MIB Viewer

aimosMasterV1HeartbeatInterval

OBJECT-TYPE
1.3.6.1.4.1.6408.201.3.5.13.1.3
Access
read-write
Status
current
Source
AIMOS
Sub-identifiers
0
Alternatively to a regular polling of the Master Controllers by an SNMP Manager, the Master Controller is capable of sending a regular 'I'm-alive-message' to the A.I.M.O.S. SNMP Agent. In this way, the A.I.M.O.S. SNMP Agent will recognise a failure of the Master Controller when the message is no longer sent and can consequently generate and send out a aimosAlarmNew notification with the objects aimosAlarmListAlarmID set to alarmHeartbeatMissing(63) and aimosAlarmListSpecificProblem set to 8888. aimosMasterV1HeartbeatInterval is an object of type WeekMinutes, by which the interval at which the Master Controller is to send this 'life sign' can be set. Values from 0 up to 10.080 are allowed. Setting 0 deactivates the Heartbeat feature, the highest setting 10.080 sets the interval to one week.
WeekMinutes