitude of the present battery voltage in DC Volt. |
| 1.3.6.1.4.1.186.1.19.2.3.6.4 | ScalarupsBatteryDischargeCurrent | read-only | mandatory | The present battery discharge current in 1/10 DC Amp. |
| 1.3.6.1.4.1.186.1.19.2.3.6.5 | ScalarupsBatteryChargeStatus | read-only | mandatory | The UPS charger status. |
| 1.3.6.1.4.1.186.1.19.2.3.6.6 | ScalarupsBatteryNumberofDischarge | read-only | mandatory | This will increment when ups goes into backup mode which is longer than 10 seconds. |
| 1.3.6.1.4.1.186.1.19.2.3.6.7 | ScalarupsBatteryCalculatedShutdownVoltage | read-only | mandatory | The battery's shutdown voltage in DC Volt. |
| 1.3.6.1.4.1.186.1.19.2.3.6.8 | ScalarupsBatteryLifeRemaining | read-only | mandatory | The number of hours of UPS operation in the present environment until the batteries must be replaced. |
| 1.3.6.1.4.1.186.1.19.2.3.6.9 | ScalarupsBatteryRatedAmpereHour | read-only | mandatory | The battery capacity in Amp-Hour. |
| 1.3.6.1.4.1.186.1.19.2.3.6.10 | ScalarupsBatteryInSeries | read-only | mandatory | The number of batteries in each string connected in series. |
| 1.3.6.1.4.1.186.1.19.2.3.6.11 | ScalarupsBatteryInParallel | read-only | mandatory | The number of batteries connected in parallel. |
| 1.3.6.1.4.1.186.1.19.2.3.6.12 | ScalarupsBatteryInstallationDate | read-only | mandatory | The battery installation date in YYYYMMDD format. |
| 1.3.6.1.4.1.186.1.19.2.3.6.13 | ScalarupsBatteryVoltageShutdownLevel | read-only | mandatory | The UPS battery voltage shutdown level. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14 | TableupsBatteryExtTable | not-accessible | mandatory | A list of Battery table entries. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1 | RowupsBatteryExtEntry | not-accessible | mandatory | An entry containing information applicable to a particular Battery. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1.1 | ColumnupsBatteryExtIndex | not-accessible | mandatory | The Battery line identifier |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1.2 | ColumnupsBatteryExtInSeries | read-only | mandatory | Specifies the number of batteries in the external cabinet that are connected in series. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1.3 | ColumnupsBatteryExtInParallel | read-only | mandatory | Specifies the number of batteries in the external cabinet that are connected in parallel. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1.4 | ColumnupsBatteryExtRatedAmpereHour | read-only | mandatory | The external battery's capacity in Amp-Hour. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1.5 | ColumnupsBatteryExtCRate | read-only | mandatory | The external battery's C rate. |
| 1.3.6.1.4.1.186.1.19.2.3.6.14.1.6 | ColumnupsBatteryExtInstallDate | read-only | mandatory | The battery installation date in YYYYMMDD format. |
| 1.3.6.1.4.1.186.1.19.2.3.6.15 | ScalarupsBatteryLowBattLevel | read-only | mandatory | The low battery level of the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.6.16 | ScalarupsBatteryChargerOverVoltageDelay | read-only | mandatory | The UPS's charger over voltage detection delay in seconds. |
| 1.3.6.1.4.1.186.1.19.2.3.6.17 | ScalarupsBatteryCalcLBLevel | read-only | mandatory | The calculated low battery level. |
| 1.3.6.1.4.1.186.1.19.2.3.6.18 | ScalarupsBatteryCapacity | read-only | mandatory | The UPS battery capacity in percent. |
| 1.3.6.1.4.1.186.1.19.2.3.6.19 | ScalarupsBatteryRuntime | read-only | mandatory | The UPS battery runtime in minutes. It will return -1 or N/A if not available. |
| 1.3.6.1.4.1.186.1.19.2.3.7 | NodeupsStsCtlCfg | |||
| 1.3.6.1.4.1.186.1.19.2.3.7 | NodeupsTrapDCBusOverCurrent | Fault: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.7.1 | ScalarupsStsCtlCfgSystemTemperature | read-only | mandatory | The UPS system temperature in Celsius. |
| 1.3.6.1.4.1.186.1.19.2.3.7.2 | ScalarupsStsCtlCfgBatteryTemperature | read-only | mandatory | The UPS Battery temperature in Celsius. |
| 1.3.6.1.4.1.186.1.19.2.3.7.3 | ScalarupsStsCtlCfgPresentMode | read-only | mandatory | The present mode of the UPS system. |
| 1.3.6.1.4.1.186.1.19.2.3.7.4 | ScalarupsStsCtlCfgModeRequest | read-write | mandatory | The mode of the UPS system requested by the user. |
| 1.3.6.1.4.1.186.1.19.2.3.7.5 | ScalarupsStsCtlCfgModeTransitionTimer | read-write | mandatory | The timer upon whose expiration a mode transition will be attempted by the system. |
| 1.3.6.1.4.1.186.1.19.2.3.7.6 | ScalarupsStsCtlCfgEPOContactState | read-only | mandatory | The EPO contact state of the UPS system. |
| 1.3.6.1.4.1.186.1.19.2.3.7.7 | ScalarupsStsCtlCfgRunStopSwitchState | read-only | mandatory | The Run/Stop switch state of the UPS system. |
| 1.3.6.1.4.1.186.1.19.2.3.7.8 | ScalarupsStsCtlCfgServicePortCommStatus | read-only | mandatory | The service port communication status. |
| 1.3.6.1.4.1.186.1.19.2.3.7.9 | ScalarupsStsCtlCfgInternalCommStatus | read-only | mandatory | The internal communication status of the UPS system such as display panel. |
| 1.3.6.1.4.1.186.1.19.2.3.7.10 | ScalarupsStsCtlCfgSecurityLevel | read-write | mandatory | The current security level of the UPS system |
| 1.3.6.1.4.1.186.1.19.2.3.7.11 | ScalarupsStsCtlCfgPresentDate | read-write | mandatory | The present date of the UPS. This is configurable by Administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.7.12 | ScalarupsStsCtlCfgPresentTime | read-write | mandatory | The present time of the UPS. This is configurable by Administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.7.13 | ScalarupsStsCtlCfgPresentTimeStamp | read-only | mandatory | Present system timestamp. |
| 1.3.6.1.4.1.186.1.19.2.3.7.14 | ScalarupsStsCtlCfgEnableRMTIToControlMode | read-write | mandatory | Allow to enable or disable SNMP to control the UPS Shutdown and Online Mode. |
| 1.3.6.1.4.1.186.1.19.2.3.7.15 | ScalarupsStsCtlCfgEnableStartupDelay | read-write | mandatory | This delay timer, when enabled, will begin counting down at UPS startup immediately following a UPS shutdown by any means other than battery exhaustion. UPS ou… |
| 1.3.6.1.4.1.186.1.19.2.3.7.16 | ScalarupsStsCtlCfgStartUpDelayMode | read-write | mandatory | UPS mode into which the UPS will transition at the expiration of the Start-Up delay timer. |
| 1.3.6.1.4.1.186.1.19.2.3.7.17 | ScalarupsStsCtlCfgStartUpDelay | read-write | mandatory | When the timer is counting down, its changing value is reflected, otherwise its starting value is reported. |
| 1.3.6.1.4.1.186.1.19.2.3.7.18 | ScalarupsStsCtlCfgRemoteShutDownContactState | read-only | mandatory | The state of the Remote Contacts Shutdown Control. |
