WIENER-CRATE-MIB
173 objects
Introduction of the communication.can branch.
Imported Objects
| SNMPv2-SMI | enterprises Opaque |
| SNMPv2-TC | DisplayString MacAddress TEXTUAL-CONVENTION |
| UCD-SNMP-MIB | -- Float -- |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.19947 | Identitywiener | Introduction of the communication.can branch. | ||
| 1.3.6.1.4.1.19947.1 | Identitycrate | current | SNMP control for electronic crates. A crate is a complete electronic system and consists of the mechanical rack, a power supply, a fan tray and a backplane. Al… | |
| 1.3.6.1.4.1.19947.1.1 | Identitysystem | current | A collection of objects which affect the complete crate | |
| 1.3.6.1.4.1.19947.1.1.1 | ScalarsysMainSwitch | read-write | current | Read: An enumerated value which shows the current state of the crates main switch. Write: Try to switch the complete crate ON or OFF. Only the values ON or OFF… |
| 1.3.6.1.4.1.19947.1.1.2 | ScalarsysStatus | read-only | current | A bit string which shows the status (health) of the complete crate. If a bit is set (1), the explanation is satisfied mainOn (0), system is switched on, indivi… |
| 1.3.6.1.4.1.19947.1.1.3 | ScalarsysVmeSysReset | read-write | current | Read: Always 0. Write: Trigger the generation of the VME SYSRESET or CPIC RESET signal. This signal will be active for a time of 200 ms |
| 1.3.6.1.4.1.19947.1.1.4 | ScalarsysHardwareReset | read-write | current | Triggered a Reset via Watchdog or ResetLine. |
| 1.3.6.1.4.1.19947.1.1.5 | ScalarsysFactoryDefaults | read-write | current | A set operation performs a complete factory reset of ALL data stored in the controller (e.g. community names, passwords, ...). |
| 1.3.6.1.4.1.19947.1.1.10 | ScalarsysConfigDoMeasurementCurrent | read-write | current | CSet the analog inputs to measure voltage or current. |
| 1.3.6.1.4.1.19947.1.1.11 | ScalarsysOperatingTime | read-write | current | The time in seconds for how long the controller was in action. |
| 1.3.6.1.4.1.19947.1.1.1024 | ScalarsysDebugMemory8 | read-write | current | Debug 16-bit memory access. |
| 1.3.6.1.4.1.19947.1.1.1025 | ScalarsysDebugMemory16 | read-write | current | Debug 16-bit memory access. |
| 1.3.6.1.4.1.19947.1.1.1026 | ScalarsysDebugMemory32 | read-write | current | Debug 32-bit memory access. |
| 1.3.6.1.4.1.19947.1.1.1027 | ScalarsysDebug | read-write | current | Debug communication with the MPOD. This is a direct map to the ancient functions which are accessible via USB (without SLIP/SNMP). |
| 1.3.6.1.4.1.19947.1.1.1028 | ScalarsysDebugDisplay | read-write | current | Debug communication with the MPOD display. |
| 1.3.6.1.4.1.19947.1.1.1029 | ScalarsysDebugBoot | read-write | current | Debug communication with the simple debug interface / bootloader. |
| 1.3.6.1.4.1.19947.1.2 | Identityinput | current | All objects which are associated with the power input of the crate | |
| 1.3.6.1.4.1.19947.1.3 | Identityoutput | current | All objects which are associated with the power output of the crate | |
| 1.3.6.1.4.1.19947.1.3.1 | ScalaroutputNumber | read-only | current | The number of output channels of the crate. |
| 1.3.6.1.4.1.19947.1.3.2 | TableoutputTable | not-accessible | current | A list of output entries. |
| 1.3.6.1.4.1.19947.1.3.2.1 | RowoutputEntry | not-accessible | current | A table row |
| 1.3.6.1.4.1.19947.1.3.2.1.1 | ColumnoutputIndex | not-accessible | current | A unique number for each power output channel. Its value ranges between 1 and total number of output channels. This value is equivalent to the output channel n… |
| 1.3.6.1.4.1.19947.1.3.2.1.2 | ColumnoutputName | read-only | current | A textual string containing a short name of the output. If the crate is equipped with an alphanumeric display, this string is shown to identify a output channe… |
