MIB Viewer

TOSHIBAUPS-MIB

474 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.186Nodetoshiba
1.3.6.1.4.1.186.1Nodeequ
1.3.6.1.4.1.186.1.19NodeequUPS
1.3.6.1.4.1.186.1.19.2NodeticUPS
1.3.6.1.4.1.186.1.19.2.3Nodermti3
1.3.6.1.4.1.186.1.19.2.3.1NodeupsIdent
1.3.6.1.4.1.186.1.19.2.3.1NodeupsTrapFaultFault: One or more fault reported.
1.3.6.1.4.1.186.1.19.2.3.1.1ScalarupsIdentManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.186.1.19.2.3.1.2ScalarupsIdentTypeformread-onlymandatoryThe UPS Typeform.
1.3.6.1.4.1.186.1.19.2.3.1.3ScalarupsIdentSerialNumberread-onlymandatoryThe UPS Serial Number.
1.3.6.1.4.1.186.1.19.2.3.1.4ScalarupsIdentMainFirmwareVersionread-onlymandatoryThe UPS firmware version of the main controller.
1.3.6.1.4.1.186.1.19.2.3.1.5ScalarupsIdentMainBootSectorVersionread-onlymandatoryThe UPS boot sector version of the main controller.
1.3.6.1.4.1.186.1.19.2.3.1.6ScalarupsIdentMainBootLoaderVersionread-onlymandatoryThe UPS Boot Loader version of the main controller.
1.3.6.1.4.1.186.1.19.2.3.1.7ScalarupsIdentJobNumberread-onlymandatoryThe UPS Job Number.
1.3.6.1.4.1.186.1.19.2.3.1.8ScalarupsIdentTestPersonread-onlymandatoryThe test person.
1.3.6.1.4.1.186.1.19.2.3.1.9ScalarupsIdentTestDateread-onlymandatoryThe test date displayed as YYYYMMDD format.
1.3.6.1.4.1.186.1.19.2.3.1.10ScalarupsIdentHardwareBuildDateread-onlymandatoryThe date that the UPS was built in YYYYMMDD format.
1.3.6.1.4.1.186.1.19.2.3.1.11ScalarupsIdentEEPROMVersionread-onlymandatoryThe UPS Main controller's EEPROM version.
1.3.6.1.4.1.186.1.19.2.3.1.12ScalarupsIdentSysNameread-writemandatoryA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.186.1.19.2.3.1.13ScalarupsIdentAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.186.1.19.2.3.1.14ScalarupsIdentInstallationDateread-writemandatoryThe UPS installation date in YYYYMMDD format.
1.3.6.1.4.1.186.1.19.2.3.2NodeupsInput
1.3.6.1.4.1.186.1.19.2.3.2NodeupsTrapFaultClearFault Clear: One or more fault reported.
1.3.6.1.4.1.186.1.19.2.3.2.1ScalarupsInputPowerSupplyConfigurationread-onlymandatoryThis parameter summarizes the measured and collected data describing the input power supply.
1.3.6.1.4.1.186.1.19.2.3.2.2ScalarupsInputNumLinesread-onlymandatoryThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.186.1.19.2.3.2.3TableupsInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsInputNumLine.
1.3.6.1.4.1.186.1.19.2.3.2.3.1RowupsInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.186.1.19.2.3.2.3.1.1ColumnupsInputIndexnot-accessiblemandatoryThe input line identifier
1.3.6.1.4.1.186.1.19.2.3.2.3.1.2ColumnupsInputFrequencyread-onlymandatoryThe present input frequency to the UPS system in 1/10 of Hz.
1.3.6.1.4.1.186.1.19.2.3.2.3.1.3ColumnupsInputVoltageread-onlymandatoryThe input utility line voltage in RMS volts.
1.3.6.1.4.1.186.1.19.2.3.2.3.1.4ColumnupsInputCurrentread-onlymandatoryThe magnitude of the present input Current in 1/10 RMS Amp.
1.3.6.1.4.1.186.1.19.2.3.2.4ScalarupsInputActivePowerread-onlymandatoryThe UPS active power in Watt. -1 if value is invalid.
1.3.6.1.4.1.186.1.19.2.3.2.5ScalarupsInputApparentPowerread-onlymandatoryThe input apparent power in Volt-Amp.
1.3.6.1.4.1.186.1.19.2.3.2.6ScalarupsInputPowerFactorread-onlymandatoryRatio of actual power to apparent power. -1 if value is invalid.
1.3.6.1.4.1.186.1.19.2.3.2.7TableupsInputRatedTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsInputNumLine.
1.3.6.1.4.1.186.1.19.2.3.2.7.1RowupsInputRatedEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.186.1.19.2.3.2.7.1.1ColumnupsInputSlotIndexnot-accessiblemandatoryThe input line identifier
1.3.6.1.4.1.186.1.19.2.3.2.7.1.2ColumnupsInputRatedFrequencyread-onlymandatoryThe present rated input frequency of the UPS system in 1/10 of Hz.
1.3.6.1.4.1.186.1.19.2.3.2.7.1.3ColumnupsInputRatedVoltageread-writemandatoryThe magnitude of the rated input voltage in RMS volts. This is set by the administrator.
1.3.6.1.4.1.186.1.19.2.3.2.7.1.4ColumnupsInputRatedCurrentread-onlymandatoryThe magnitude of the rated input current in 1/10 RMS Amp.
1.3.6.1.4.1.186.1.19.2.3.2.8ScalarupsInputOverVoltageread-onlymandatoryThis is the maximum limit of the input voltage before the UPS enters the over voltage state.
1.3.6.1.4.1.186.1.19.2.3.2.9ScalarupsInputOverVoltageRecoverylevelread-onlymandatoryThe over voltage recovery level. It is the limit at which the UPS returns from over voltage state.
1.3.6.1.4.1.186.1.19.2.3.2.10ScalarupsInputVoltagePercentread-onlymandatoryThe input voltage displayed as a percent.
1.3.6.1.4.1.186.1.19.2.3.2.11ScalarupsInputCurrentPercentread-onlymandatoryThe input current displayed as a percent.
1.3.6.1.4.1.186.1.19.2.3.2.12ScalarupsInputUnderVoltageDetectlevelread-onlymandatoryThe input under voltage detection level in RMS volt.
1.3.6.1.4.1.186.1.19.2.3.2.13ScalarupsInputUnderVoltageRecoverylevelread-onlymandatoryThe input under voltage recovery level in RMS volt.
1.3.6.1.4.1.186.1.19.2.3.2.14ScalarupsInputRatedActivePowerread-onlymandatoryThe rated input active power in Watt.
1.3.6.1.4.1.186.1.19.2.3.2.15ScalarupsInputFreqWithErrread-writemandatoryThe input frequency configuration in 1/10 Hz when detection error occurred. This is set by the administrator.
1.3.6.1.4.1.186.1.19.2.3.3NodeupsOutput
1.3.6.1.4.1.186.1.19.2.3.3NodeupsTrapOpenFuseFault: An open fuse reported.
1.3.6.1.4.1.186.1.19.2.3.3.1ScalarupsOutputPowerSupplyConfigurationread-onlymandatoryThis parameter summarizes the measured and collected data describing the output power supply.
1.3.6.1.4.1.186.1.19.2.3.3.2ScalarupsOutputNumLinesread-onlymandatoryThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.186.1.19.2.3.3.3TableupsOutputTablenot-accessiblemandatoryA list of Output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.186.1.19.2.3.3.3.1RowupsOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Output line.
1.3.6.1.4.1.186.1.19.2.3.3.3.1.1ColumnupsOutputIndexnot-accessiblemandatoryThe Output line identifier.
1.3.6.1.4.1.186.1.19.2.3.3.3.1.2ColumnupsOutputFrequencyread-onlymandatoryThe present output frequency of the UPS system in 1/10 of Hz.
1.3.6.1.4.1.186.1.19.2.3.3.3.1.3ColumnupsOutputVoltageread-onlymandatoryThe Output voltage in RMS volts.
1.3.6.1.4.1.186.1.19.2.3.3.3.1.4ColumnupsOutputCurrentread-onlymandatoryThe magnitude of the present output current in 1/10 RMS Amps.
1.3.6.1.4.1.186.1.19.2.3.3.3.1.5ColumnupsOutputActivePowerread-onlymandatoryThe present output active power in Watt.
1.3.6.1.4.1.186.1.19.2.3.3.3.1.6ColumnupsOutputApparentPowerread-onlymandatoryThe output apparent power in Volt-Amp.
1.3.6.1.4.1.186.1.19.2.3.3.4ScalarupsOutputLoadPercentageread-onlymandatoryThe present UPS ouput load percentage which is current percent or active power whichever greater.
1.3.6.1.4.1.186.1.19.2.3.3.5TableupsOutputRatedTablenot-accessiblemandatoryA list of Output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.186.1.19.2.3.3.5.1RowupsOutputRatedEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Output line.
1.3.6.1.4.1.186.1.19.2.3.3.5.1.1ColumnupsOutputSlotIndexnot-accessiblemandatoryThe Output line identifier.