| 1.3.6.1.4.1.186.1.19.2.3.7.19 | ScalarupsStsCtlCfgRemoteShutdownContactMode | read-write | mandatory | The mode of the Remote Contacts Shutdown control. |
| 1.3.6.1.4.1.186.1.19.2.3.7.20 | ScalarupsStsCtlCfgEnableDryContactLANShutdown | read-write | mandatory | When enable, UPS will accept LAN signal request for UPS shutdown but only in accordance with restrictions of the following timer. |
| 1.3.6.1.4.1.186.1.19.2.3.7.21 | ScalarupsStsCtlCfgDryContactLANShutdownTimer | read-write | mandatory | Timer begins upon input power recovery and during its lifetime, allows the LAN input signal to affect a UPS Shutdown control. |
| 1.3.6.1.4.1.186.1.19.2.3.7.22 | ScalarupsStsCtlCfgDryContactOnBattDelay | read-write | mandatory | Time delay between actual event occurrence and dry contact closure to signal external devices of the event. |
| 1.3.6.1.4.1.186.1.19.2.3.7.23 | ScalarupsStsCtlCfgDryContactLowBattDelay | read-write | mandatory | Delay timer between actual event occurrence and dry contact closure to signal external devices of the event. |
| 1.3.6.1.4.1.186.1.19.2.3.7.24 | ScalarupsStsCtlCfgEnableStartupBattTest | read-write | mandatory | Forces a battery test when UPS starts. |
| 1.3.6.1.4.1.186.1.19.2.3.7.25 | ScalarupsStsCtlCfgEnableBatteryTest | read-write | mandatory | Allow to enable or disable battery test. |
| 1.3.6.1.4.1.186.1.19.2.3.7.26 | ScalarupsStsCtlCfgBatteryTestConditionStatus | read-only | mandatory | This notifies the user of the availability of the battery test feature. |
| 1.3.6.1.4.1.186.1.19.2.3.7.27 | ScalarupsStsCtlCfgMaxBatteryTestFreq | read-write | mandatory | This specified how often the battery test should occur. This is set by the administrator |
| 1.3.6.1.4.1.186.1.19.2.3.7.28 | ScalarupsStsCtlCfgEnableRestartAfterBattShutdown | read-write | mandatory | Mode set for UPS input power detection immediately after a shutdown while on batteries. This is set by the administrator. |
| 1.3.6.1.4.1.186.1.19.2.3.7.29 | ScalarupsStsCtlCfgRestartDelay | read-write | mandatory | Countdown begins only when UPS input power is restored immediately following a UPS Shutdown while on batteries. |
| 1.3.6.1.4.1.186.1.19.2.3.7.30 | ScalarupsStsCtlCfgEnableAutoTransferMode | read-write | mandatory | This feature allows the administrators to enable or to disable the auto transfer feature of the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.7.31 | ScalarupsStsCtlCfgAutoRetransferDelay | read-write | mandatory | Time period to wait after fault occurrence before attempting transfer back Online |
| 1.3.6.1.4.1.186.1.19.2.3.7.32 | ScalarupsStsCtlCfgServicePortCommSetting | read-write | mandatory | The UPS baud rate settings. |
| 1.3.6.1.4.1.186.1.19.2.3.7.33 | ScalarupsStsCtlCfgInvertRemoteShutdownLogic | read-write | mandatory | Remote Shutdown logic. |
| 1.3.6.1.4.1.186.1.19.2.3.7.34 | ScalarupsStsCtlCfgRestartMode | read-write | mandatory | Restart Mode. |
| 1.3.6.1.4.1.186.1.19.2.3.8 | NodeupsHistory | |||
| 1.3.6.1.4.1.186.1.19.2.3.8 | NodeupsTrapDCBusOverCurrentClear | Fault Clear: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.8.1 | ScalarupsHistorySysOperationTime | read-only | mandatory | The amount of time the UPS has been on. |
| 1.3.6.1.4.1.186.1.19.2.3.8.2 | ScalarupsHistoryInverterOperationTime | read-only | mandatory | The amount of time the UPS has been in On-Line Mode. |
| 1.3.6.1.4.1.186.1.19.2.3.8.3 | ScalarupsHistoryBackupOperationTime | read-only | mandatory | The amount of time the UPS has been in BackUp Mode. |
| 1.3.6.1.4.1.186.1.19.2.3.8.4 | ScalarupsHistoryLifetimeRemaining | read-only | mandatory | The remaining lifetime of the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.8.5 | ScalarupsHistoryHighestSystemTemp | read-only | mandatory | The highest system temperature of the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.8.6 | ScalarupsHistoryHighestBatteryTemp | read-only | mandatory | The highest battery temperature. |
| 1.3.6.1.4.1.186.1.19.2.3.8.7 | ScalarupsHistoryTotalNumInputUnderVolt | read-only | mandatory | Total number of times the UPS has entered under voltage state. |
| 1.3.6.1.4.1.186.1.19.2.3.8.8 | ScalarupsHistoryTotalNumOverload | read-only | mandatory | Total number of times the UPS has been overloaded. |
| 1.3.6.1.4.1.186.1.19.2.3.8.9 | ScalarupsHistoryTotalNumTest | read-only | mandatory | Total number of tests that has been conducted on the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.8.10 | ScalarupsHistoryTotalNumBackup | read-only | mandatory | Total number of times the UPS has been in Back-Up mode. |
| 1.3.6.1.4.1.186.1.19.2.3.8.11 | ScalarupsHistoryTotalNumFaults | read-only | mandatory | Total number of faults that has occurred on the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.8.12 | ScalarupsHistoryTotalNumOperationModeChange | read-only | mandatory | The number of mode changes that has occurred. |
| 1.3.6.1.4.1.186.1.19.2.3.8.13 | ScalarupsHistoryTotalNumWarnings | read-only | mandatory | The number of warnings that has occurred on the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.8.14 | ScalarupsHistoryTotalNumSystemSettingsChanged | read-only | mandatory | The number of times the System settings have been changed. |
| 1.3.6.1.4.1.186.1.19.2.3.8.15 | ScalarupsHistoryTotalNumResets | read-only | mandatory | The number of times the UPS has reset. |
| 1.3.6.1.4.1.186.1.19.2.3.9 | NodeupsDisplay | |||
| 1.3.6.1.4.1.186.1.19.2.3.9 | NodeupsTrapDCBusOverVoltage | Fault: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.9.1 | ScalarupsDisplayFirmwareVersion | read-only | mandatory | The firmware version of the display. |
| 1.3.6.1.4.1.186.1.19.2.3.9.2 | ScalarupsDisplayBootSectorVersion | read-only | mandatory | The boot sector version of the display. |
| 1.3.6.1.4.1.186.1.19.2.3.9.3 | ScalarupsDisplayBootLoaderVersion | read-only | mandatory | The boot loader version of the display. |
| 1.3.6.1.4.1.186.1.19.2.3.9.4 | ScalarupsDisplaySleepTimer | read-write | mandatory | The sleep timer for the display. |
| 1.3.6.1.4.1.186.1.19.2.3.9.5 | ScalarupsDisplayBuzzerMode | read-write | mandatory | Configures buzzer mode. |
| 1.3.6.1.4.1.186.1.19.2.3.9.6 | ScalarupsDisplayBuzzerStatus | read-only | mandatory | Shows the current state of the buzzer. |
| 1.3.6.1.4.1.186.1.19.2.3.9.7 | ScalarupsDisplayRMTIInstallDate | read-only | mandatory | The RMTI installation date. |
| 1.3.6.1.4.1.186.1.19.2.3.9.8 | ScalarupsDisplayRMTIInstallStatus | read-only | mandatory | Shows the installation status of the RMTI. |
| 1.3.6.1.4.1.186.1.19.2.3.9.9 | ScalarupsDisplayRMTIBaudRate | read-only | mandatory | Configures the baud rate. |
| 1.3.6.1.4.1.186.1.19.2.3.9.10 | ScalarupsDisplayRMTIDataLink | read-only | mandatory | Shows the data status of the RMTI. |