| 1.3.6.1.4.1.19947.1.3.2.1.3 | ColumnoutputGroup | read-write | current | The group number (1...63) assigned to each channel. If commands shall be sent to all channels with a specific group number (e.g. with the groupsSwitch command … |
| 1.3.6.1.4.1.19947.1.3.2.1.4 | ColumnoutputStatus | read-only | current | A bit string which shows the status (health and operating conditions) of one output channel. If a bit is set (1), the explanation is satisfied: outputOn (0), o… |
| 1.3.6.1.4.1.19947.1.3.2.1.5 | ColumnoutputMeasurementSenseVoltage | read-only | current | The measured voltage at the sense input lines. |
| 1.3.6.1.4.1.19947.1.3.2.1.6 | ColumnoutputMeasurementTerminalVoltage | read-only | current | The measured voltage at the output terminals. |
| 1.3.6.1.4.1.19947.1.3.2.1.7 | ColumnoutputMeasurementCurrent | read-only | current | The measured output current. |
| 1.3.6.1.4.1.19947.1.3.2.1.8 | ColumnoutputMeasurementTemperature | read-only | current | The measured temperature of the power module. |
| 1.3.6.1.4.1.19947.1.3.2.1.9 | ColumnoutputSwitch | read-write | current | Read: An enumerated value which shows the current state of the output channel. Write: Change the state of the channel. If the channel is On, and the write valu… |
| 1.3.6.1.4.1.19947.1.3.2.1.10 | ColumnoutputVoltage | read-write | current | The nominal output voltage of the channel. |
| 1.3.6.1.4.1.19947.1.3.2.1.11 | ColumnoutputAdjustVoltage | read-write | obsolete | A posibillity to make small changes of the output voltage. |
| 1.3.6.1.4.1.19947.1.3.2.1.12 | ColumnoutputCurrent | read-write | current | The current limit of the channel. |
| 1.3.6.1.4.1.19947.1.3.2.1.13 | ColumnoutputVoltageRiseRate | read-write | current | Voltage Fall Slew Rate [V/s]. The slew rate of the output voltage if it increases (after switch on or if the Voltage has been changed). |
| 1.3.6.1.4.1.19947.1.3.2.1.14 | ColumnoutputVoltageFallRate | read-write | current | Voltage Rise Slew Rate [V/s]. The slew rate of the output voltage if it decreases (after switch off or if the Voltage has been changed). |
| 1.3.6.1.4.1.19947.1.3.2.1.15 | ColumnoutputSupervisionBehavior | read-write | current | A bit field packed into an integer which define the behavior of the output channel / power supply after failures. For each supervision value, a two-bit field e… |
| 1.3.6.1.4.1.19947.1.3.2.1.16 | ColumnoutputSupervisionMinSenseVoltage | read-write | current | If the measured sense voltage is below this value, the power supply performs the function defined by SupervisionAction. |
| 1.3.6.1.4.1.19947.1.3.2.1.17 | ColumnoutputSupervisionMaxSenseVoltage | read-write | current | If the measured sense voltage is above this value, the power supply performs the function defined by SupervisionAction. |
| 1.3.6.1.4.1.19947.1.3.2.1.18 | ColumnoutputSupervisionMaxTerminalVoltage | read-write | current | If the measured voltage at the power supply output terminals is above this value, the power supply performs the function defined by SupervisionAction. |
| 1.3.6.1.4.1.19947.1.3.2.1.19 | ColumnoutputSupervisionMaxCurrent | read-write | current | If the measured current is above this value, the power supply performs the function defined by SupervisionAction. |
| 1.3.6.1.4.1.19947.1.3.2.1.20 | ColumnoutputSupervisionMaxTemperature | read-write | current | If the measured module temperature is above this value, the power supply performs the function defined by SupervisionAction. |
| 1.3.6.1.4.1.19947.1.3.2.1.21 | ColumnoutputConfigMaxSenseVoltage | read-write | current | The maximum possible value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.22 | ColumnoutputConfigMaxTerminalVoltage | read-write | current | The maximum possible value of the terminal voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.23 | ColumnoutputConfigMaxCurrent | read-write | current | The maximum possible value of the output current |