1.3.6.1.4.1.186.1.19.2.3.3.5.1.2ColumnupsOutputRatedFrequencyread-onlymandatoryThe present output rated frequency of the UPS system in 1/10 of Hz.
1.3.6.1.4.1.186.1.19.2.3.3.5.1.3ColumnupsOutputRatedVoltageread-writemandatoryThe rated output voltage in RMS volts. This is set by the administrator
1.3.6.1.4.1.186.1.19.2.3.3.5.1.4ColumnupsOutputRatedCurrentread-onlymandatoryThe output rated current in 1/10 RMS Amp.
1.3.6.1.4.1.186.1.19.2.3.3.5.1.5ColumnupsOutputRatedActivePowerread-onlymandatoryThe output rated active power in Watt.
1.3.6.1.4.1.186.1.19.2.3.3.5.1.6ColumnupsOutputRatedApparentPowerread-onlymandatoryThe output rated apparent power in Volt-Amp.
1.3.6.1.4.1.186.1.19.2.3.3.6ScalarupsOutputUndervoltagelevelread-onlymandatoryThis parameter displays the minimum allowable voltage before it falls into under voltage range.
1.3.6.1.4.1.186.1.19.2.3.3.7ScalarupsOutputOverVoltagelevelread-onlymandatoryThis is the maximum limit of the output voltage before the UPS enters the over voltage state.
1.3.6.1.4.1.186.1.19.2.3.3.8ScalarupsOutputFrequencySynchRangeread-onlymandatoryThe allowable range for synchronizing output frequency in 1/10 of Hz.
1.3.6.1.4.1.186.1.19.2.3.3.9ScalarupsOutputVoltageAdjustread-writemandatoryThis parameter allows UPS to be configured to have adjustable voltages. This is set by the administrator.
1.3.6.1.4.1.186.1.19.2.3.3.10ScalarupsOutputRatedPowerFactorread-onlymandatoryThe rated output power factor.
1.3.6.1.4.1.186.1.19.2.3.4NodeupsBypass
1.3.6.1.4.1.186.1.19.2.3.4NodeupsTrapOpenFuseClearFault Clear: An open fuse reported.
1.3.6.1.4.1.186.1.19.2.3.4.1ScalarupsBypassPowerSupplyConfigurationread-onlymandatoryThis parameter summarizes the measured and collected data describing the power supply into the bypass circuit.
1.3.6.1.4.1.186.1.19.2.3.4.2ScalarupsBypassNumLineread-onlymandatoryThe number of bypass lines utilized in this device. This variable indicates the number of rows in the bypass table.
1.3.6.1.4.1.186.1.19.2.3.4.3TableupsBypassTablenot-accessiblemandatoryA list of Bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.4.1.186.1.19.2.3.4.3.1RowupsBypassEntrynot-accessiblemandatoryAn entry containing information applicable to a particular line.
1.3.6.1.4.1.186.1.19.2.3.4.3.1.1ColumnupsBypassIndexnot-accessiblemandatoryThe Bypass line identifier.
1.3.6.1.4.1.186.1.19.2.3.4.3.1.2ColumnupsBypassFrequencyread-onlymandatoryThe present Bypass frequency of the UPS system in 1/10 of Hz of each phase.
1.3.6.1.4.1.186.1.19.2.3.4.3.1.3ColumnupsBypassVoltageread-onlymandatoryThe Bypass utility line voltage in RMS volts.
1.3.6.1.4.1.186.1.19.2.3.4.3.1.4ColumnupsBypassCurrentread-onlymandatoryThe magnitude of the present bypass Current in 1/10 RMS Amp.
1.3.6.1.4.1.186.1.19.2.3.4.4ScalarupsBypassApparentPowerread-onlymandatoryThe Bypass Apparent power in Volt-Amp.
1.3.6.1.4.1.186.1.19.2.3.4.5ScalarupsBypassUnderVoltageDetectionlevelread-onlymandatoryThis parameter displays the minimum allowable voltage before it falls into bypass undervoltage range.
1.3.6.1.4.1.186.1.19.2.3.4.6ScalarupsBypassUnderVoltageRecoverylevelread-onlymandatoryThis parameter displays the allowable voltage that it can recover from.
1.3.6.1.4.1.186.1.19.2.3.4.7ScalarupsBypassOverVoltageDetectionlevelread-onlymandatoryThis parameter displays the maximum allowable voltage before it falls into over voltage range.
1.3.6.1.4.1.186.1.19.2.3.4.8ScalarupsBypassOverVoltageRecoverylevelread-onlymandatoryThis parameter displays the allowable voltage that it can recover from.
1.3.6.1.4.1.186.1.19.2.3.5NodeupsDCBus
1.3.6.1.4.1.186.1.19.2.3.5NodeupsTrapCurrentLimitFaultFault: A current limit fault reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.5.1ScalarupsDCBusTotalVoltageread-onlymandatoryThe DC Bus voltage in DC volts.
1.3.6.1.4.1.186.1.19.2.3.5.2ScalarupsDCBusPositiveVoltageread-onlymandatoryThe DC Bus positive voltage in DC volts.
1.3.6.1.4.1.186.1.19.2.3.5.3ScalarupsDCBusNegativeVoltageread-onlymandatoryThe DC Bus negative voltage in DC volts.
1.3.6.1.4.1.186.1.19.2.3.5.4ScalarupsDCBusRatedVoltageread-onlymandatoryThe DC Bus rated voltage in DC volts.
1.3.6.1.4.1.186.1.19.2.3.6NodeupsBattery
1.3.6.1.4.1.186.1.19.2.3.6NodeupsTrapCurrentLimitFaultClearFault Clear: A current limit fault reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.6.1ScalarupsBatteryStatusread-onlymandatoryThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time sufficient to handle the…
1.3.6.1.4.1.186.1.19.2.3.6.2ScalarupsSecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whiche…
1.3.6.1.4.1.186.1.19.2.3.6.3ScalarupsBatteryVoltageread-onlymandatoryThe magnitude of the present battery voltage in DC Volt.
1.3.6.1.4.1.186.1.19.2.3.6.4ScalarupsBatteryDischargeCurrentread-onlymandatoryThe present battery discharge current in 1/10 DC Amp.
1.3.6.1.4.1.186.1.19.2.3.6.5ScalarupsBatteryChargeStatusread-onlymandatoryThe UPS charger status.
1.3.6.1.4.1.186.1.19.2.3.6.6ScalarupsBatteryNumberofDischargeread-onlymandatoryThis will increment when ups goes into backup mode which is longer than 10 seconds.
1.3.6.1.4.1.186.1.19.2.3.6.7ScalarupsBatteryCalculatedShutdownVoltageread-onlymandatoryThe battery's shutdown voltage in DC Volt.
1.3.6.1.4.1.186.1.19.2.3.6.8ScalarupsBatteryLifeRemainingread-onlymandatoryThe number of hours of UPS operation in the present environment until the batteries must be replaced.
1.3.6.1.4.1.186.1.19.2.3.6.9ScalarupsBatteryRatedAmpereHourread-onlymandatoryThe battery capacity in Amp-Hour.
1.3.6.1.4.1.186.1.19.2.3.6.10ScalarupsBatteryInSeriesread-onlymandatoryThe number of batteries in each string connected in series.
1.3.6.1.4.1.186.1.19.2.3.6.11ScalarupsBatteryInParallelread-onlymandatoryThe number of batteries connected in parallel.
1.3.6.1.4.1.186.1.19.2.3.6.12ScalarupsBatteryInstallationDateread-onlymandatoryThe battery installation date in YYYYMMDD format.
1.3.6.1.4.1.186.1.19.2.3.6.13ScalarupsBatteryVoltageShutdownLevelread-onlymandatoryThe UPS battery voltage shutdown level.
1.3.6.1.4.1.186.1.19.2.3.6.14TableupsBatteryExtTablenot-accessiblemandatoryA list of Battery table entries.
1.3.6.1.4.1.186.1.19.2.3.6.14.1RowupsBatteryExtEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Battery.
1.3.6.1.4.1.186.1.19.2.3.6.14.1.1ColumnupsBatteryExtIndexnot-accessiblemandatoryThe Battery line identifier
1.3.6.1.4.1.186.1.19.2.3.6.14.1.2ColumnupsBatteryExtInSeriesread-onlymandatorySpecifies the number of batteries in the external cabinet that are connected in series.
1.3.6.1.4.1.186.1.19.2.3.6.14.1.3ColumnupsBatteryExtInParallelread-onlymandatorySpecifies the number of batteries in the external cabinet that are connected in parallel.
1.3.6.1.4.1.186.1.19.2.3.6.14.1.4ColumnupsBatteryExtRatedAmpereHourread-onlymandatoryThe external battery's capacity in Amp-Hour.
1.3.6.1.4.1.186.1.19.2.3.6.14.1.5ColumnupsBatteryExtCRateread-onlymandatoryThe external battery's C rate.