| 1.3.6.1.4.1.186.1.19.2.3.9.11 | ScalarupsDisplayRMTINetworkLink | read-only | mandatory | Shows the network status of the RMTI. |
| 1.3.6.1.4.1.186.1.19.2.3.10 | NodeupsAlarm | |||
| 1.3.6.1.4.1.186.1.19.2.3.10 | NodeupsTrapDCBusOverVoltageClear | Fault Clear: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.10.1 | ScalarupsAlarmsPresent | read-only | mandatory | The present number of active alarm conditions. |
| 1.3.6.1.4.1.186.1.19.2.3.10.2 | TableupsAlarmTable | not-accessible | mandatory | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is … |
| 1.3.6.1.4.1.186.1.19.2.3.10.2.1 | RowupsAlarmEntry | not-accessible | mandatory | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.186.1.19.2.3.10.2.1.1 | ColumnupsAlarmId | not-accessible | mandatory | An unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.186.1.19.2.3.10.2.1.2 | ColumnupsAlarmDescr | read-only | mandatory | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.186.1.19.2.3.10.2.1.3 | ColumnupsAlarmTime | read-only | mandatory | The value of upsConfigSystemTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed… |
| 1.3.6.1.4.1.186.1.19.2.3.10.3 | NodeupsWellKnownAlarms | |||
| 1.3.6.1.4.1.186.1.19.2.3.10.3.1 | ScalarupsAlarmFault | read-only | mandatory | Fault: One or more fault reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.2 | ScalarupsAlarmOpenFuse | read-only | mandatory | Fault: An open fuse reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.3 | ScalarupsAlarmCurrentLimitFault | read-only | mandatory | Fault: A current limit reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.4 | ScalarupsAlarmDCBusOverCurrent | read-only | mandatory | Fault: A DC bus overcurrent reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.5 | ScalarupsAlarmDCOverVoltage | read-only | mandatory | Fault: A DC bus overvoltage repoprted. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.6 | ScalarupsAlarmDCBusImbalance | read-only | mandatory | Fault: A DC bus imbalance reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.7 | ScalarupsAlarmOutputUnderVoltage | read-only | mandatory | Fault: An inverter output undervoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.8 | ScalarupsAlarmOutputOverVoltage | read-only | mandatory | Fault: An inverter output overvoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.9 | ScalarupsAlarmHeatSinkOverheat | read-only | mandatory | Fault: Heat sink or device overheat reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.10 | ScalarupsAlarmBypassOverload | read-only | mandatory | Fault: A bypass overload reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.11 | ScalarupsAlarmChargerOverVoltageFault | read-only | mandatory | Fault: Charger overvoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.12 | ScalarupsAlarmOutputOverCurrent | read-only | mandatory | Fault: A output overcurrent reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.13 | ScalarupsAlarmDCUnderVoltAtBoostUp | read-only | mandatory | Fault: A DC bus undervoltage reported during DC bus boost-up. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.14 | ScalarupsAlarmDCUnderVoltAtCharge | read-only | mandatory | Fault: A DC bus undervoltage during DC bus charging reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.15 | ScalarupsAlarmBypassOverheat | read-only | mandatory | Fault: A bypass Overheat reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.16 | ScalarupsAlarmResettableInverterOverload | read-only | mandatory | Fault: An inverter overload reported. It is resetable. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.17 | ScalarupsAlarmUnresettableInverterOverload | read-only | mandatory | Fault: An inverter overload reported. It is not resetable. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.18 | ScalarupsAlarmInputOverVoltage | read-only | mandatory | Warning: An input overvoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.19 | ScalarupsAlarmInputUnderVoltage | read-only | mandatory | Warning: An input undervoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.20 | ScalarupsAlarmInputFrequencyError | read-only | mandatory | Warning: An input frequency error reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.21 | ScalarupsAlarmBypassOverVoltage | read-only | mandatory | Warning: A bypass overvoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.22 | ScalarupsAlarmBypassUnderVoltage | read-only | mandatory | Warning: A bypass undervoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.23 | ScalarupsAlarmBypassFrequencyError | read-only | mandatory | Warning: An bypass frequency error reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.24 | ScalarupsAlarmDCBusUnderVoltAtBattTest | read-only | mandatory | Warning: A DC bus undervoltage reported during battery test |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.25 | ScalarupsAlarmBatteryLow | read-only | mandatory | Warning: A Low battery reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.26 | ScalarupsAlarmBatteryAtShutdownlevel | read-only | mandatory | Warning: A Battery shutdown voltage level reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.27 | ScalarupsAlarmReplaceBattery | read-only | mandatory | Warning: Batteries are in need of replacement. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.28 | ScalarupsAlarmChargerOverVoltageWarning | read-only | mandatory | Warning: Charger overvoltage reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.29 | ScalarupsAlarmBatteryTestFailed | read-only | mandatory | Warning: A battery test failed event reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.30 | ScalarupsAlarmBatteryDepleted | read-only | mandatory | Warning: A battery depleted event reported. It will not be able to support critical loads. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.31 | ScalarupsAlarmBatteryOverheat | read-only | mandatory | Warning: A Battery overheat reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.32 | ScalarupsAlarmSystemOverheat | read-only | mandatory | Warning: A system overheat reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.33 | ScalarupsAlarmOutputOverloadWarning | read-only | mandatory | Warning: An inverter output overload reported. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Loa… |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.34 | ScalarupsAlarmCurrentLimitWarning | read-only | mandatory | Warning: A current limit reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.35 | ScalarupsAlarmAsyncOperation | read-only | mandatory | Warning: An Asynchronous operation reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.36 | ScalarupsAlarmServiceUPS | read-only | mandatory | Warning: UPS is in need of service. Please contact authorized Toshiba service center for assistance. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.37 | ScalarupsAlarmBatteryNearExpiration | read-only | mandatory | Warning: Batteries are nearing the end of their expected lifetime. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.38 | ScalarupsAlarmBatteryExpired | read-only | mandatory | Warning: Batteries have reached their expected lifetime. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.39 | ScalarupsAlarmDisplayCableError | read-only | mandatory | Warning: A display cable error reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.40 | ScalarupsAlarmRemotEyeCommError | read-only | mandatory | Warning: A Communication error between the main control and the RemotEye reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.41 | ScalarupsAlarmRemotEyeUplinkCommError | read-only | mandatory | Warning: A communication error between the RemotEye III and the network reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.42 | ScalarupsAlarmServicePortCommError | read-only | mandatory | Warning: A communication error between the main controller and the service communication port reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.43 | ScalarupsAlarmDispCommError | read-only | mandatory | Warning: A communication error between the main controller and display controller reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.44 | ScalarupsAlarmSystemTestFailed | read-only | mandatory | Warning: A system test failed event reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.45 | ScalarupsAlarmBypassOn | read-only | mandatory | Warning: The UPS is in Stop (Bypass) mode |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.46 | ScalarupsAlarmPowerFailure | read-only | mandatory | Info: A power failure reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.47 | ScalarupsAlarmShutdownPending | read-only | mandatory | Info: An output shutdown in progress reported. Output will turn off after delay. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.48 | ScalarupsAlarmOutputOffAsRequested | read-only | mandatory | Info: An output shutdown mode requested. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.49 | ScalarupsAlarmOutputOff | read-only | mandatory | Info: An output off reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.50 | ScalarupsAlarmBatteryTestInProgress | read-only | mandatory | Info: A battery test in progress reported. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.51 | ScalarupsAlarmBatteryOn | read-only | mandatory | Info: The UPS is on Battery mode; it is supplying output power from its batteries. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.52 | ScalarupsAlarmEMDSensor1AlarmTriggered | read-only | mandatory | Info: EMD sensor 1 alarm is triggered. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.53 | ScalarupsAlarmEMDSensor2AlarmTriggered | read-only | mandatory | Info: EMD sensor 2 alarm is triggered. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.54 | ScalarupsAlarmEMDHumidityAtLowCriticalPoint | read-only | mandatory | Info: EMD humidity is at low critical point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.55 | ScalarupsAlarmEMDHumidityAtHighCriticalPoint | read-only | mandatory | Info: EMD humidity is at high critical point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.56 | ScalarupsAlarmEMDHumidityAtLowWarningPoint | read-only | mandatory | Info: EMD humidity is at low warning point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.57 | ScalarupsAlarmEMDHumidityAtHighWarningPoint | read-only | mandatory | Info: EMD humidity is at high warning point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.58 | ScalarupsAlarmEMDTemperatureAtLowCriticalPoint | read-only | mandatory | Info: EMD Temperature is at low critical point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.59 | ScalarupsAlarmEMDTemperatureAtHighCriticalPoint | read-only | mandatory | Info: EMD Temperature is at high critical point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.60 | ScalarupsAlarmEMDTemperatureAtLowWarningPoint | read-only | mandatory | Info: EMD Temperature is at low warning point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.61 | ScalarupsAlarmEMDTemperatureAtHighWarningPoint | read-only | mandatory | Info: EMD Temperature is at high warning point. |
| 1.3.6.1.4.1.186.1.19.2.3.10.3.62 | ScalarupsAlarmLogInError | read-only | mandatory | Info: Username/Password information is incorrect. |
| 1.3.6.1.4.1.186.1.19.2.3.11 | NodeupsPassword | |||
| 1.3.6.1.4.1.186.1.19.2.3.11 | NodeupsTrapDCBusImbalance | Fault: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.11.1 | ScalarupsPwdAdminCurrentAccessLevel | read-only | mandatory | The administrator access level. |
| 1.3.6.1.4.1.186.1.19.2.3.11.2 | ScalarupsPwdAdminCurrentLogin | read-write | mandatory | The administrator access login name. |
| 1.3.6.1.4.1.186.1.19.2.3.11.3 | ScalarupsPwdAdminNewLoginAccess | read-write | mandatory | The administrator access login name. |
| 1.3.6.1.4.1.186.1.19.2.3.11.4 | ScalarupsPwdAdminCurrentPswd | read-write | mandatory | The current password. |
| 1.3.6.1.4.1.186.1.19.2.3.11.5 | ScalarupsPwdAdminNewPswd | read-write | mandatory | The current password. |
| 1.3.6.1.4.1.186.1.19.2.3.12 | NodeupsAgent | |||
| 1.3.6.1.4.1.186.1.19.2.3.12 | NodeupsTrapDCBusImbalanceClear | Fault Clear: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.12.1 | ScalarupsAgentSoftwareVersion | read-only | mandatory | The RemotEye III version number |
| 1.3.6.1.4.1.186.1.19.2.3.12.2 | ScalarupsAgentHardwareAddress | read-only | mandatory | The hardware/MAC address that NMS can identify the managed device |
| 1.3.6.1.4.1.186.1.19.2.3.12.3 | ScalarupsAgentIPAddress | read-write | mandatory | The ip address that NMS can identify the managed device |
| 1.3.6.1.4.1.186.1.19.2.3.12.4 | ScalarupsAgentGatewayAddress | read-write | mandatory | The default gateway that allow device managed through routers |
| 1.3.6.1.4.1.186.1.19.2.3.12.5 | ScalarupsAgentSubnetMask | read-write | mandatory | Internet address subnet mask |
| 1.3.6.1.4.1.186.1.19.2.3.12.6 | ScalarupsAgentDate | read-write | mandatory | The date in agent, format is MM/DD/YYYY. |
| 1.3.6.1.4.1.186.1.19.2.3.12.7 | ScalarupsAgentTime | read-write | mandatory | The time in agent, format is HH:MM:SS. |
| 1.3.6.1.4.1.186.1.19.2.3.12.8 | ScalarupsAgentGeneralRecordLogFrequency | read-write | mandatory | The interval frequency of the general record log. The value is in seconds. |