| 1.3.6.1.4.1.19947.1.3.2.1.24 | ColumnoutputSupervisionMaxPower | read-write | current | If the measured power (measured current * measured terminal voltage) is above this value, the power supply performs the function defined by SupervisionAction. |
| 1.3.6.1.4.1.19947.1.3.2.1.25 | ColumnoutputCurrentRiseRate | read-write | current | Current Fall Slew Rate [A/s]. The slew rate of the output current if it increases (after switch on or if the Current has been changed). |
| 1.3.6.1.4.1.19947.1.3.2.1.26 | ColumnoutputCurrentFallRate | read-write | current | Current Rise Slew Rate [A/s]. The slew rate of the output current if it decreases (after switch off or if the Current has been changed). |
| 1.3.6.1.4.1.19947.1.3.2.1.27 | ColumnoutputTripTimeMaxCurrent | read-write | current | Minimum time the outputSupervisionMaxCurrent threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavi… |
| 1.3.6.1.4.1.19947.1.3.2.1.28 | ColumnoutputHardwareLimitVoltage | read-only | current | Hardware Voltage Limit [V]. Potentiometer to adjust the global hardware voltage limit (for all channels of a module). |
| 1.3.6.1.4.1.19947.1.3.2.1.29 | ColumnoutputHardwareLimitCurrent | read-only | current | Hardware Current Limit [A]. Potentiometer to adjust the global hardware current limit (for all channels of a module). |
| 1.3.6.1.4.1.19947.1.3.2.1.30 | ColumnoutputConfigGainSenseVoltage | read-write | current | The gain value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.31 | ColumnoutputConfigOffsetSenseVoltage | read-write | current | The offset value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.32 | ColumnoutputConfigGainTerminalVoltage | read-write | current | The gain value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.33 | ColumnoutputConfigOffsetTerminalVoltage | read-write | current | The offset value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.34 | ColumnoutputConfigGainCurrent | read-write | current | The gain value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.35 | ColumnoutputConfigOffsetCurrent | read-write | current | The offset value of the sense voltage |
| 1.3.6.1.4.1.19947.1.3.2.1.37 | ColumnoutputUserConfig | read-write | current | Definition of user-changeable items. A bit field packed into an integer which define the behavior of the output channel. Usable for WIENER LV devices only. The… |
| 1.3.6.1.4.1.19947.1.3.2.1.38 | ColumnoutputRegulationMode | read-write | current | Definition of the regulation mode. Deprecated, use outputUserConfig for this function in the future! It is possible to set different regulation modes, dependen… |
| 1.3.6.1.4.1.19947.1.3.2.1.39 | ColumnoutputConfigMaxTemperature | read-write | current | The maximum possible value of outputSupervisionMaxTemperature. |
| 1.3.6.1.4.1.19947.1.3.2.1.40 | ColumnoutputResistance | read-write | current | Item to specify an external resistor. For instance a wire resistor or an external resistor to protect the detectot which is supplied by a cascaded HV module. |
| 1.3.6.1.4.1.19947.1.3.2.1.41 | ColumnoutputTripTimeMinSenseVoltage | read-write | current | Minimum time the outputSupervisionMinSenseVoltage threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionB… |
| 1.3.6.1.4.1.19947.1.3.2.1.42 | ColumnoutputTripTimeMaxSenseVoltage | read-write | current | Minimum time the outputSupervisionMaxSenseVoltage threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionB… |
| 1.3.6.1.4.1.19947.1.3.2.1.43 | ColumnoutputTripTimeMaxTerminalVoltage | read-write | current | Minimum time the outputSupervisionMaxTerminalVoltage threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisi… |
| 1.3.6.1.4.1.19947.1.3.2.1.44 | ColumnoutputTripTimeMaxTemperature | read-write | current | Minimum time the outputSupervisionMaxTemperature threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBe… |
| 1.3.6.1.4.1.19947.1.3.2.1.45 | ColumnoutputTripTimeMaxPower | read-write | current | Minimum time the outputSupervisionMaxPower threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior… |
