MIB Viewer

puConfigShutdownInterval

OBJECT-TYPE
1.3.6.1.4.1.11096.6.1.1.1.1.2.1.3
Access
read-only
Status
obsolete
Sub-identifiers
0
This variable is used in conjunction with puConfigShutdownRemainingLife such that when either condition is met a controlled shutdown will take place. puConfigShutdownInterval specifies the interval after which a controlled shutdown should take place in the event of a power outage. remainingLife(1) - indicates that the shutdown is based on the remaining battery life only and NOT the duration of the power outage. The variable puConfigShutdownRemainingLife determines how the shutdown is controlled. immediately(2) - the shutdown should take place as soon as the power outage is detected. The variable puConfigRemainingLife is irrelevant in this case. oneMinute(3), twoMinutes(4), threeMinutes(5), - the interval after which a controlled fiveMinutes(6), shutdown should take place in the event of tenMinutes(7) a power outage. NOTE: the variable puConfigShutdownEnabled must be enabled(1), for this variable to have any effect in determining when the controlled shutdown is performed. This object is obsolete. Power units must be indexed by IP address.
INTEGER { remainingLife(1), immediately(2), oneMinute(3), twoMinutes(4), threeMinutes(5), fiveMinutes(6), tenMinutes(7) }