| 1.3.6.1.4.1.186.1.19.2.3.12.9 | ScalarupsAgentPollingRate | read-write | mandatory | The frequency that proxy agent polls the connected UPS in RemotEye III protocols. |
| 1.3.6.1.4.1.186.1.19.2.3.12.10 | ScalarupsAgentDHCPControl | read-write | mandatory | Enable or disable DHCP/BootP capability |
| 1.3.6.1.4.1.186.1.19.2.3.12.11 | ScalarupsAgentTelnetControl | read-write | mandatory | Enable or disable telnet access |
| 1.3.6.1.4.1.186.1.19.2.3.12.12 | ScalarupsAgentTFTPControl | read-write | mandatory | Enable or disable network upgrade capability |
| 1.3.6.1.4.1.186.1.19.2.3.12.13 | ScalarupsAgentResetToDefault | read-write | mandatory | Reset all parameters of REMOTEYE III to default value |
| 1.3.6.1.4.1.186.1.19.2.3.12.14 | ScalarupsAgentRestart | read-write | mandatory | Restart REMOTEYE III |
| 1.3.6.1.4.1.186.1.19.2.3.12.15 | ScalarupsAgentSystemName | read-write | mandatory | The Agent System name |
| 1.3.6.1.4.1.186.1.19.2.3.12.16 | ScalarupsAgentSystemContact | read-write | mandatory | Contact Information |
| 1.3.6.1.4.1.186.1.19.2.3.12.17 | ScalarupsAgentSystemLocation | read-write | mandatory | Agent Location |
| 1.3.6.1.4.1.186.1.19.2.3.12.18 | ScalarupsAgentDefaultLanguage | read-write | mandatory | Current Default Language |
| 1.3.6.1.4.1.186.1.19.2.3.12.19 | ScalarupsAgentClearGeneralHistory | read-write | mandatory | Clear general history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.20 | ScalarupsAgentClearTestHistory | read-write | mandatory | Clear test history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.21 | ScalarupsAgentClearBackupHistory | read-write | mandatory | Clear Backup history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.22 | ScalarupsAgentClearFaultHistory | read-write | mandatory | Clear Fault history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.23 | ScalarupsAgentClearOperationModeHistory | read-write | mandatory | Clear operation mode history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.24 | ScalarupsAgentClearWarningHistory | read-write | mandatory | Clear warning history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.25 | ScalarupsAgentClearSystemsettingsChangeHistory | read-write | mandatory | Clear System settings change history log data |
| 1.3.6.1.4.1.186.1.19.2.3.12.26 | ScalarupsAgentClearRMTIEventHistory | read-write | mandatory | Clear RemotEye Event History log data |
| 1.3.6.1.4.1.186.1.19.2.3.13 | NodeupsConnectedClients | |||
| 1.3.6.1.4.1.186.1.19.2.3.13 | NodeupsTrapOutputUnderVoltage | Fault: An output undervoltage reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.13.1 | ScalarupsConnectedClientsNum | read-only | mandatory | The count of clients which have registered for UPS Shutdown control. |
| 1.3.6.1.4.1.186.1.19.2.3.13.2 | TableupsConnectedClientsTable | not-accessible | mandatory | The devices powered by UPS and registered to RemotEye III |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1 | RowupsConnectedClientsEntry | not-accessible | mandatory | The devices protected by RemotEye III |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.1 | ColumnupsConnectedClientsIndex | not-accessible | mandatory | The index of the device that is plugged into the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.2 | ColumnupsConnectedClientsIPAddress | read-only | mandatory | The ip address of the device. |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.3 | ColumnupsConnectedClientsName | read-only | mandatory | The name/description of the device plugged into the UPS. |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.4 | ColumnupsConnectedClientsTimeAtConnection | read-only | mandatory | The time that the device registered to REMOTEYE III |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.5 | ColumnupsConnectedClientsShutdownDelay | read-only | mandatory | The shutdown delay set on REMOTEYE III |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.6 | ColumnupsConnectedClientsConnectionTimeout | read-only | mandatory | The device timeout counter. Unit: 10 seconds |
| 1.3.6.1.4.1.186.1.19.2.3.13.2.1.7 | ColumnupsConnectedClientsShutdownTest | read-only | mandatory | The client will shutdown test after receive shutdown request from REMOTEYE III. |
| 1.3.6.1.4.1.186.1.19.2.3.14 | NodeupsEmail | |||
| 1.3.6.1.4.1.186.1.19.2.3.14 | NodeupsTrapOutputUnderVoltageClear | Fault Clear: An output undervoltage reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.14.1 | ScalarupsEmailMailServer | read-write | mandatory | The Email mail server for REMOTEYE III. |
| 1.3.6.1.4.1.186.1.19.2.3.14.2 | ScalarupsEmailUserAccount | read-write | mandatory | The Email mail server login name. |
| 1.3.6.1.4.1.186.1.19.2.3.14.3 | ScalarupsEmailUserPassword | read-write | mandatory | The Email mail server password. |
| 1.3.6.1.4.1.186.1.19.2.3.14.4 | ScalarupsEmailDomainName | read-write | mandatory | The Email mail server domain name |
| 1.3.6.1.4.1.186.1.19.2.3.14.5 | ScalarupsEmailDNSServer | read-write | mandatory | The Email DNS server name |
| 1.3.6.1.4.1.186.1.19.2.3.14.6 | ScalarupsEmailStatusReportSendTime | read-write | mandatory | The Email Status Report Send Time |
| 1.3.6.1.4.1.186.1.19.2.3.14.7 | TableupsEmailClientsTable | not-accessible | mandatory | The email addresses that RemotEye III will send logs and status reports to. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1 | RowupsEmailClientsEntry | not-accessible | mandatory | The email addresses that RemotEye III will send logs and status reports to. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1.1 | ColumnupsEmailClientsIndex | read-only | mandatory | The index of the email clients. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1.2 | ColumnupsEmailClientsEmailAddress | read-write | mandatory | The email address of the clients. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1.3 | ColumnupsEmailClientsDescription | read-write | mandatory | The name/description of the clients. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1.4 | ColumnupsEmailClientsDailyStatusReportType | read-write | mandatory | The type of daily information that clients would like to receive. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1.5 | ColumnupsEmailClientsEventStatusReportType | read-write | mandatory | The type of event information that clients would like to receive when event occurs. |
| 1.3.6.1.4.1.186.1.19.2.3.14.7.1.6 | ColumnupsEmailClientsInfoLevel | read-write | mandatory | The type of information that clients would like to receive. |
| 1.3.6.1.4.1.186.1.19.2.3.15 | NodeupsSNMP | |||