| 1.3.6.1.4.1.19947.1.3.2.1.46 | ColumnoutputTripTimeTimeout | read-write | current | Maximum time the communication between module and controller can paused before activation the trip action [ms]. The trip action is defined in outputSupervision… |
| 1.3.6.1.4.1.19947.1.3.2.1.47 | ColumnoutputTripActionMinSenseVoltage | read-write | current | Trip action if outputSuperisionMinSenseVoltage threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this c… |
| 1.3.6.1.4.1.19947.1.3.2.1.48 | ColumnoutputTripActionMaxSenseVoltage | read-write | current | Trip action if outputSuperisionMaxSenseVoltage threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this c… |
| 1.3.6.1.4.1.19947.1.3.2.1.49 | ColumnoutputTripActionMaxTerminalVoltage | read-write | current | Trip action if outputSuperisionMaxTerminalVoltage threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off thi… |
| 1.3.6.1.4.1.19947.1.3.2.1.50 | ColumnoutputTripActionMaxCurrent | read-write | current | Trip action if outputSuperisionMaxCurrent threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channe… |
| 1.3.6.1.4.1.19947.1.3.2.1.51 | ColumnoutputTripActionMaxTemperature | read-write | current | Trip action if outputSuperisionMaxTemperature threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this ch… |
| 1.3.6.1.4.1.19947.1.3.2.1.52 | ColumnoutputTripActionMaxPower | read-write | current | Trip action if outputSuperisionMaxPower threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel … |
| 1.3.6.1.4.1.19947.1.3.2.1.53 | ColumnoutputTripActionExternalInhibit | read-write | current | Trip action if the external inhibit input has been activated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switc… |
| 1.3.6.1.4.1.19947.1.3.2.1.54 | ColumnoutputTripActionTimeout | read-write | current | Trip action if the communication between module and controller has been paused longer than outputTripTimeTimeout. The enumerated value is: WIENER LV devices 0 … |
| 1.3.6.1.4.1.19947.1.3.2.1.1024 | ColumnoutputConfigDataS | read-write | current | Configuration Data raw access. This allows to read / write output channel specific user configuration data. This OID is intended for use by WIENER system softw… |
| 1.3.6.1.4.1.19947.1.3.2.1.1025 | ColumnoutputConfigDataU | read-write | current | Configuration Data raw access. This allows to read / write output channel specific user configuration data. This OID is intended for use by WIENER system softw… |
| 1.3.6.1.4.1.19947.1.3.3 | ScalargroupsNumber | read-only | current | The number of output groups of the crate. |
| 1.3.6.1.4.1.19947.1.3.4 | TablegroupsTable | not-accessible | current | A list of output groups entries. |
| 1.3.6.1.4.1.19947.1.3.4.1 | RowgroupsEntry | not-accessible | current | A table row |
| 1.3.6.1.4.1.19947.1.3.4.1.1 | ColumngroupsIndex | not-accessible | current | A unique number for each power output group. Its value ranges between 1 and 1999. The special group 0 is predefined and gives access to all channels. |
| 1.3.6.1.4.1.19947.1.3.4.1.9 | ColumngroupsSwitch | read-write | current | Read: This function is not defined with groups of output channels. Write: Switch the state of all channels of a group. If any channel is On, and the write valu… |
| 1.3.6.1.4.1.19947.1.3.5 | ScalarmoduleNumber | read-only | current | The number of HV/LV modules of the crate. |
| 1.3.6.1.4.1.19947.1.3.6 | TablemoduleTable | not-accessible | current | A list of output module entries. |
| 1.3.6.1.4.1.19947.1.3.6.1 | RowmoduleEntry | not-accessible | current | A row in the table of HV/LV modules |
| 1.3.6.1.4.1.19947.1.3.6.1.1 | ColumnmoduleIndex | not-accessible | current | A unique number for each HV/LV module. Its value ranges between 1 and the total number of HV/LV modules. Note, index 1 corresponds to ma0. |