1.3.6.1.4.1.186.1.19.2.3.6.14.1.6ColumnupsBatteryExtInstallDateread-onlymandatoryThe battery installation date in YYYYMMDD format.
1.3.6.1.4.1.186.1.19.2.3.6.15ScalarupsBatteryLowBattLevelread-onlymandatoryThe low battery level of the UPS.
1.3.6.1.4.1.186.1.19.2.3.6.16ScalarupsBatteryChargerOverVoltageDelayread-onlymandatoryThe UPS's charger over voltage detection delay in seconds.
1.3.6.1.4.1.186.1.19.2.3.6.17ScalarupsBatteryCalcLBLevelread-onlymandatoryThe calculated low battery level.
1.3.6.1.4.1.186.1.19.2.3.6.18ScalarupsBatteryCapacityread-onlymandatoryThe UPS battery capacity in percent.
1.3.6.1.4.1.186.1.19.2.3.6.19ScalarupsBatteryRuntimeread-onlymandatoryThe UPS battery runtime in minutes. It will return -1 or N/A if not available.
1.3.6.1.4.1.186.1.19.2.3.7NodeupsStsCtlCfg
1.3.6.1.4.1.186.1.19.2.3.7NodeupsTrapDCBusOverCurrentFault: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.7.1ScalarupsStsCtlCfgSystemTemperatureread-onlymandatoryThe UPS system temperature in Celsius.
1.3.6.1.4.1.186.1.19.2.3.7.2ScalarupsStsCtlCfgBatteryTemperatureread-onlymandatoryThe UPS Battery temperature in Celsius.
1.3.6.1.4.1.186.1.19.2.3.7.3ScalarupsStsCtlCfgPresentModeread-onlymandatoryThe present mode of the UPS system.
1.3.6.1.4.1.186.1.19.2.3.7.4ScalarupsStsCtlCfgModeRequestread-writemandatoryThe mode of the UPS system requested by the user.
1.3.6.1.4.1.186.1.19.2.3.7.5ScalarupsStsCtlCfgModeTransitionTimerread-writemandatoryThe timer upon whose expiration a mode transition will be attempted by the system.
1.3.6.1.4.1.186.1.19.2.3.7.6ScalarupsStsCtlCfgEPOContactStateread-onlymandatoryThe EPO contact state of the UPS system.
1.3.6.1.4.1.186.1.19.2.3.7.7ScalarupsStsCtlCfgRunStopSwitchStateread-onlymandatoryThe Run/Stop switch state of the UPS system.
1.3.6.1.4.1.186.1.19.2.3.7.8ScalarupsStsCtlCfgServicePortCommStatusread-onlymandatoryThe service port communication status.
1.3.6.1.4.1.186.1.19.2.3.7.9ScalarupsStsCtlCfgInternalCommStatusread-onlymandatoryThe internal communication status of the UPS system such as display panel.
1.3.6.1.4.1.186.1.19.2.3.7.10ScalarupsStsCtlCfgSecurityLevelread-writemandatoryThe current security level of the UPS system
1.3.6.1.4.1.186.1.19.2.3.7.11ScalarupsStsCtlCfgPresentDateread-writemandatoryThe present date of the UPS. This is configurable by Administrator.
1.3.6.1.4.1.186.1.19.2.3.7.12ScalarupsStsCtlCfgPresentTimeread-writemandatoryThe present time of the UPS. This is configurable by Administrator.
1.3.6.1.4.1.186.1.19.2.3.7.13ScalarupsStsCtlCfgPresentTimeStampread-onlymandatoryPresent system timestamp.
1.3.6.1.4.1.186.1.19.2.3.7.14ScalarupsStsCtlCfgEnableRMTIToControlModeread-writemandatoryAllow to enable or disable SNMP to control the UPS Shutdown and Online Mode.
1.3.6.1.4.1.186.1.19.2.3.7.15ScalarupsStsCtlCfgEnableStartupDelayread-writemandatoryThis delay timer, when enabled, will begin counting down at UPS startup immediately following a UPS shutdown by any means other than battery exhaustion. UPS ou…
1.3.6.1.4.1.186.1.19.2.3.7.16ScalarupsStsCtlCfgStartUpDelayModeread-writemandatoryUPS mode into which the UPS will transition at the expiration of the Start-Up delay timer.
1.3.6.1.4.1.186.1.19.2.3.7.17ScalarupsStsCtlCfgStartUpDelayread-writemandatoryWhen the timer is counting down, its changing value is reflected, otherwise its starting value is reported.
1.3.6.1.4.1.186.1.19.2.3.7.18ScalarupsStsCtlCfgRemoteShutDownContactStateread-onlymandatoryThe state of the Remote Contacts Shutdown Control.
1.3.6.1.4.1.186.1.19.2.3.7.19ScalarupsStsCtlCfgRemoteShutdownContactModeread-writemandatoryThe mode of the Remote Contacts Shutdown control.
1.3.6.1.4.1.186.1.19.2.3.7.20ScalarupsStsCtlCfgEnableDryContactLANShutdownread-writemandatoryWhen enable, UPS will accept LAN signal request for UPS shutdown but only in accordance with restrictions of the following timer.
1.3.6.1.4.1.186.1.19.2.3.7.21ScalarupsStsCtlCfgDryContactLANShutdownTimerread-writemandatoryTimer begins upon input power recovery and during its lifetime, allows the LAN input signal to affect a UPS Shutdown control.
1.3.6.1.4.1.186.1.19.2.3.7.22ScalarupsStsCtlCfgDryContactOnBattDelayread-writemandatoryTime delay between actual event occurrence and dry contact closure to signal external devices of the event.
1.3.6.1.4.1.186.1.19.2.3.7.23ScalarupsStsCtlCfgDryContactLowBattDelayread-writemandatoryDelay timer between actual event occurrence and dry contact closure to signal external devices of the event.
1.3.6.1.4.1.186.1.19.2.3.7.24ScalarupsStsCtlCfgEnableStartupBattTestread-writemandatoryForces a battery test when UPS starts.
1.3.6.1.4.1.186.1.19.2.3.7.25ScalarupsStsCtlCfgEnableBatteryTestread-writemandatoryAllow to enable or disable battery test.
1.3.6.1.4.1.186.1.19.2.3.7.26ScalarupsStsCtlCfgBatteryTestConditionStatusread-onlymandatoryThis notifies the user of the availability of the battery test feature.
1.3.6.1.4.1.186.1.19.2.3.7.27ScalarupsStsCtlCfgMaxBatteryTestFreqread-writemandatoryThis specified how often the battery test should occur. This is set by the administrator
1.3.6.1.4.1.186.1.19.2.3.7.28ScalarupsStsCtlCfgEnableRestartAfterBattShutdownread-writemandatoryMode set for UPS input power detection immediately after a shutdown while on batteries. This is set by the administrator.
1.3.6.1.4.1.186.1.19.2.3.7.29ScalarupsStsCtlCfgRestartDelayread-writemandatoryCountdown begins only when UPS input power is restored immediately following a UPS Shutdown while on batteries.
1.3.6.1.4.1.186.1.19.2.3.7.30ScalarupsStsCtlCfgEnableAutoTransferModeread-writemandatoryThis feature allows the administrators to enable or to disable the auto transfer feature of the UPS.
1.3.6.1.4.1.186.1.19.2.3.7.31ScalarupsStsCtlCfgAutoRetransferDelayread-writemandatoryTime period to wait after fault occurrence before attempting transfer back Online
1.3.6.1.4.1.186.1.19.2.3.7.32ScalarupsStsCtlCfgServicePortCommSettingread-writemandatoryThe UPS baud rate settings.
1.3.6.1.4.1.186.1.19.2.3.7.33ScalarupsStsCtlCfgInvertRemoteShutdownLogicread-writemandatoryRemote Shutdown logic.
1.3.6.1.4.1.186.1.19.2.3.7.34ScalarupsStsCtlCfgRestartModeread-writemandatoryRestart Mode.
1.3.6.1.4.1.186.1.19.2.3.8NodeupsHistory
1.3.6.1.4.1.186.1.19.2.3.8NodeupsTrapDCBusOverCurrentClearFault Clear: A DC bus overcurrent reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.8.1ScalarupsHistorySysOperationTimeread-onlymandatoryThe amount of time the UPS has been on.
1.3.6.1.4.1.186.1.19.2.3.8.2ScalarupsHistoryInverterOperationTimeread-onlymandatoryThe amount of time the UPS has been in On-Line Mode.
1.3.6.1.4.1.186.1.19.2.3.8.3ScalarupsHistoryBackupOperationTimeread-onlymandatoryThe amount of time the UPS has been in BackUp Mode.
1.3.6.1.4.1.186.1.19.2.3.8.4ScalarupsHistoryLifetimeRemainingread-onlymandatoryThe remaining lifetime of the UPS.
1.3.6.1.4.1.186.1.19.2.3.8.5ScalarupsHistoryHighestSystemTempread-onlymandatoryThe highest system temperature of the UPS.