| 1.3.6.1.4.1.186.1.19.2.3.15 | NodeupsTrapOutputOverVoltage | Fault: An output overvoltage reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.15.1 | ScalarupsSNMPVersion | read-only | mandatory | The SNMP version |
| 1.3.6.1.4.1.186.1.19.2.3.15.2 | TableupsSNMPTrapsReceiversTable | not-accessible | mandatory | A list of managers to send traps to. The number of entries is given by the value of upsSNMPNumTrapReceivers |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1 | RowupsSNMPTrapsReceiversEntry | not-accessible | mandatory | The managers to send traps to. |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1.1 | ColumnupsSNMPTrapsReceiversIndex | read-only | mandatory | The index to a trap receiver entry. |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1.2 | ColumnupsSNMPTrapsReceiversIPAddress | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1.3 | ColumnupsSNMPTrapReceiversCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1.4 | ColumnupsSNMPTrapReceiversTrapType | read-write | mandatory | The trap group that NMS desired. |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1.5 | ColumnupsSNMPTrapReceiversInfoReceivingSeverityLevel | read-write | mandatory | The severity level of traps to be received by this manager. |
| 1.3.6.1.4.1.186.1.19.2.3.15.2.1.6 | ColumnupsSNMPTrapReceiversDescription | read-write | mandatory | Description of trap receivers |
| 1.3.6.1.4.1.186.1.19.2.3.15.3 | TableupsSNMPCommunitiesTable | not-accessible | mandatory | A list of managers which can access REMOTEYE III with private community string. |
| 1.3.6.1.4.1.186.1.19.2.3.15.3.1 | RowupsSNMPCommunitiesEntry | not-accessible | mandatory | The managers. |
| 1.3.6.1.4.1.186.1.19.2.3.15.3.1.1 | ColumnupsSNMPCommunitiesIndex | read-only | mandatory | The index to a access control entry. |
| 1.3.6.1.4.1.186.1.19.2.3.15.3.1.2 | ColumnupsSNMPCommunitiesIPAddress | read-write | mandatory | The IP address of the manager to access REMOTEYE III |
| 1.3.6.1.4.1.186.1.19.2.3.15.3.1.3 | ColumnupsSNMPCommunitiesAccessString | read-write | mandatory | The community name to use in the manager when access REMOTEYE III |
| 1.3.6.1.4.1.186.1.19.2.3.15.3.1.4 | ColumnupsSNMPCommunitiesAccessMode | read-write | mandatory | Access type, only read/Write access type can change parameter of REMOTEYE III |
| 1.3.6.1.4.1.186.1.19.2.3.16 | NodeupsEMD | |||
| 1.3.6.1.4.1.186.1.19.2.3.16 | NodeupsTrapOutputOverVoltageClear | Fault Clear: An output overvoltage reported. Contact your Toshiba authorized service center for examination. | ||
| 1.3.6.1.4.1.186.1.19.2.3.16.1 | ScalarupsEMDType | read-only | mandatory | The name assign to specific EMD. |
| 1.3.6.1.4.1.186.1.19.2.3.16.2 | ScalarupsEMDTemperature | read-only | mandatory | The EMD temperature. |
| 1.3.6.1.4.1.186.1.19.2.3.16.3 | ScalarupsEMDTemperatureLowWarningSetPoint | read-write | mandatory | The EMD temperature low warning set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.4 | ScalarupsEMDTemperatureLowCriticalSetPoint | read-write | mandatory | The EMD temperature low critical set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.5 | ScalarupsEMDTemperatureHighWarningSetPoint | read-write | mandatory | The EMD temperature high warning set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.6 | ScalarupsEMDTemperatureHighCriticalSetPoint | read-write | mandatory | The EMD temperature high critical set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.7 | ScalarupsEMDTemperatureHysteresis | read-write | mandatory | The EMD temperature hysteresis. |
| 1.3.6.1.4.1.186.1.19.2.3.16.8 | ScalarupsEMDTemperatureCalibrationOffset | read-write | mandatory | The EMD temperature calibration offset. |
| 1.3.6.1.4.1.186.1.19.2.3.16.9 | ScalarupsEMDHumidity | read-only | mandatory | The EMD Humidity. |
| 1.3.6.1.4.1.186.1.19.2.3.16.10 | ScalarupsEMDHumidityLowWarningSetPoint | read-write | mandatory | The EMD Humidity low warning set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.11 | ScalarupsEMDHumidityLowCriticalSetPoint | read-write | mandatory | The EMD Humidity low critical set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.12 | ScalarupsEMDHumidityHighWarningSetPoint | read-write | mandatory | The EMD Humidity high warning set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.13 | ScalarupsEMDHumidityHighCriticalSetPoint | read-write | mandatory | The EMD Humidity high critical set point. |
| 1.3.6.1.4.1.186.1.19.2.3.16.14 | ScalarupsEMDHumidityHysteresis | read-write | mandatory | The EMD Humidity hysteresis. |
| 1.3.6.1.4.1.186.1.19.2.3.16.15 | ScalarupsEMDHumidityCalibrationOffset | read-write | mandatory | The EMD Humidity calibration offset. |
| 1.3.6.1.4.1.186.1.19.2.3.16.16 | ScalarupsEMDR1Status | read-only | mandatory | The EMD dry contact 1 status. |
| 1.3.6.1.4.1.186.1.19.2.3.16.17 | ScalarupsEMDAlarmR1Enable | read-write | mandatory | The EMD contact R1 alarm enable setting. |
| 1.3.6.1.4.1.186.1.19.2.3.16.18 | ScalarupsEMDAlarmR1Hysteresis | read-write | mandatory | The EMD Contact R1 alarm hysteresis. |
| 1.3.6.1.4.1.186.1.19.2.3.16.19 | ScalarupsEMDR2Status | read-only | mandatory | The EMD dry contact 2 status. |
| 1.3.6.1.4.1.186.1.19.2.3.16.20 | ScalarupsEMDAlarmR2Enable | read-write | mandatory | The EMD contact R2 alarm enable setting. |
| 1.3.6.1.4.1.186.1.19.2.3.16.21 | ScalarupsEMDAlarmR2Hysteresis | read-write | mandatory | The EMD Contact R2 alarm hysteresis. |
| 1.3.6.1.4.1.186.1.19.2.3.17 | NodeupsTrapHeatSinkOverheat | Fault: A Heat sink or device overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.18 | NodeupsTrapHeatSinkOverheatClear | Fault Clear: A Heat sink or device overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.19 | NodeupsTrapBypassOverload | Fault: A bypass overload reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.20 | NodeupsTrapBypassOverloadClear | Fault Clear: A bypass overload reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.21 | NodeupsTrap | |||
| 1.3.6.1.4.1.186.1.19.2.3.21 | NodeupsTrapChargerOvervoltageFault | Warning: Charger overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.22 | NodeupsTrapChargerOvervoltageFaultClear | Warning Clear: Charger overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.23 | NodeupsTrapOutputOvercurrent | Warning: An output overcurrent reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.24 | NodeupsTrapOutputOvercurrentClear | Warning Clear: An output overcurrent reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.25 | NodeupsTrapDCUnderVoltageAtBoostUp | Fault: A DC bus undervoltage during boost-up reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.26 | NodeupsTrapDCUnderVoltageAtBoostUpClear | Fault Clear: A DC bus undervoltage during boost-up reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.27 | NodeupsTrapDCUnderVoltageAtCharge | Fault: A DC bus undervoltage during charging reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.28 | NodeupsTrapDCUnderVoltageAtChargeClear | Fault Clear: A DC bus undervoltage during charging reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.29 | NodeupsTrapBypassOverheat | Fault: A Bypass overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.30 | NodeupsTrapBypassOverheatClear | Fault Clear: A Bypass overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.31 | NodeupsTrapResettableInverterOverload | Fault: An inverter overload reported. It is resettable. | ||