| 1.3.6.1.4.1.19947.1.3.6.1.2 | ColumnmoduleDescription | read-only | current | Vendor, FirmwareName, ChannelNumber, SerialNumber, FirmwareRelease Vendor WIENER or iseg FirmwareName: 'E16D0' EDS 16 channels per PCB, distributor module, ran… |
| 1.3.6.1.4.1.19947.1.3.6.1.3 | IdentitymoduleAuxiliaryMeasurementVoltage | current | The measured module auxiliary voltages. | |
| 1.3.6.1.4.1.19947.1.3.6.1.3.1 | ScalarmoduleAuxiliaryMeasurementVoltage0 | read-only | current | The measured module auxiliary voltage. |
| 1.3.6.1.4.1.19947.1.3.6.1.3.2 | ScalarmoduleAuxiliaryMeasurementVoltage1 | read-only | current | The measured module auxiliary voltage. |
| 1.3.6.1.4.1.19947.1.3.6.1.4 | ColumnmoduleHardwareLimitVoltage | read-only | current | The module hardware voltage limit. |
| 1.3.6.1.4.1.19947.1.3.6.1.5 | ColumnmoduleHardwareLimitCurrent | read-only | current | The module hardware current limit. |
| 1.3.6.1.4.1.19947.1.3.6.1.6 | ColumnmoduleRampSpeedVoltage | read-write | current | The module voltage ramp speed (iseg HV modules have the same ramp speed value for all channels). |
| 1.3.6.1.4.1.19947.1.3.6.1.7 | ColumnmoduleRampSpeedCurrent | read-write | current | The module current ramp speed (iseg HV modules have the same ramp speed value for all channels). |
| 1.3.6.1.4.1.19947.1.3.6.1.8 | ColumnmoduleStatus | read-only | current | A bit string which shows the current module status. If a bit is set (1), the explanation is satisfied: moduleIsFineAdjustment (0), Module has reached state fin… |
| 1.3.6.1.4.1.19947.1.3.6.1.9 | ColumnmoduleEventStatus | read-only | current | A bit string which shows the current module status. If a bit is set (1), the explanation is satisfied: moduleEventPowerFail (0), Event power fail generated by … |
| 1.3.6.1.4.1.19947.1.3.6.1.10 | ColumnmoduleEventChannelStatus | read-only | current | Bit field that reserves one bit for every channel. bit 0 HV channel 0 bit 1 HV channel 1 bit x HV channel x |
| 1.3.6.1.4.1.19947.1.3.6.1.11 | ColumnmoduleDoClear | read-write | current | All events of the module will be cleared. |
| 1.3.6.1.4.1.19947.1.3.6.1.12 | IdentitymoduleAuxiliaryMeasurementTemperature | current | The number of auxiliary temperature sensors in the module. | |
| 1.3.6.1.4.1.19947.1.3.6.1.12.1 | ScalarmoduleAuxiliaryMeasurementTemperature0 | read-only | current | The measured module temperature of sensor 1. |
| 1.3.6.1.4.1.19947.1.3.6.1.12.2 | ScalarmoduleAuxiliaryMeasurementTemperature1 | read-only | current | The measured module temperature of sensor 2. |
| 1.3.6.1.4.1.19947.1.3.6.1.12.3 | ScalarmoduleAuxiliaryMeasurementTemperature2 | read-only | current | The measured module temperature of sensor 3. |
| 1.3.6.1.4.1.19947.1.3.6.1.12.4 | ScalarmoduleAuxiliaryMeasurementTemperature3 | read-only | current | The measured module temperature of sensor 4. |
| 1.3.6.1.4.1.19947.1.3.6.1.1024 | ColumnmoduleConfigDataS | read-write | current | Configuration Data raw access. This allows to read / write output channel specific system configuration data. This OID is intended for use by WIENER system sof… |
| 1.3.6.1.4.1.19947.1.3.6.1.1025 | ColumnmoduleConfigDataU | read-write | current | Configuration Data raw access. This allows to read / write output channel specific user configuration data. This OID is intended for use by WIENER system softw… |
| 1.3.6.1.4.1.19947.1.4 | Identitysensor | current | All objects which are associated with temperature sensors in the crate | |
| 1.3.6.1.4.1.19947.1.4.1 | ScalarsensorNumber | read-only | current | The number of temperature sensors of the crate. |
| 1.3.6.1.4.1.19947.1.4.2 | TablesensorTable | not-accessible | current | A (conceptual table) of temperature sensor data. |
| 1.3.6.1.4.1.19947.1.4.2.1 | RowsensorEntry | not-accessible | current | An entry (conceptual row) of the sensorTable. |
| 1.3.6.1.4.1.19947.1.4.2.1.1 | ColumnsensorIndex | not-accessible | current | A unique number for each temperature sensor in the crate |