1.3.6.1.4.1.186.1.19.2.3.8.6ScalarupsHistoryHighestBatteryTempread-onlymandatoryThe highest battery temperature.
1.3.6.1.4.1.186.1.19.2.3.8.7ScalarupsHistoryTotalNumInputUnderVoltread-onlymandatoryTotal number of times the UPS has entered under voltage state.
1.3.6.1.4.1.186.1.19.2.3.8.8ScalarupsHistoryTotalNumOverloadread-onlymandatoryTotal number of times the UPS has been overloaded.
1.3.6.1.4.1.186.1.19.2.3.8.9ScalarupsHistoryTotalNumTestread-onlymandatoryTotal number of tests that has been conducted on the UPS.
1.3.6.1.4.1.186.1.19.2.3.8.10ScalarupsHistoryTotalNumBackupread-onlymandatoryTotal number of times the UPS has been in Back-Up mode.
1.3.6.1.4.1.186.1.19.2.3.8.11ScalarupsHistoryTotalNumFaultsread-onlymandatoryTotal number of faults that has occurred on the UPS.
1.3.6.1.4.1.186.1.19.2.3.8.12ScalarupsHistoryTotalNumOperationModeChangeread-onlymandatoryThe number of mode changes that has occurred.
1.3.6.1.4.1.186.1.19.2.3.8.13ScalarupsHistoryTotalNumWarningsread-onlymandatoryThe number of warnings that has occurred on the UPS.
1.3.6.1.4.1.186.1.19.2.3.8.14ScalarupsHistoryTotalNumSystemSettingsChangedread-onlymandatoryThe number of times the System settings have been changed.
1.3.6.1.4.1.186.1.19.2.3.8.15ScalarupsHistoryTotalNumResetsread-onlymandatoryThe number of times the UPS has reset.
1.3.6.1.4.1.186.1.19.2.3.9NodeupsDisplay
1.3.6.1.4.1.186.1.19.2.3.9NodeupsTrapDCBusOverVoltageFault: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.9.1ScalarupsDisplayFirmwareVersionread-onlymandatoryThe firmware version of the display.
1.3.6.1.4.1.186.1.19.2.3.9.2ScalarupsDisplayBootSectorVersionread-onlymandatoryThe boot sector version of the display.
1.3.6.1.4.1.186.1.19.2.3.9.3ScalarupsDisplayBootLoaderVersionread-onlymandatoryThe boot loader version of the display.
1.3.6.1.4.1.186.1.19.2.3.9.4ScalarupsDisplaySleepTimerread-writemandatoryThe sleep timer for the display.
1.3.6.1.4.1.186.1.19.2.3.9.5ScalarupsDisplayBuzzerModeread-writemandatoryConfigures buzzer mode.
1.3.6.1.4.1.186.1.19.2.3.9.6ScalarupsDisplayBuzzerStatusread-onlymandatoryShows the current state of the buzzer.
1.3.6.1.4.1.186.1.19.2.3.9.7ScalarupsDisplayRMTIInstallDateread-onlymandatoryThe RMTI installation date.
1.3.6.1.4.1.186.1.19.2.3.9.8ScalarupsDisplayRMTIInstallStatusread-onlymandatoryShows the installation status of the RMTI.
1.3.6.1.4.1.186.1.19.2.3.9.9ScalarupsDisplayRMTIBaudRateread-onlymandatoryConfigures the baud rate.
1.3.6.1.4.1.186.1.19.2.3.9.10ScalarupsDisplayRMTIDataLinkread-onlymandatoryShows the data status of the RMTI.
1.3.6.1.4.1.186.1.19.2.3.9.11ScalarupsDisplayRMTINetworkLinkread-onlymandatoryShows the network status of the RMTI.
1.3.6.1.4.1.186.1.19.2.3.10NodeupsAlarm
1.3.6.1.4.1.186.1.19.2.3.10NodeupsTrapDCBusOverVoltageClearFault Clear: A DC bus overvoltage reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.10.1ScalarupsAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.186.1.19.2.3.10.2TableupsAlarmTablenot-accessiblemandatoryA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.186.1.19.2.3.10.2.1RowupsAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.186.1.19.2.3.10.2.1.1ColumnupsAlarmIdnot-accessiblemandatoryAn unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.186.1.19.2.3.10.2.1.2ColumnupsAlarmDescrread-onlymandatoryA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.186.1.19.2.3.10.2.1.3ColumnupsAlarmTimeread-onlymandatoryThe value of upsConfigSystemTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed…
1.3.6.1.4.1.186.1.19.2.3.10.3NodeupsWellKnownAlarms
1.3.6.1.4.1.186.1.19.2.3.10.3.1ScalarupsAlarmFaultread-onlymandatoryFault: One or more fault reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.2ScalarupsAlarmOpenFuseread-onlymandatoryFault: An open fuse reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.3ScalarupsAlarmCurrentLimitFaultread-onlymandatoryFault: A current limit reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.4ScalarupsAlarmDCBusOverCurrentread-onlymandatoryFault: A DC bus overcurrent reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.5ScalarupsAlarmDCOverVoltageread-onlymandatoryFault: A DC bus overvoltage repoprted.
1.3.6.1.4.1.186.1.19.2.3.10.3.6ScalarupsAlarmDCBusImbalanceread-onlymandatoryFault: A DC bus imbalance reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.7ScalarupsAlarmOutputUnderVoltageread-onlymandatoryFault: An inverter output undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.8ScalarupsAlarmOutputOverVoltageread-onlymandatoryFault: An inverter output overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.9ScalarupsAlarmHeatSinkOverheatread-onlymandatoryFault: Heat sink or device overheat reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.10ScalarupsAlarmBypassOverloadread-onlymandatoryFault: A bypass overload reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.11ScalarupsAlarmChargerOverVoltageFaultread-onlymandatoryFault: Charger overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.12ScalarupsAlarmOutputOverCurrentread-onlymandatoryFault: A output overcurrent reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.13ScalarupsAlarmDCUnderVoltAtBoostUpread-onlymandatoryFault: A DC bus undervoltage reported during DC bus boost-up.
1.3.6.1.4.1.186.1.19.2.3.10.3.14ScalarupsAlarmDCUnderVoltAtChargeread-onlymandatoryFault: A DC bus undervoltage during DC bus charging reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.15ScalarupsAlarmBypassOverheatread-onlymandatoryFault: A bypass Overheat reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.16ScalarupsAlarmResettableInverterOverloadread-onlymandatoryFault: An inverter overload reported. It is resetable.
1.3.6.1.4.1.186.1.19.2.3.10.3.17ScalarupsAlarmUnresettableInverterOverloadread-onlymandatoryFault: An inverter overload reported. It is not resetable.
1.3.6.1.4.1.186.1.19.2.3.10.3.18ScalarupsAlarmInputOverVoltageread-onlymandatoryWarning: An input overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.19ScalarupsAlarmInputUnderVoltageread-onlymandatoryWarning: An input undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.20ScalarupsAlarmInputFrequencyErrorread-onlymandatoryWarning: An input frequency error reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.21ScalarupsAlarmBypassOverVoltageread-onlymandatoryWarning: A bypass overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.22ScalarupsAlarmBypassUnderVoltageread-onlymandatoryWarning: A bypass undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.23ScalarupsAlarmBypassFrequencyErrorread-onlymandatoryWarning: An bypass frequency error reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.24ScalarupsAlarmDCBusUnderVoltAtBattTestread-onlymandatoryWarning: A DC bus undervoltage reported during battery test
1.3.6.1.4.1.186.1.19.2.3.10.3.25ScalarupsAlarmBatteryLowread-onlymandatoryWarning: A Low battery reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.26ScalarupsAlarmBatteryAtShutdownlevelread-onlymandatoryWarning: A Battery shutdown voltage level reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.27ScalarupsAlarmReplaceBatteryread-onlymandatoryWarning: Batteries are in need of replacement.
1.3.6.1.4.1.186.1.19.2.3.10.3.28ScalarupsAlarmChargerOverVoltageWarningread-onlymandatoryWarning: Charger overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.29ScalarupsAlarmBatteryTestFailedread-onlymandatoryWarning: A battery test failed event reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.30ScalarupsAlarmBatteryDepletedread-onlymandatoryWarning: A battery depleted event reported. It will not be able to support critical loads.
1.3.6.1.4.1.186.1.19.2.3.10.3.31ScalarupsAlarmBatteryOverheatread-onlymandatoryWarning: A Battery overheat reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.32ScalarupsAlarmSystemOverheatread-onlymandatoryWarning: A system overheat reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.33ScalarupsAlarmOutputOverloadWarningread-onlymandatoryWarning: An inverter output overload reported. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Loa…
1.3.6.1.4.1.186.1.19.2.3.10.3.34ScalarupsAlarmCurrentLimitWarningread-onlymandatoryWarning: A current limit reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.35ScalarupsAlarmAsyncOperationread-onlymandatoryWarning: An Asynchronous operation reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.36ScalarupsAlarmServiceUPSread-onlymandatoryWarning: UPS is in need of service. Please contact authorized Toshiba service center for assistance.