| 1.3.6.1.4.1.186.1.19.2.3.32 | NodeupsTrapResettableInverterOverloadClear | Fault Clear: An inverter overload reported. It is resettable. | ||
| 1.3.6.1.4.1.186.1.19.2.3.33 | NodeupsTrapUnResettableInverterOverload | Fault: An inverter overload reported. It is not resettable. | ||
| 1.3.6.1.4.1.186.1.19.2.3.34 | NodeupsTrapUnResettableInverterOverloadClear | Fault Clear: An inverter overload reported. It is not resettable. | ||
| 1.3.6.1.4.1.186.1.19.2.3.35 | NodeupsTrapInputOverVoltage | Warning: An input overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.36 | NodeupsTrapInputOverVoltageClear | Warning Clear: An input overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.37 | NodeupsTrapInputUnderVoltage | Warning: An input undervoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.38 | NodeupsTrapInputUnderVoltageClear | Warning Clear: An input undervoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.39 | NodeupsTrapInputFrequencyError | Warning: An input frequency error reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.40 | NodeupsTrapInputFrequencyErrorClear | Warning Clear: An input frequency error reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.41 | NodeupsTrapBypassOverVoltage | Warning: A bypass overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.42 | NodeupsTrapBypassOverVoltageClear | Warning Clear: A bypass overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.43 | NodeupsTrapBypassUnderVoltage | Warning: A bypass undervoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.44 | NodeupsTrapBypassUnderVoltageClear | Warning Clear: A bypass undervoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.45 | NodeupsTrapBypassFrequencyError | Warning: A bypass frequency error reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.46 | NodeupsTrapBypassFrequencyErrorClear | Warning Clear: A bypass frequency error reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.47 | NodeupsTrapDCUnderVoltageAtTest | Warning: A DC bus undervoltage during battery test reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.48 | NodeupsTrapDCUnderVoltageAtTestClear | Warning Clear: A DC bus undervoltage during battery test reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.49 | NodeupsTrapBatteryLow | Warning: A low battery level reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.50 | NodeupsTrapBatteryLowClear | Warning Clear: A low battery level reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.51 | NodeupsTrapBatteryAtShutdownlevel | Warning: A shutdown battery level reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.52 | NodeupsTrapBatteryAtShutdownlevelClear | Warning Clear: A shutdown battery level reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.53 | NodeupsTrapReplaceBattery | Warning: A replacement of batteries reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.54 | NodeupsTrapReplaceBatteryClear | Warning Clear: A replacement of batteries reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.55 | NodeupsTrapChargerOverVoltageWarning | Warning: A charger overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.56 | NodeupsTrapChargerOverVoltageWarningClear | Warning Clear: A charger overvoltage reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.57 | NodeupsTrapBatteryTestFailed | Warning: A battery test failed event reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.58 | NodeupsTrapBatteryTestFailedClear | Warning Clear: A battery test failed event reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.59 | NodeupsTrapBatteryDepleted | Warning: A battery depleted event reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.60 | NodeupsTrapBatteryDepletedClear | Warning Clear: A battery depleted event reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.61 | NodeupsTrapBatteryOverheat | Warning: A battery overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.62 | NodeupsTrapBatteryOverheatClear | Warning Clear: A battery overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.63 | NodeupsTrapSystemOverheat | Warning: A system overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.64 | NodeupsTrapSystemOverheatClear | Warning Clear: A system overheat reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.65 | NodeupsTrapOutputOverloadWarning | Warning: An output overload reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.66 | NodeupsTrapOutputOverloadWarningClear | Warning Clear: An output overload reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.67 | NodeupsTrapCurrentLimitWarning | Warning: A current limit reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.68 | NodeupsTrapCurrentLimitWarningClear | Warning Clear: A current limit reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.69 | NodeupsTrapAsyncOperation | Warning: An Asynchronous operation reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.70 | NodeupsTrapAsyncOperationClear | Warning Clear: An Asynchronous operation reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.71 | NodeupsTrapServiceUPS | Warning: UPS is in need of service. | ||
| 1.3.6.1.4.1.186.1.19.2.3.72 | NodeupsTrapServiceUPSClear | Warning Clear: UPS is in need of service. | ||