| 1.3.6.1.4.1.19947.1.4.2.1.2 | ColumnsensorTemperature | read-only | current | The measured temperature of the sensor. Unused temperature probes have the special value -128 |
| 1.3.6.1.4.1.19947.1.4.2.1.3 | ColumnsensorWarningThreshold | read-write | current | If the measured temperature of the sensor is higher than this value, the fan speed of the connected fan tray is increased. The value 127 has the special meanin… |
| 1.3.6.1.4.1.19947.1.4.2.1.4 | ColumnsensorFailureThreshold | read-write | current | If the measured temperature of the sensor is higher than this value, the power supply switches off. The value 127 has the special meaning: channel disabled. |
| 1.3.6.1.4.1.19947.1.4.2.1.6 | ColumnsensorAlarmThreshold | read-write | current | If the measured temperature of the sensor is much higher than this value, the fans rotate in full speed. The value 127 has the special meaning: channel disable… |
| 1.3.6.1.4.1.19947.1.4.2.1.7 | ColumnsensorName | read-write | current | A textual string containing a short name of the sensor. If the crate is equipped with an alphanumeric display, this string is shown to identify a sensor channe… |
| 1.3.6.1.4.1.19947.1.4.2.1.8 | ColumnsensorID | read-write | current | Shows the 1-Wire Id of the corresponding Sensor. |
| 1.3.6.1.4.1.19947.1.4.2.1.9 | ColumnsensorStatus | read-only | current | A bit field packed into an integer which define the Status of the Sensors after failures. For each Status value, a two-bit field exists. Bits-Value 00 Temperat… |
| 1.3.6.1.4.1.19947.1.5 | Identitycommunication | current | All objects which affect the remote control of the crate | |
| 1.3.6.1.4.1.19947.1.5.1 | Identitysnmp | current | SNMP configuration. | |
| 1.3.6.1.4.1.19947.1.5.1.1 | TablesnmpCommunityTable | not-accessible | current | The SNMP community string table for different views. |
| 1.3.6.1.4.1.19947.1.5.1.1.1 | RowsnmpCommunityEntry | not-accessible | current | One table row. |
| 1.3.6.1.4.1.19947.1.5.1.1.1.1 | ColumnsnmpAccessRight | not-accessible | current | A unique number for each access right |
| 1.3.6.1.4.1.19947.1.5.1.1.1.2 | ColumnsnmpCommunityName | read-write | current | The SNMP community names for different views. The rights of the different communities are: public no write access private can switch power on/off, generate sys… |
| 1.3.6.1.4.1.19947.1.5.1.2 | ScalarsnmpPort | read-write | current | The UDP port number of the SNMP protocol. A value of 0 disables all future SNMP communication! |
| 1.3.6.1.4.1.19947.1.5.1.3 | ScalarhttpPort | read-write | current | The TCP port number of the HTTP (web) protocol. A value of 0 disables all HTTP access. |
| 1.3.6.1.4.1.19947.1.5.1.10 | ScalarfirmwareUpdate | read-write | current | Send a update String |
| 1.3.6.1.4.1.19947.1.5.1.11 | ScalaripDynamicAddress | read-only | current | Shows the Ip which is currently used |
| 1.3.6.1.4.1.19947.1.5.1.12 | ScalaripStaticAddress | read-write | current | Shows the Ip which is setted by user |
| 1.3.6.1.4.1.19947.1.5.1.13 | ScalarmacAddress | read-write | current | Shows the MAC of the corresponding device |
| 1.3.6.1.4.1.19947.1.5.2 | Identitycan | current | CAN-Bus tunnel via SNMP. | |
| 1.3.6.1.4.1.19947.1.5.2.1 | ScalarcanBitRate | read-write | current | Control of the CAN-Bus. The value defines the bit rate of the CAN-bus interface. A write disconnects the CAN interface from the ISEG modules and connects it to… |
| 1.3.6.1.4.1.19947.1.5.2.2 | ScalarcanReceive | read-only | current | Control of the CAN-Bus Receive FIFO. A read access returns the total number of CAN messages stored in the receive fifo and the oldest message. This message is … |
| 1.3.6.1.4.1.19947.1.5.2.3 | ScalarcanTransmit | read-write | current | Control of the CAN-Bus Transmit FIFO. A read access returns the total number of CAN messages stored in the transmit fifo and a NULL message. A write inserts th… |