1.3.6.1.4.1.186.1.19.2.3.10.3.37ScalarupsAlarmBatteryNearExpirationread-onlymandatoryWarning: Batteries are nearing the end of their expected lifetime.
1.3.6.1.4.1.186.1.19.2.3.10.3.38ScalarupsAlarmBatteryExpiredread-onlymandatoryWarning: Batteries have reached their expected lifetime.
1.3.6.1.4.1.186.1.19.2.3.10.3.39ScalarupsAlarmDisplayCableErrorread-onlymandatoryWarning: A display cable error reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.40ScalarupsAlarmRemotEyeCommErrorread-onlymandatoryWarning: A Communication error between the main control and the RemotEye reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.41ScalarupsAlarmRemotEyeUplinkCommErrorread-onlymandatoryWarning: A communication error between the RemotEye III and the network reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.42ScalarupsAlarmServicePortCommErrorread-onlymandatoryWarning: A communication error between the main controller and the service communication port reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.43ScalarupsAlarmDispCommErrorread-onlymandatoryWarning: A communication error between the main controller and display controller reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.44ScalarupsAlarmSystemTestFailedread-onlymandatoryWarning: A system test failed event reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.45ScalarupsAlarmBypassOnread-onlymandatoryWarning: The UPS is in Stop (Bypass) mode
1.3.6.1.4.1.186.1.19.2.3.10.3.46ScalarupsAlarmPowerFailureread-onlymandatoryInfo: A power failure reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.47ScalarupsAlarmShutdownPendingread-onlymandatoryInfo: An output shutdown in progress reported. Output will turn off after delay.
1.3.6.1.4.1.186.1.19.2.3.10.3.48ScalarupsAlarmOutputOffAsRequestedread-onlymandatoryInfo: An output shutdown mode requested.
1.3.6.1.4.1.186.1.19.2.3.10.3.49ScalarupsAlarmOutputOffread-onlymandatoryInfo: An output off reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.50ScalarupsAlarmBatteryTestInProgressread-onlymandatoryInfo: A battery test in progress reported.
1.3.6.1.4.1.186.1.19.2.3.10.3.51ScalarupsAlarmBatteryOnread-onlymandatoryInfo: The UPS is on Battery mode; it is supplying output power from its batteries.
1.3.6.1.4.1.186.1.19.2.3.10.3.52ScalarupsAlarmEMDSensor1AlarmTriggeredread-onlymandatoryInfo: EMD sensor 1 alarm is triggered.
1.3.6.1.4.1.186.1.19.2.3.10.3.53ScalarupsAlarmEMDSensor2AlarmTriggeredread-onlymandatoryInfo: EMD sensor 2 alarm is triggered.
1.3.6.1.4.1.186.1.19.2.3.10.3.54ScalarupsAlarmEMDHumidityAtLowCriticalPointread-onlymandatoryInfo: EMD humidity is at low critical point.
1.3.6.1.4.1.186.1.19.2.3.10.3.55ScalarupsAlarmEMDHumidityAtHighCriticalPointread-onlymandatoryInfo: EMD humidity is at high critical point.
1.3.6.1.4.1.186.1.19.2.3.10.3.56ScalarupsAlarmEMDHumidityAtLowWarningPointread-onlymandatoryInfo: EMD humidity is at low warning point.
1.3.6.1.4.1.186.1.19.2.3.10.3.57ScalarupsAlarmEMDHumidityAtHighWarningPointread-onlymandatoryInfo: EMD humidity is at high warning point.
1.3.6.1.4.1.186.1.19.2.3.10.3.58ScalarupsAlarmEMDTemperatureAtLowCriticalPointread-onlymandatoryInfo: EMD Temperature is at low critical point.
1.3.6.1.4.1.186.1.19.2.3.10.3.59ScalarupsAlarmEMDTemperatureAtHighCriticalPointread-onlymandatoryInfo: EMD Temperature is at high critical point.
1.3.6.1.4.1.186.1.19.2.3.10.3.60ScalarupsAlarmEMDTemperatureAtLowWarningPointread-onlymandatoryInfo: EMD Temperature is at low warning point.
1.3.6.1.4.1.186.1.19.2.3.10.3.61ScalarupsAlarmEMDTemperatureAtHighWarningPointread-onlymandatoryInfo: EMD Temperature is at high warning point.
1.3.6.1.4.1.186.1.19.2.3.10.3.62ScalarupsAlarmLogInErrorread-onlymandatoryInfo: Username/Password information is incorrect.
1.3.6.1.4.1.186.1.19.2.3.11NodeupsPassword
1.3.6.1.4.1.186.1.19.2.3.11NodeupsTrapDCBusImbalanceFault: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.11.1ScalarupsPwdAdminCurrentAccessLevelread-onlymandatoryThe administrator access level.
1.3.6.1.4.1.186.1.19.2.3.11.2ScalarupsPwdAdminCurrentLoginread-writemandatoryThe administrator access login name.
1.3.6.1.4.1.186.1.19.2.3.11.3ScalarupsPwdAdminNewLoginAccessread-writemandatoryThe administrator access login name.
1.3.6.1.4.1.186.1.19.2.3.11.4ScalarupsPwdAdminCurrentPswdread-writemandatoryThe current password.
1.3.6.1.4.1.186.1.19.2.3.11.5ScalarupsPwdAdminNewPswdread-writemandatoryThe current password.
1.3.6.1.4.1.186.1.19.2.3.12NodeupsAgent
1.3.6.1.4.1.186.1.19.2.3.12NodeupsTrapDCBusImbalanceClearFault Clear: A DC bus imbalance reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.12.1ScalarupsAgentSoftwareVersionread-onlymandatoryThe RemotEye III version number
1.3.6.1.4.1.186.1.19.2.3.12.2ScalarupsAgentHardwareAddressread-onlymandatoryThe hardware/MAC address that NMS can identify the managed device
1.3.6.1.4.1.186.1.19.2.3.12.3ScalarupsAgentIPAddressread-writemandatoryThe ip address that NMS can identify the managed device
1.3.6.1.4.1.186.1.19.2.3.12.4ScalarupsAgentGatewayAddressread-writemandatoryThe default gateway that allow device managed through routers
1.3.6.1.4.1.186.1.19.2.3.12.5ScalarupsAgentSubnetMaskread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.186.1.19.2.3.12.6ScalarupsAgentDateread-writemandatoryThe date in agent, format is MM/DD/YYYY.
1.3.6.1.4.1.186.1.19.2.3.12.7ScalarupsAgentTimeread-writemandatoryThe time in agent, format is HH:MM:SS.
1.3.6.1.4.1.186.1.19.2.3.12.8ScalarupsAgentGeneralRecordLogFrequencyread-writemandatoryThe interval frequency of the general record log. The value is in seconds.
1.3.6.1.4.1.186.1.19.2.3.12.9ScalarupsAgentPollingRateread-writemandatoryThe frequency that proxy agent polls the connected UPS in RemotEye III protocols.
1.3.6.1.4.1.186.1.19.2.3.12.10ScalarupsAgentDHCPControlread-writemandatoryEnable or disable DHCP/BootP capability
1.3.6.1.4.1.186.1.19.2.3.12.11ScalarupsAgentTelnetControlread-writemandatoryEnable or disable telnet access
1.3.6.1.4.1.186.1.19.2.3.12.12ScalarupsAgentTFTPControlread-writemandatoryEnable or disable network upgrade capability
1.3.6.1.4.1.186.1.19.2.3.12.13ScalarupsAgentResetToDefaultread-writemandatoryReset all parameters of REMOTEYE III to default value
1.3.6.1.4.1.186.1.19.2.3.12.14ScalarupsAgentRestartread-writemandatoryRestart REMOTEYE III
1.3.6.1.4.1.186.1.19.2.3.12.15ScalarupsAgentSystemNameread-writemandatoryThe Agent System name
1.3.6.1.4.1.186.1.19.2.3.12.16ScalarupsAgentSystemContactread-writemandatoryContact Information
1.3.6.1.4.1.186.1.19.2.3.12.17ScalarupsAgentSystemLocationread-writemandatoryAgent Location
1.3.6.1.4.1.186.1.19.2.3.12.18ScalarupsAgentDefaultLanguageread-writemandatoryCurrent Default Language
1.3.6.1.4.1.186.1.19.2.3.12.19ScalarupsAgentClearGeneralHistoryread-writemandatoryClear general history log data
1.3.6.1.4.1.186.1.19.2.3.12.20ScalarupsAgentClearTestHistoryread-writemandatoryClear test history log data
1.3.6.1.4.1.186.1.19.2.3.12.21ScalarupsAgentClearBackupHistoryread-writemandatoryClear Backup history log data
1.3.6.1.4.1.186.1.19.2.3.12.22ScalarupsAgentClearFaultHistoryread-writemandatoryClear Fault history log data
1.3.6.1.4.1.186.1.19.2.3.12.23ScalarupsAgentClearOperationModeHistoryread-writemandatoryClear operation mode history log data
1.3.6.1.4.1.186.1.19.2.3.12.24ScalarupsAgentClearWarningHistoryread-writemandatoryClear warning history log data
1.3.6.1.4.1.186.1.19.2.3.12.25ScalarupsAgentClearSystemsettingsChangeHistoryread-writemandatoryClear System settings change history log data
1.3.6.1.4.1.186.1.19.2.3.12.26ScalarupsAgentClearRMTIEventHistoryread-writemandatoryClear RemotEye Event History log data
1.3.6.1.4.1.186.1.19.2.3.13NodeupsConnectedClients
1.3.6.1.4.1.186.1.19.2.3.13NodeupsTrapOutputUnderVoltageFault: An output undervoltage reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.13.1ScalarupsConnectedClientsNumread-onlymandatoryThe count of clients which have registered for UPS Shutdown control.