| 1.3.6.1.4.1.186.1.19.2.3.73 | NodeupsTrapBatteryNearExpiration | Warning: A near expiration of batteries reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.74 | NodeupsTrapBatteryNearExpirationClear | Warning Clear: A near expiration of batteries reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.75 | NodeupsTrapBatteryExpired | Warning: A expiration of batteries reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.76 | NodeupsTrapBatteryExpiredClear | Warning Clear: A expiration of batteries reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.77 | NodeupsTrapDisplayCableError | Warning: A display cable error reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.78 | NodeupsTrapDisplayCableErrorClear | Warning Clear: A display cable error reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.79 | NodeupsTrapRemotEyeCommError | Warning: A communication error between the main control and the RemotEye III reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.80 | NodeupsTrapRemotEyeCommErrorClear | Warning Clear: A communication error between the main control and the RemotEye III reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.81 | NodeupsTrapRemotEyeUplinkCommError | Warning: A communication error between the RemotEye III and the network reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.82 | NodeupsTrapRemotEyeUplinkCommErrorClear | Warning Clear: A communication error between the RemotEye III and the network reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.83 | NodeupsTrapServicePortCommError | Warning: A communication error between the main controller and the service port reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.84 | NodeupsTrapServicePortCommErrorClear | Warning Clear: A communication error between the main controller and the service port reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.85 | NodeupsTrapDispCommError | Warning: A communication error between the main controller and the display controller reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.86 | NodeupsTrapDispCommErrorClear | Warning Clear: A communication error between the main controller and the display controller reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.87 | NodeupsTrapSystemTestFailed | Warning: A system test failed event reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.88 | NodeupsTrapSystemTestFailedClear | Warning Clear: A system test failed event reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.89 | NodeupsTrapBypassOn | Warning: The UPS is in Stop (Bypass) mode. | ||
| 1.3.6.1.4.1.186.1.19.2.3.90 | NodeupsTrapBypassOnClear | Warning Clear: The UPS is in Stop (Bypass) mode. | ||
| 1.3.6.1.4.1.186.1.19.2.3.91 | NodeupsTrapPowerFailure | Info: A power failure reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.92 | NodeupsTrapPowerFailureClear | Info Clear: A power failure reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.93 | NodeupsTrapShutdownPending | Info: A output shutdown in progress reported. Output will turn off after delay. | ||
| 1.3.6.1.4.1.186.1.19.2.3.94 | NodeupsTrapShutdownPendingClear | Info Clear: A output shutdown in progress reported. Output will turn off after delay. | ||
| 1.3.6.1.4.1.186.1.19.2.3.95 | NodeupsTrapOutputOffAsRequested | Info: An output shutdown mode requested. | ||
| 1.3.6.1.4.1.186.1.19.2.3.96 | NodeupsTrapOutputOffAsRequestedClear | Info Clear: An output shutdown mode requested. | ||
| 1.3.6.1.4.1.186.1.19.2.3.97 | NodeupsTrapOutputOff | Info: The UPS system output is off. | ||
| 1.3.6.1.4.1.186.1.19.2.3.98 | NodeupsTrapOutputOffClear | Info Clear: The UPS system output is off. | ||
| 1.3.6.1.4.1.186.1.19.2.3.99 | NodeupsTrapBatteryTestInProgress | Info: A battery test in progress reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.100 | NodeupsTrapBatteryTestInProgressClear | Info Clear: A battery test in progress reported. | ||
| 1.3.6.1.4.1.186.1.19.2.3.101 | NodeupsTrapBatteryOn | Info: The UPS is on Battery mode; it is supplying output power from its batteries. | ||
| 1.3.6.1.4.1.186.1.19.2.3.102 | NodeupsTrapBatteryOnClear | Info Clear: The UPS is on Battery mode; it is supplying output power from its batteries. | ||
| 1.3.6.1.4.1.186.1.19.2.3.103 | NodeupsTrapEMDSensor1AlarmTriggered | Warning: EMD sensor 1 alarm is triggered. | ||
| 1.3.6.1.4.1.186.1.19.2.3.104 | NodeupsTrapEMDSensor1AlarmTriggeredClear | Warning Clear: EMD sensor 1 alarm is triggered. | ||
| 1.3.6.1.4.1.186.1.19.2.3.105 | NodeupsTrapEMDSensor2AlarmTriggered | Warning: EMD sensor 2 alarm is triggered. | ||
| 1.3.6.1.4.1.186.1.19.2.3.106 | NodeupsTrapEMDSensor2AlarmTriggeredClear | Warning Clear: EMD sensor 2 alarm is triggered. | ||
| 1.3.6.1.4.1.186.1.19.2.3.107 | NodeupsTrapEMDHumidityAtLowCiriticalPoint | Warning: EMD humidity is at low critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.108 | NodeupsTrapEMDHumidityAtLowCiriticalPointClear | Warning Clear: EMD humidity is at low critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.109 | NodeupsTrapEMDHumidityAtHighCiriticalPoint | Warning: EMD humidity is at high critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.110 | NodeupsTrapEMDHumidityAtHighCiriticalPointClear | Warning Clear: EMD humidity is at high critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.111 | NodeupsTrapEMDHumidityAtLowWarningPoint | Warning: EMD humidity is at low warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.112 | NodeupsTrapEMDHumidityAtLowWarningPointClear | Warning Clear: EMD humidity is at low warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.113 | NodeupsTrapEMDHumidityAtHighWarningPoint | Warning: EMD humidity is at high warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.114 | NodeupsTrapEMDHumidityAtHighWarningPointClear | Warning Clear: EMD humidity is at high warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.115 | NodeupsTrapEMDTemperatureAtLowCiriticalPoint | Warning: EMD Temperature is at low critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.116 | NodeupsTrapEMDTemperatureAtLowCiriticalPointClear | Warning Clear: EMD Temperature is at low critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.117 | NodeupsTrapEMDTemperatureAtHighCiriticalPoint | Warning: EMD Temperature is at high critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.118 | NodeupsTrapEMDTemperatureAtHighCiriticalPointClear | Warning Clear: EMD Temperature is at high critical point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.119 | NodeupsTrapEMDTemperatureAtLowWarningPoint | Warning: EMD Temperature is at low warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.120 | NodeupsTrapEMDTemperatureAtLowWarningPointClear | Warning Clear: EMD Temperature is at low warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.121 | NodeupsTrapEMDTemperatureAtHighWarningPoint | Warning: EMD Temperature is at high warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.122 | NodeupsTrapEMDTemperatureAtHighWarningPointClear | Warning Clear: EMD Temperature is at high warning point. | ||
| 1.3.6.1.4.1.186.1.19.2.3.123 | NodeupsTrapLogInError | Info: Username/Password information is incorrect. | ||
| 1.3.6.1.4.1.186.1.19.2.3.124 | NodeupsTrapLogInErrorClear | Info Clear: Username/Password information is incorrect. |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| NonNegativeInteger | INTEGER (0..2147483647) | ||
| PositiveInteger | INTEGER (0..2147483647) |