| 1.3.6.1.4.1.19947.1.5.2.4 | ScalarcanReceiveHv | read-only | current | Control of the internal HV CAN-Bus on the backplane Receive FIFO. A read access returns the total number of CAN messages stored in the receive fifo and the old… |
| 1.3.6.1.4.1.19947.1.5.2.5 | ScalarcanTransmitHv | read-write | current | Control of the internal HV CAN-Bus on the backplane. A write access with: CANID=0x600 DLC=4 DATAID=0x1001 CONTROL will switch the HV modules into a special sta… |
| 1.3.6.1.4.1.19947.1.5.2.6 | ScalarcanBitRateHv | read-write | current | Control of the bit rate of the HV CAN-Bus. The value defines the bit rate of the CAN-bus interface. Possible Values are 125000 and 250000. Changing this value … |
| 1.3.6.1.4.1.19947.1.6 | Identitypowersupply | current | All objects which are specific for the power supply of the crate | |
| 1.3.6.1.4.1.19947.1.6.2 | ScalarpsSerialNumber | read-only | current | The serial number of the power supply. |
| 1.3.6.1.4.1.19947.1.6.3 | ScalarpsOperatingTime | read-write | current | The time in seconds for how long the power supply was switched on. |
| 1.3.6.1.4.1.19947.1.6.4 | ScalarpsAuxiliaryNumber | read-only | current | The number of auxiliary channels of the power supply. |
| 1.3.6.1.4.1.19947.1.6.5 | TablepsAuxiliaryTable | not-accessible | current | A list of psAuxiliary entries. |
| 1.3.6.1.4.1.19947.1.6.5.1 | RowpsAuxiliaryEntry | not-accessible | current | A table row |
| 1.3.6.1.4.1.19947.1.6.5.1.1 | ColumnpsAuxiliaryIndex | not-accessible | current | A unique number for each power supply auxiliary channel. Its value ranges between 1 and total number of output channels. SMI index starts at 1, so index 1 corr… |
| 1.3.6.1.4.1.19947.1.6.5.1.3 | ColumnpsAuxiliaryMeasurementVoltage | read-only | current | The measured power supply auxiliary output voltage. |
| 1.3.6.1.4.1.19947.1.6.5.1.4 | ColumnpsAuxiliaryMeasurementCurrent | read-only | current | The measured power supply auxiliary output current. |
| 1.3.6.1.4.1.19947.1.6.1024 | ScalarpsDirectAccess | read-write | current | Direct data transfer to the UEP6000 power supply. A read access returns nothing, a write access returns the response of the power supply. |
| 1.3.6.1.4.1.19947.1.7 | Identityfantray | current | All objects which are specific for the fan tray of the crate | |
| 1.3.6.1.4.1.19947.1.7.2 | ScalarfanSerialNumber | read-write | current | The serial number of the fan tray. |
| 1.3.6.1.4.1.19947.1.7.3 | ScalarfanOperatingTime | read-write | current | The time in seconds for how long the fan tray was switched on. |
| 1.3.6.1.4.1.19947.1.7.4 | ScalarfanAirTemperature | read-only | current | The temperature of the fan tray inlet air. |
| 1.3.6.1.4.1.19947.1.7.5 | ScalarfanSwitchOffDelay | read-write | current | The maximum time in seconds for which the fans will continue running after the power supply has been switched off. This feature is used to cool down the electr… |
| 1.3.6.1.4.1.19947.1.7.6 | ScalarfanNominalSpeed | read-write | current | The nominal fan rotation speed (RPM, Revolutions Per Minute) Value 0 does switch off the fans (only allowed if at least one rack temperature sensor is present)… |
| 1.3.6.1.4.1.19947.1.7.7 | ScalarfanNumberOfFans | read-write | current | The number of installed fans |
| 1.3.6.1.4.1.19947.1.7.8 | TablefanSpeedTable | not-accessible | current | A list of fanSpeedEntries. |
| 1.3.6.1.4.1.19947.1.7.8.1 | RowfanSpeedEntry | not-accessible | current | A table row |
| 1.3.6.1.4.1.19947.1.7.8.1.1 | ColumnfanNumber | not-accessible | current | A unique number for each fan. |
| 1.3.6.1.4.1.19947.1.7.8.1.2 | ColumnfanSpeed | read-only | current | The measured fan rotation speed (RPM, Revolutions Per Minute) |
| 1.3.6.1.4.1.19947.1.7.9 | ScalarfanMaxSpeed | read-write | current | The highest allowed rotationspeed of fan. |
| 1.3.6.1.4.1.19947.1.7.10 | ScalarfanMinSpeed | read-write | current | The lowest allowed Rotationspeed of fan. |
| 1.3.6.1.4.1.19947.1.7.11 | ScalarfanConfigMaxSpeed | read-write | current | Hardwarelimits. Can only set by WIENER. |