1.3.6.1.4.1.186.1.19.2.3.13.2TableupsConnectedClientsTablenot-accessiblemandatoryThe devices powered by UPS and registered to RemotEye III
1.3.6.1.4.1.186.1.19.2.3.13.2.1RowupsConnectedClientsEntrynot-accessiblemandatoryThe devices protected by RemotEye III
1.3.6.1.4.1.186.1.19.2.3.13.2.1.1ColumnupsConnectedClientsIndexnot-accessiblemandatoryThe index of the device that is plugged into the UPS.
1.3.6.1.4.1.186.1.19.2.3.13.2.1.2ColumnupsConnectedClientsIPAddressread-onlymandatoryThe ip address of the device.
1.3.6.1.4.1.186.1.19.2.3.13.2.1.3ColumnupsConnectedClientsNameread-onlymandatoryThe name/description of the device plugged into the UPS.
1.3.6.1.4.1.186.1.19.2.3.13.2.1.4ColumnupsConnectedClientsTimeAtConnectionread-onlymandatoryThe time that the device registered to REMOTEYE III
1.3.6.1.4.1.186.1.19.2.3.13.2.1.5ColumnupsConnectedClientsShutdownDelayread-onlymandatoryThe shutdown delay set on REMOTEYE III
1.3.6.1.4.1.186.1.19.2.3.13.2.1.6ColumnupsConnectedClientsConnectionTimeoutread-onlymandatoryThe device timeout counter. Unit: 10 seconds
1.3.6.1.4.1.186.1.19.2.3.13.2.1.7ColumnupsConnectedClientsShutdownTestread-onlymandatoryThe client will shutdown test after receive shutdown request from REMOTEYE III.
1.3.6.1.4.1.186.1.19.2.3.14NodeupsEmail
1.3.6.1.4.1.186.1.19.2.3.14NodeupsTrapOutputUnderVoltageClearFault Clear: An output undervoltage reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.14.1ScalarupsEmailMailServerread-writemandatoryThe Email mail server for REMOTEYE III.
1.3.6.1.4.1.186.1.19.2.3.14.2ScalarupsEmailUserAccountread-writemandatoryThe Email mail server login name.
1.3.6.1.4.1.186.1.19.2.3.14.3ScalarupsEmailUserPasswordread-writemandatoryThe Email mail server password.
1.3.6.1.4.1.186.1.19.2.3.14.4ScalarupsEmailDomainNameread-writemandatoryThe Email mail server domain name
1.3.6.1.4.1.186.1.19.2.3.14.5ScalarupsEmailDNSServerread-writemandatoryThe Email DNS server name
1.3.6.1.4.1.186.1.19.2.3.14.6ScalarupsEmailStatusReportSendTimeread-writemandatoryThe Email Status Report Send Time
1.3.6.1.4.1.186.1.19.2.3.14.7TableupsEmailClientsTablenot-accessiblemandatoryThe email addresses that RemotEye III will send logs and status reports to.
1.3.6.1.4.1.186.1.19.2.3.14.7.1RowupsEmailClientsEntrynot-accessiblemandatoryThe email addresses that RemotEye III will send logs and status reports to.
1.3.6.1.4.1.186.1.19.2.3.14.7.1.1ColumnupsEmailClientsIndexread-onlymandatoryThe index of the email clients.
1.3.6.1.4.1.186.1.19.2.3.14.7.1.2ColumnupsEmailClientsEmailAddressread-writemandatoryThe email address of the clients.
1.3.6.1.4.1.186.1.19.2.3.14.7.1.3ColumnupsEmailClientsDescriptionread-writemandatoryThe name/description of the clients.
1.3.6.1.4.1.186.1.19.2.3.14.7.1.4ColumnupsEmailClientsDailyStatusReportTyperead-writemandatoryThe type of daily information that clients would like to receive.
1.3.6.1.4.1.186.1.19.2.3.14.7.1.5ColumnupsEmailClientsEventStatusReportTyperead-writemandatoryThe type of event information that clients would like to receive when event occurs.
1.3.6.1.4.1.186.1.19.2.3.14.7.1.6ColumnupsEmailClientsInfoLevelread-writemandatoryThe type of information that clients would like to receive.
1.3.6.1.4.1.186.1.19.2.3.15NodeupsSNMP
1.3.6.1.4.1.186.1.19.2.3.15NodeupsTrapOutputOverVoltageFault: An output overvoltage reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.15.1ScalarupsSNMPVersionread-onlymandatoryThe SNMP version
1.3.6.1.4.1.186.1.19.2.3.15.2TableupsSNMPTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of upsSNMPNumTrapReceivers
1.3.6.1.4.1.186.1.19.2.3.15.2.1RowupsSNMPTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.186.1.19.2.3.15.2.1.1ColumnupsSNMPTrapsReceiversIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.186.1.19.2.3.15.2.1.2ColumnupsSNMPTrapsReceiversIPAddressread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.186.1.19.2.3.15.2.1.3ColumnupsSNMPTrapReceiversCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.186.1.19.2.3.15.2.1.4ColumnupsSNMPTrapReceiversTrapTyperead-writemandatoryThe trap group that NMS desired.
1.3.6.1.4.1.186.1.19.2.3.15.2.1.5ColumnupsSNMPTrapReceiversInfoReceivingSeverityLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.186.1.19.2.3.15.2.1.6ColumnupsSNMPTrapReceiversDescriptionread-writemandatoryDescription of trap receivers
1.3.6.1.4.1.186.1.19.2.3.15.3TableupsSNMPCommunitiesTablenot-accessiblemandatoryA list of managers which can access REMOTEYE III with private community string.
1.3.6.1.4.1.186.1.19.2.3.15.3.1RowupsSNMPCommunitiesEntrynot-accessiblemandatoryThe managers.
1.3.6.1.4.1.186.1.19.2.3.15.3.1.1ColumnupsSNMPCommunitiesIndexread-onlymandatoryThe index to a access control entry.
1.3.6.1.4.1.186.1.19.2.3.15.3.1.2ColumnupsSNMPCommunitiesIPAddressread-writemandatoryThe IP address of the manager to access REMOTEYE III
1.3.6.1.4.1.186.1.19.2.3.15.3.1.3ColumnupsSNMPCommunitiesAccessStringread-writemandatoryThe community name to use in the manager when access REMOTEYE III
1.3.6.1.4.1.186.1.19.2.3.15.3.1.4ColumnupsSNMPCommunitiesAccessModeread-writemandatoryAccess type, only read/Write access type can change parameter of REMOTEYE III
1.3.6.1.4.1.186.1.19.2.3.16NodeupsEMD
1.3.6.1.4.1.186.1.19.2.3.16NodeupsTrapOutputOverVoltageClearFault Clear: An output overvoltage reported. Contact your Toshiba authorized service center for examination.
1.3.6.1.4.1.186.1.19.2.3.16.1ScalarupsEMDTyperead-onlymandatoryThe name assign to specific EMD.
1.3.6.1.4.1.186.1.19.2.3.16.2ScalarupsEMDTemperatureread-onlymandatoryThe EMD temperature.
1.3.6.1.4.1.186.1.19.2.3.16.3ScalarupsEMDTemperatureLowWarningSetPointread-writemandatoryThe EMD temperature low warning set point.
1.3.6.1.4.1.186.1.19.2.3.16.4ScalarupsEMDTemperatureLowCriticalSetPointread-writemandatoryThe EMD temperature low critical set point.
1.3.6.1.4.1.186.1.19.2.3.16.5ScalarupsEMDTemperatureHighWarningSetPointread-writemandatoryThe EMD temperature high warning set point.
1.3.6.1.4.1.186.1.19.2.3.16.6ScalarupsEMDTemperatureHighCriticalSetPointread-writemandatoryThe EMD temperature high critical set point.
1.3.6.1.4.1.186.1.19.2.3.16.7ScalarupsEMDTemperatureHysteresisread-writemandatoryThe EMD temperature hysteresis.
1.3.6.1.4.1.186.1.19.2.3.16.8ScalarupsEMDTemperatureCalibrationOffsetread-writemandatoryThe EMD temperature calibration offset.
1.3.6.1.4.1.186.1.19.2.3.16.9ScalarupsEMDHumidityread-onlymandatoryThe EMD Humidity.
