MIB Viewer

UPSMAN

54 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.1356Nodeupsman
1.3.6.1.4.1.1356.1NodecommunicationLostSEVERE: Communication to the UPS has been lost. Check cable or network connections, steps to reestablish communication are in progress.
1.3.6.1.4.1.1356.1Nodeups
1.3.6.1.4.1.1356.1.1NodeupsIdent
1.3.6.1.4.1.1356.1.1.1ScalarupsIdentModelNameread-onlymandatoryThe UPS model name (e.g. 'O1000S').
1.3.6.1.4.1.1356.1.1.2ScalarupsIdentUpsIDNameread-writemandatoryAn ID string identifying the UPS. This object can be set by the administrator.
1.3.6.1.4.1.1356.1.2NodeupsBattery
1.3.6.1.4.1.1356.1.2.1ScalarupsBatteryStatusread-onlymandatoryThe status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is …
1.3.6.1.4.1.1356.1.2.2ScalarupsBatteryCapacityread-onlymandatoryThe remaining battery capacity expressed in percent of full capacity.
1.3.6.1.4.1.1356.1.2.3ScalarupsBatteryVoltageread-onlymandatoryThe current battery voltage expressed in VDC.
1.3.6.1.4.1.1356.1.2.4ScalarupsBatteryTemperatureread-onlymandatoryThe current internal UPS temperature expressed in Celsius.
1.3.6.1.4.1.1356.1.2.5ScalarupsBatteryRunTimeRemainingread-onlymandatoryThe UPS battery run time remaining before battery exhaustion, in seconds.
1.3.6.1.4.1.1356.1.2.6ScalarupsBatteryLifeTimeRemainingread-onlycurrentForecast of the battery lifetime, replacement recommended in x month. Format: month
1.3.6.1.4.1.1356.1.3NodeupsInput
1.3.6.1.4.1.1356.1.3.1ScalarupsInputLineVoltageread-onlymandatoryThe current utility line voltage in VAC.
1.3.6.1.4.1.1356.1.3.2ScalarupsInputLineFrequenceread-onlymandatoryThe current utility line frequence in Hz.
1.3.6.1.4.1.1356.1.4NodeupsOutput
1.3.6.1.4.1.1356.1.4.1ScalarupsOutputStatusread-onlymandatoryThe current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1).
1.3.6.1.4.1.1356.1.4.2ScalarupsOutputLoadread-onlymandatoryThe current UPS load expressed in percent of rated capacity.
1.3.6.1.4.1.1356.1.4.3ScalarupsOutputFrequencyread-onlycurrentThe present output frequency, format: 0.1 Hertz.
1.3.6.1.4.1.1356.1.4.4ScalarupsOutputVoltageread-onlycurrentThe present output voltage, format: RMS Volts.
1.3.6.1.4.1.1356.1.5NodeupsTest
1.3.6.1.4.1.1356.1.5.1ScalarupsRunTestread-writemandatorySet this value to run a test. If this this variable is set to NoTest(0) no test will be initiated.
1.3.6.1.4.1.1356.1.5.2ScalarupsLastTestPerformedread-onlymandatoryThis value shows which last test was performed. If this value is set to noTest(0) no test has been run since startup.
1.3.6.1.4.1.1356.1.5.3ScalarupsLastTestResultread-onlymandatoryThe current UPS Test Result. If this value is undefined(0) no test has been run since startup.
1.3.6.1.4.1.1356.1.5.4ScalarupsLastTestedBackupTimeread-onlymandatoryThis value shows the last tested backup time in minutes. To acquire a new value perform one of battery test's.
1.3.6.1.4.1.1356.1.6NodeupsControl
1.3.6.1.4.1.1356.1.6.1ScalarupsRunShutdownRestoreread-writemandatorySet this value to run a shutdown procedure. If this this variable is set to (0) nothing happens.
1.3.6.1.4.1.1356.1.6.2ScalarupsShutdownSecsread-writemandatoryThis value indicates the time in seconds after which a ups shutdown will be performed. If this value is (0) shutdown executes immediately.
1.3.6.1.4.1.1356.1.6.3ScalarupsRestoreSecsread-writemandatoryThis value indicates the time in seconds after which a ups restore will be performed. If this value is (0) restore executes immediately.
1.3.6.1.4.1.1356.1.7NodeupsAlarms
1.3.6.1.4.1.1356.1.7.1ScalarupsAlarmFatalFaultStatusread-onlycurrentCRITICAL ALARM : A fatal fault in the UPS has been detected. Detailed information by referring to UpsAlarmFatalFaultDetail Possible causes: Fatal Fault none (-…
1.3.6.1.4.1.1356.1.7.2ScalarupsAlarmWarningStatusread-onlycurrentWARNING : The UPS has detect a minor fault, warning level. Detailed information by referring to UpsAlarmWarningDetail.
1.3.6.1.4.1.1356.1.7.3ScalarupsAlarmInputBadStatusread-onlycurrentAn abnormal condition of the input in the UPS has been detected. Detailed information by referring to UpsAlarmInputBadDetail.
1.3.6.1.4.1.1356.1.7.4ScalarupsAlarmOutputOverloadStatusread-onlycurrentAn abnormal output overload in the UPS has been detected.
1.3.6.1.4.1.1356.1.7.5ScalarupsAlarmBatteryBadStatusread-onlycurrentAn abnormal condition of the battery in the UPS has been detected. Detailed information by referring to UpsAlarmBatteryBadDetail.
1.3.6.1.4.1.1356.1.7.6ScalarupsAlarmTempBadStatusread-onlycurrentAn abnormal condition of the temperature in the UPS has been detected. Detailed information by referring to UpsAlarmTempBadDetail.
1.3.6.1.4.1.1356.2Nodemgmt
1.3.6.1.4.1.1356.2NodeupsOverloadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capcity.
1.3.6.1.4.1.1356.3NodeupsTurnedOffWARNING: The UPS has been turned 'off' by the management station.
1.3.6.1.4.1.1356.4NodecommunicationEstablishedINFORMATION: Communication with the UPS has been established.
1.3.6.1.4.1.1356.5NodepowerRestoredINFORMATION: Utility power has been restored.
1.3.6.1.4.1.1356.6NodeupsOnBatteryWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.1356.7NodetestStartedINFORMATION: A UPS test was started.
1.3.6.1.4.1.1356.8NodetestCompletedINFORMATION: A UPS test is completed. Now a test result should be available in upsTest.lastTestResult.
1.3.6.1.4.1.1356.9NodeupsBatteryLowWARNING: Battery Low.
1.3.6.1.4.1.1356.10NodeupsShutdownImminentINFORMATION: Server Shutdown imminent.
1.3.6.1.4.1.1356.11NodeupsmanStartedINFORMATION: The UpsMan service has been started.
1.3.6.1.4.1.1356.12NodeupsmanTrapInputBadAn abnormal condition of input UPS has been detected.
1.3.6.1.4.1.1356.13NodeupsmanTrapOutputOverloadRemovedThe UPS has returned from an overload situation to normal operation.
1.3.6.1.4.1.1356.14NodeupsmanTrapBatteryBadAn abnormal condition of the UPS batteries has been detected.
1.3.6.1.4.1.1356.15NodeupsmanTrapTempBadAn abnormal UPS temperature has been detected.
1.3.6.1.4.1.1356.16NodeupsmanTrapTempBadRemovedThe abnormal UPS temperature is back to normal level.
1.3.6.1.4.1.1356.17NodeupsmanTrapFatalFaultA fatal fault in the UPS has been detected. The UPS can not backup, contact your UPS service team.