| 1.3.6.1.4.1.19947.1.7.12 | ScalarfanConfigMinSpeed | read-write | current | Hardwarelimits Can only set by WIENER. |
| 1.3.6.1.4.1.19947.1.8 | Identityrack | current | All objects which are specific for the crate (BIN) of the crate | |
| 1.3.6.1.4.1.19947.1.9 | Identitysignal | current | All objects which are associated with analog/digtal input/output in the crate | |
| 1.3.6.1.4.1.19947.1.9.1 | ScalarnumberOfAnalogInputs | read-only | current | The number of additional analog inputs of the crate. |
| 1.3.6.1.4.1.19947.1.9.2 | TableanalogInputTable | not-accessible | current | A (conceptual table) of analog input data. |
| 1.3.6.1.4.1.19947.1.9.2.1 | RowanalogInputEntry | not-accessible | current | An entry (conceptual row) of the analogInputTable. |
| 1.3.6.1.4.1.19947.1.9.2.1.1 | ColumnanalogInputIndex | not-accessible | current | A unique number for each analog input of the crate |
| 1.3.6.1.4.1.19947.1.9.2.1.2 | ColumnanalogMeasurementVoltage | read-only | current | The measured voltage of the analog input. |
| 1.3.6.1.4.1.19947.1.9.2.1.3 | ColumnanalogMeasurementCurrent | read-only | current | The measured current of the analog input. |
| 1.3.6.1.4.1.19947.1.9.5 | ScalardigitalInput | read-only | current | The value of the digital inputs. |
| 1.3.6.1.4.1.19947.1.9.6 | ScalardigitalOutput | read-only | current | The value of the digital outputs. |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| Float | Opaque (SIZE (7)) | current | A single precision floating-point number. The semantics and encoding are identical for type 'single' defined in IEEE Standard for Binary Floating-Point, ANSI/IEEE Std 754-1985. The value is restricted to the BER seriali… |
| OutputTripAction | INTEGER { ignore (0), channelOff (1), specialOff (2), allOff (3) } crate OBJECT-IDENTITY STATUS current DESCRIPTION "SNMP control for electronic crates. A crate is a complete electronic system and consists of the mechanical rack, a power supply, a fan tray and a backplane. All this things are necessary to provide an adequate housing for electronic modules (e.g. VME CPU's)" ::= { wiener 1 } system OBJECT-IDENTITY STATUS current DESCRIPTION "A collection of objects which affect the complete crate" ::= { crate 1 } input OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are associated with the power input of the crate" ::= { crate 2 } output OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are associated with the power output of the crate" ::= { crate 3 } sensor OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are associated with temperature sensors in the crate" ::= { crate 4 } communication OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which affect the remote control of the crate" ::= { crate 5 } powersupply OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are specific for the power supply of the crate" ::= { crate 6 } fantray OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are specific for the fan tray of the crate" ::= { crate 7 } rack OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are specific for the crate (BIN) of the crate" ::= { crate 8 } signal OBJECT-IDENTITY STATUS current DESCRIPTION "All objects which are associated with analog/digtal input/output in the crate" ::= { crate 9 } System ::= SEQUENCE { sysMainSwitch INTEGER, sysStatus BITS, sysVmeSysReset INTEGER, sysHardwareReset Integer32, sysFactoryDefaults INTEGER, sysConfigDoMeasurementCurrent BITS, sysOperatingTime Integer32, sysDebugMemory8 Integer32, sysDebugMemory16 Integer32, sysDebugMemory32 Integer32, sysDebug OCTET STRING, sysDebugDisplay OCTET STRING, sysDebugBoot OCTET STRING } | current | Special data type used for outpot trip action OIDs. |
| OutputTripTime | Integer32 (0..65535) | current | Special data type used for output trip time OIDs. Represents a 16 bit unsigned integer value. BER-coded as INTEGER |