1.3.6.1.4.1.186.1.19.2.3.16.10ScalarupsEMDHumidityLowWarningSetPointread-writemandatoryThe EMD Humidity low warning set point.
1.3.6.1.4.1.186.1.19.2.3.16.11ScalarupsEMDHumidityLowCriticalSetPointread-writemandatoryThe EMD Humidity low critical set point.
1.3.6.1.4.1.186.1.19.2.3.16.12ScalarupsEMDHumidityHighWarningSetPointread-writemandatoryThe EMD Humidity high warning set point.
1.3.6.1.4.1.186.1.19.2.3.16.13ScalarupsEMDHumidityHighCriticalSetPointread-writemandatoryThe EMD Humidity high critical set point.
1.3.6.1.4.1.186.1.19.2.3.16.14ScalarupsEMDHumidityHysteresisread-writemandatoryThe EMD Humidity hysteresis.
1.3.6.1.4.1.186.1.19.2.3.16.15ScalarupsEMDHumidityCalibrationOffsetread-writemandatoryThe EMD Humidity calibration offset.
1.3.6.1.4.1.186.1.19.2.3.16.16ScalarupsEMDR1Statusread-onlymandatoryThe EMD dry contact 1 status.
1.3.6.1.4.1.186.1.19.2.3.16.17ScalarupsEMDAlarmR1Enableread-writemandatoryThe EMD contact R1 alarm enable setting.
1.3.6.1.4.1.186.1.19.2.3.16.18ScalarupsEMDAlarmR1Hysteresisread-writemandatoryThe EMD Contact R1 alarm hysteresis.
1.3.6.1.4.1.186.1.19.2.3.16.19ScalarupsEMDR2Statusread-onlymandatoryThe EMD dry contact 2 status.
1.3.6.1.4.1.186.1.19.2.3.16.20ScalarupsEMDAlarmR2Enableread-writemandatoryThe EMD contact R2 alarm enable setting.
1.3.6.1.4.1.186.1.19.2.3.16.21ScalarupsEMDAlarmR2Hysteresisread-writemandatoryThe EMD Contact R2 alarm hysteresis.
1.3.6.1.4.1.186.1.19.2.3.17NodeupsTrapHeatSinkOverheatFault: A Heat sink or device overheat reported.
1.3.6.1.4.1.186.1.19.2.3.18NodeupsTrapHeatSinkOverheatClearFault Clear: A Heat sink or device overheat reported.
1.3.6.1.4.1.186.1.19.2.3.19NodeupsTrapBypassOverloadFault: A bypass overload reported.
1.3.6.1.4.1.186.1.19.2.3.20NodeupsTrapBypassOverloadClearFault Clear: A bypass overload reported.
1.3.6.1.4.1.186.1.19.2.3.21NodeupsTrap
1.3.6.1.4.1.186.1.19.2.3.21NodeupsTrapChargerOvervoltageFaultWarning: Charger overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.22NodeupsTrapChargerOvervoltageFaultClearWarning Clear: Charger overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.23NodeupsTrapOutputOvercurrentWarning: An output overcurrent reported.
1.3.6.1.4.1.186.1.19.2.3.24NodeupsTrapOutputOvercurrentClearWarning Clear: An output overcurrent reported.
1.3.6.1.4.1.186.1.19.2.3.25NodeupsTrapDCUnderVoltageAtBoostUpFault: A DC bus undervoltage during boost-up reported.
1.3.6.1.4.1.186.1.19.2.3.26NodeupsTrapDCUnderVoltageAtBoostUpClearFault Clear: A DC bus undervoltage during boost-up reported.
1.3.6.1.4.1.186.1.19.2.3.27NodeupsTrapDCUnderVoltageAtChargeFault: A DC bus undervoltage during charging reported.
1.3.6.1.4.1.186.1.19.2.3.28NodeupsTrapDCUnderVoltageAtChargeClearFault Clear: A DC bus undervoltage during charging reported.
1.3.6.1.4.1.186.1.19.2.3.29NodeupsTrapBypassOverheatFault: A Bypass overheat reported.
1.3.6.1.4.1.186.1.19.2.3.30NodeupsTrapBypassOverheatClearFault Clear: A Bypass overheat reported.
1.3.6.1.4.1.186.1.19.2.3.31NodeupsTrapResettableInverterOverloadFault: An inverter overload reported. It is resettable.
1.3.6.1.4.1.186.1.19.2.3.32NodeupsTrapResettableInverterOverloadClearFault Clear: An inverter overload reported. It is resettable.
1.3.6.1.4.1.186.1.19.2.3.33NodeupsTrapUnResettableInverterOverloadFault: An inverter overload reported. It is not resettable.
1.3.6.1.4.1.186.1.19.2.3.34NodeupsTrapUnResettableInverterOverloadClearFault Clear: An inverter overload reported. It is not resettable.
1.3.6.1.4.1.186.1.19.2.3.35NodeupsTrapInputOverVoltageWarning: An input overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.36NodeupsTrapInputOverVoltageClearWarning Clear: An input overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.37NodeupsTrapInputUnderVoltageWarning: An input undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.38NodeupsTrapInputUnderVoltageClearWarning Clear: An input undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.39NodeupsTrapInputFrequencyErrorWarning: An input frequency error reported.
1.3.6.1.4.1.186.1.19.2.3.40NodeupsTrapInputFrequencyErrorClearWarning Clear: An input frequency error reported.
1.3.6.1.4.1.186.1.19.2.3.41NodeupsTrapBypassOverVoltageWarning: A bypass overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.42NodeupsTrapBypassOverVoltageClearWarning Clear: A bypass overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.43NodeupsTrapBypassUnderVoltageWarning: A bypass undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.44NodeupsTrapBypassUnderVoltageClearWarning Clear: A bypass undervoltage reported.
1.3.6.1.4.1.186.1.19.2.3.45NodeupsTrapBypassFrequencyErrorWarning: A bypass frequency error reported.
1.3.6.1.4.1.186.1.19.2.3.46NodeupsTrapBypassFrequencyErrorClearWarning Clear: A bypass frequency error reported.
1.3.6.1.4.1.186.1.19.2.3.47NodeupsTrapDCUnderVoltageAtTestWarning: A DC bus undervoltage during battery test reported.
1.3.6.1.4.1.186.1.19.2.3.48NodeupsTrapDCUnderVoltageAtTestClearWarning Clear: A DC bus undervoltage during battery test reported.
1.3.6.1.4.1.186.1.19.2.3.49NodeupsTrapBatteryLowWarning: A low battery level reported.
1.3.6.1.4.1.186.1.19.2.3.50NodeupsTrapBatteryLowClearWarning Clear: A low battery level reported.
1.3.6.1.4.1.186.1.19.2.3.51NodeupsTrapBatteryAtShutdownlevelWarning: A shutdown battery level reported.
1.3.6.1.4.1.186.1.19.2.3.52NodeupsTrapBatteryAtShutdownlevelClearWarning Clear: A shutdown battery level reported.
1.3.6.1.4.1.186.1.19.2.3.53NodeupsTrapReplaceBatteryWarning: A replacement of batteries reported.
1.3.6.1.4.1.186.1.19.2.3.54NodeupsTrapReplaceBatteryClearWarning Clear: A replacement of batteries reported.
1.3.6.1.4.1.186.1.19.2.3.55NodeupsTrapChargerOverVoltageWarningWarning: A charger overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.56NodeupsTrapChargerOverVoltageWarningClearWarning Clear: A charger overvoltage reported.
1.3.6.1.4.1.186.1.19.2.3.57NodeupsTrapBatteryTestFailedWarning: A battery test failed event reported.
1.3.6.1.4.1.186.1.19.2.3.58NodeupsTrapBatteryTestFailedClearWarning Clear: A battery test failed event reported.
1.3.6.1.4.1.186.1.19.2.3.59NodeupsTrapBatteryDepletedWarning: A battery depleted event reported.
1.3.6.1.4.1.186.1.19.2.3.60NodeupsTrapBatteryDepletedClearWarning Clear: A battery depleted event reported.
1.3.6.1.4.1.186.1.19.2.3.61NodeupsTrapBatteryOverheatWarning: A battery overheat reported.
1.3.6.1.4.1.186.1.19.2.3.62NodeupsTrapBatteryOverheatClearWarning Clear: A battery overheat reported.
1.3.6.1.4.1.186.1.19.2.3.63NodeupsTrapSystemOverheatWarning: A system overheat reported.
1.3.6.1.4.1.186.1.19.2.3.64NodeupsTrapSystemOverheatClearWarning Clear: A system overheat reported.
1.3.6.1.4.1.186.1.19.2.3.65NodeupsTrapOutputOverloadWarningWarning: An output overload reported.
1.3.6.1.4.1.186.1.19.2.3.66NodeupsTrapOutputOverloadWarningClearWarning Clear: An output overload reported.
1.3.6.1.4.1.186.1.19.2.3.67NodeupsTrapCurrentLimitWarningWarning: A current limit reported.
