MIB Viewer

sysStatus

OBJECT-TYPE
1.3.6.1.4.1.19947.1.1.2
Access
read-only
Status
current
Sub-identifiers
0
A bit string which shows the status (health) of the complete crate. If a bit is set (1), the explanation is satisfied mainOn (0), system is switched on, individual outputs may be controlled by their specific ON/INHIBIT mainInhibit(1), external (hardware-)inhibit of the complete system localControlOnly (2), local control only (CANBUS write access denied) inputFailure (3), any input failure (e.g. power fail) outputFailure (4), any output failure, details in outputTable fantrayFailure (5), fantray failure sensorFailure (6), temperature of the external sensors too high vmeSysfail(7), VME SYSFAIL signal is active plugAndPlayIncompatible (8) wrong power supply and rack connected busReset (9) The sytem bus (e.g. VME or CPCI) reset signal is active. supplyDerating (10) The (first) system power supply has the DEG signal active. supplyFailure (11) The (first) system power supply has the FAL signal active. supplyDerating2 (12) The second system power supply has the DEG signal active. supplyFailure2 (13) The second system power supply has the FAL signal active.
BITS { mainOn (0) , mainInhibit (1) , localControlOnly (2) , inputFailure (3) , outputFailure (4) , fantrayFailure (5) , sensorFailure (6), vmeSysfail (7), plugAndPlayIncompatible (8), busReset (9), supplyDerating (10), supplyFailure (11), supplyDerating2 (12), supplyFailure2 (13) }