1.3.6.1.4.1.186.1.19.2.3.68NodeupsTrapCurrentLimitWarningClearWarning Clear: A current limit reported.
1.3.6.1.4.1.186.1.19.2.3.69NodeupsTrapAsyncOperationWarning: An Asynchronous operation reported.
1.3.6.1.4.1.186.1.19.2.3.70NodeupsTrapAsyncOperationClearWarning Clear: An Asynchronous operation reported.
1.3.6.1.4.1.186.1.19.2.3.71NodeupsTrapServiceUPSWarning: UPS is in need of service.
1.3.6.1.4.1.186.1.19.2.3.72NodeupsTrapServiceUPSClearWarning Clear: UPS is in need of service.
1.3.6.1.4.1.186.1.19.2.3.73NodeupsTrapBatteryNearExpirationWarning: A near expiration of batteries reported.
1.3.6.1.4.1.186.1.19.2.3.74NodeupsTrapBatteryNearExpirationClearWarning Clear: A near expiration of batteries reported.
1.3.6.1.4.1.186.1.19.2.3.75NodeupsTrapBatteryExpiredWarning: A expiration of batteries reported.
1.3.6.1.4.1.186.1.19.2.3.76NodeupsTrapBatteryExpiredClearWarning Clear: A expiration of batteries reported.
1.3.6.1.4.1.186.1.19.2.3.77NodeupsTrapDisplayCableErrorWarning: A display cable error reported.
1.3.6.1.4.1.186.1.19.2.3.78NodeupsTrapDisplayCableErrorClearWarning Clear: A display cable error reported.
1.3.6.1.4.1.186.1.19.2.3.79NodeupsTrapRemotEyeCommErrorWarning: A communication error between the main control and the RemotEye III reported.
1.3.6.1.4.1.186.1.19.2.3.80NodeupsTrapRemotEyeCommErrorClearWarning Clear: A communication error between the main control and the RemotEye III reported.
1.3.6.1.4.1.186.1.19.2.3.81NodeupsTrapRemotEyeUplinkCommErrorWarning: A communication error between the RemotEye III and the network reported.
1.3.6.1.4.1.186.1.19.2.3.82NodeupsTrapRemotEyeUplinkCommErrorClearWarning Clear: A communication error between the RemotEye III and the network reported.
1.3.6.1.4.1.186.1.19.2.3.83NodeupsTrapServicePortCommErrorWarning: A communication error between the main controller and the service port reported.
1.3.6.1.4.1.186.1.19.2.3.84NodeupsTrapServicePortCommErrorClearWarning Clear: A communication error between the main controller and the service port reported.
1.3.6.1.4.1.186.1.19.2.3.85NodeupsTrapDispCommErrorWarning: A communication error between the main controller and the display controller reported.
1.3.6.1.4.1.186.1.19.2.3.86NodeupsTrapDispCommErrorClearWarning Clear: A communication error between the main controller and the display controller reported.
1.3.6.1.4.1.186.1.19.2.3.87NodeupsTrapSystemTestFailedWarning: A system test failed event reported.
1.3.6.1.4.1.186.1.19.2.3.88NodeupsTrapSystemTestFailedClearWarning Clear: A system test failed event reported.
1.3.6.1.4.1.186.1.19.2.3.89NodeupsTrapBypassOnWarning: The UPS is in Stop (Bypass) mode.
1.3.6.1.4.1.186.1.19.2.3.90NodeupsTrapBypassOnClearWarning Clear: The UPS is in Stop (Bypass) mode.
1.3.6.1.4.1.186.1.19.2.3.91NodeupsTrapPowerFailureInfo: A power failure reported.
1.3.6.1.4.1.186.1.19.2.3.92NodeupsTrapPowerFailureClearInfo Clear: A power failure reported.
1.3.6.1.4.1.186.1.19.2.3.93NodeupsTrapShutdownPendingInfo: A output shutdown in progress reported. Output will turn off after delay.
1.3.6.1.4.1.186.1.19.2.3.94NodeupsTrapShutdownPendingClearInfo Clear: A output shutdown in progress reported. Output will turn off after delay.
1.3.6.1.4.1.186.1.19.2.3.95NodeupsTrapOutputOffAsRequestedInfo: An output shutdown mode requested.
1.3.6.1.4.1.186.1.19.2.3.96NodeupsTrapOutputOffAsRequestedClearInfo Clear: An output shutdown mode requested.
1.3.6.1.4.1.186.1.19.2.3.97NodeupsTrapOutputOffInfo: The UPS system output is off.
1.3.6.1.4.1.186.1.19.2.3.98NodeupsTrapOutputOffClearInfo Clear: The UPS system output is off.
1.3.6.1.4.1.186.1.19.2.3.99NodeupsTrapBatteryTestInProgressInfo: A battery test in progress reported.
1.3.6.1.4.1.186.1.19.2.3.100NodeupsTrapBatteryTestInProgressClearInfo Clear: A battery test in progress reported.
1.3.6.1.4.1.186.1.19.2.3.101NodeupsTrapBatteryOnInfo: The UPS is on Battery mode; it is supplying output power from its batteries.
1.3.6.1.4.1.186.1.19.2.3.102NodeupsTrapBatteryOnClearInfo Clear: The UPS is on Battery mode; it is supplying output power from its batteries.
1.3.6.1.4.1.186.1.19.2.3.103NodeupsTrapEMDSensor1AlarmTriggeredWarning: EMD sensor 1 alarm is triggered.
1.3.6.1.4.1.186.1.19.2.3.104NodeupsTrapEMDSensor1AlarmTriggeredClearWarning Clear: EMD sensor 1 alarm is triggered.
1.3.6.1.4.1.186.1.19.2.3.105NodeupsTrapEMDSensor2AlarmTriggeredWarning: EMD sensor 2 alarm is triggered.
1.3.6.1.4.1.186.1.19.2.3.106NodeupsTrapEMDSensor2AlarmTriggeredClearWarning Clear: EMD sensor 2 alarm is triggered.
1.3.6.1.4.1.186.1.19.2.3.107NodeupsTrapEMDHumidityAtLowCiriticalPointWarning: EMD humidity is at low critical point.
1.3.6.1.4.1.186.1.19.2.3.108NodeupsTrapEMDHumidityAtLowCiriticalPointClearWarning Clear: EMD humidity is at low critical point.
1.3.6.1.4.1.186.1.19.2.3.109NodeupsTrapEMDHumidityAtHighCiriticalPointWarning: EMD humidity is at high critical point.
1.3.6.1.4.1.186.1.19.2.3.110NodeupsTrapEMDHumidityAtHighCiriticalPointClearWarning Clear: EMD humidity is at high critical point.
1.3.6.1.4.1.186.1.19.2.3.111NodeupsTrapEMDHumidityAtLowWarningPointWarning: EMD humidity is at low warning point.
1.3.6.1.4.1.186.1.19.2.3.112NodeupsTrapEMDHumidityAtLowWarningPointClearWarning Clear: EMD humidity is at low warning point.
1.3.6.1.4.1.186.1.19.2.3.113NodeupsTrapEMDHumidityAtHighWarningPointWarning: EMD humidity is at high warning point.
1.3.6.1.4.1.186.1.19.2.3.114NodeupsTrapEMDHumidityAtHighWarningPointClearWarning Clear: EMD humidity is at high warning point.
1.3.6.1.4.1.186.1.19.2.3.115NodeupsTrapEMDTemperatureAtLowCiriticalPointWarning: EMD Temperature is at low critical point.
1.3.6.1.4.1.186.1.19.2.3.116NodeupsTrapEMDTemperatureAtLowCiriticalPointClearWarning Clear: EMD Temperature is at low critical point.
1.3.6.1.4.1.186.1.19.2.3.117NodeupsTrapEMDTemperatureAtHighCiriticalPointWarning: EMD Temperature is at high critical point.
1.3.6.1.4.1.186.1.19.2.3.118NodeupsTrapEMDTemperatureAtHighCiriticalPointClearWarning Clear: EMD Temperature is at high critical point.
1.3.6.1.4.1.186.1.19.2.3.119NodeupsTrapEMDTemperatureAtLowWarningPointWarning: EMD Temperature is at low warning point.
1.3.6.1.4.1.186.1.19.2.3.120NodeupsTrapEMDTemperatureAtLowWarningPointClearWarning Clear: EMD Temperature is at low warning point.
1.3.6.1.4.1.186.1.19.2.3.121NodeupsTrapEMDTemperatureAtHighWarningPointWarning: EMD Temperature is at high warning point.
1.3.6.1.4.1.186.1.19.2.3.122NodeupsTrapEMDTemperatureAtHighWarningPointClearWarning Clear: EMD Temperature is at high warning point.
1.3.6.1.4.1.186.1.19.2.3.123NodeupsTrapLogInErrorInfo: Username/Password information is incorrect.
1.3.6.1.4.1.186.1.19.2.3.124NodeupsTrapLogInErrorClearInfo Clear: Username/Password information is incorrect.
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerINTEGER (0..2147483647)
PositiveIntegerINTEGER (0..2147483647)